Application of digital power quality online monitoring system in power system

Publisher:巳午未Latest update time:2010-04-10 Source: 北极星电力网 Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

The online power quality monitoring equipment is the most basic and most important equipment in the power quality supervision and detection network of the power grid. At present, most of the monitoring equipment for some power quality indicators (such as harmonics, imbalance, etc.) produced at home and abroad and sold and used in the market cannot fully meet the actual needs of power quality supervision and management in my country's power grid. In 1996, the southern power grid in Hebei Province began to install harmonic online monitoring devices. The initial devices had many problems in data storage, data transmission and background statistical analysis. In order to meet the growing needs of power quality supervision, based on several years of operating experience and experience, a digital power quality online monitoring terminal was developed.

The new digital power quality online monitoring device has the functions of collecting various power quality parameters according to national standards, high reliability of long-term online operation, convenient and practical on-site operation, and communication with the central station. At the same time, it can also record and store data for a long time and read data conveniently. The device adopts the DSP digital signal processor and high-speed multi-channel AD simultaneous sampling technology equivalent to the latest foreign products, and uses PC104 industrial computer for data processing, display and storage. It has powerful functions, easy operation and software upgrade.

1 Function and composition

The power grid power quality monitoring system consists of power quality monitoring terminals, central stations and analysis software.

1.1 Power quality monitoring terminal For information, please visit: Power Transmission and Distribution Equipment Network

Input three-phase voltage 100V, three-phase current 5A or 1A for data signal processing, and use FFT to calculate the amplitude and phase angle of each harmonic voltage and current. Calculate unbalanced voltage and current, calculate and display technical data such as three-phase voltage, current, voltage qualification rate, frequency, active power, reactive power and power factor. Responsible for data processing, storage, communication connection and data transmission with the central station, and form substation reports.

The main functions of the power quality monitoring terminal are as follows:

a. The input signal is TV, TA secondary side three-phase voltage (100V), three-phase current (5A or 1A).

b. With a public telephone MODEM interface, you can easily dial in and receive data at the central station.

c. Large screen (320×240) backlit LCD graphic display. Information source: http://www.tede.cn

d. Chinese graphics (spectrum diagram, waveform diagram, curve diagram, vector diagram) operation interface.

e. The terminal can store data for more than one year, and the stored data is a group of data packets of 3 minutes or 5 minutes.

f. With LAN connection interface, data can be transcribed on site using a laptop.

g.Multi-parameter comprehensive measurement, real-time fixed-point alarm, and parameter value and parameter alarm status can be set.

h. Harmonic voltage, current, negative sequence voltage, current over-limit alarm output relay.  Information from: www.tede.cn

1.2 Central Station and Analysis Software Information from: www.tede.cn

The central station receives data from the processor through a modem or network, performs statistical analysis, forms files, reports and curves, and can display data and graphics (such as spectrum diagrams, waveform diagrams, curve diagrams, vector diagrams, etc.). It can manage multiple power quality monitoring terminals, analyze and process the collected data, analyze and form reports for the power quality of a certain period of time or a certain event process period, automatically form daily, monthly and annual reports, automatically find out the time periods and lines where the harmonic content rate exceeds the standard, and calculate the voltage qualification rate and power supply reliability.

The central station is a client-server mode, and the data is stored in the server's database, which can be easily called and queried.

2 Main technical indicators Information source: http://www.tede.cn

2.1 Measurement items Information from: Power Transmission and Distribution Equipment Network

The device uses (220±15%)Vac or [(220 +10%)~(220-15%)>Vdc power supply. The measurable items include: voltage, current, frequency, voltage qualification rate, active power, reactive power, apparent power, power factor, voltage unbalance, current unbalance, harmonic voltage, harmonic current (up to 31/50 or higher), harmonic phase, harmonic power, distortion rate, etc.

2.2 Measurement accuracy

Voltage measurement: ±0.2%

Current measurement: ±0.2%

Voltage unbalance measurement error: ≤0.2% For information, please visit: Power Transmission and Distribution Equipment Network

Current unbalance measurement error: ≤1%

Frequency measurement: 47~53 Hz, accuracy is ±0.01Hz(50Hz)

Signal conversion accuracy: 14bit 

Sampling frequency: 8kHz/channel Information from: www.tede.cn

3. Software/Hardware Composition of Power Quality Monitoring Terminal

The hardware of the power quality monitoring terminal consists of TA/TV and signal preprocessing, DSP processor, PC104 industrial computer, PC104 and DSP parallel communication ISA bus parallel expansion, modem, LCD display (VGA monochrome with backlight), network adapter, power supply, etc.

The software of the power quality monitoring terminal consists of DSP software and PC104 software.

3.1 DSP software

3.1.1 DSP Principle

The monitoring terminal uses the TMS320F240 chip of TI's 320C2XX series. Considering the limited internal storage capacity of the chip, high-speed SRAM and EEPROM are expanded in the DSP part. The final design of the system requires the acquisition of 1024 points (6 channels at the same time) in each power frequency cycle, and the 6-channel radix 2 FFT transformation calculation of 1024 points is required and transmitted to the PC104 processing unit, which requires a faster clock frequency. In this device, the internal clock of the DSP is nearly 40MHz.

A fast 14-bit high-precision AD converter is added to the DSP processing part. This AD converter can perform 6-channel simultaneous sampling, which guarantees the accurate calculation of active power, reactive power, and positive/negative sequence.

3.1.2 Composition and Function of DSP

a. Data acquisition part, including frequency sampling and calculation, and 6-channel simultaneous sampling of AD converter.

b. Data processing, converting the format of collected data.

c.FFT transformation calculation.

d. Data transmission: transfer DSP data to PC104.

3.1.3 Input and Operation Information from: Power Transmission and Distribution Equipment Network

Input three-phase voltage and current, measure frequency, 1024 or 512-point AD conversion (AD uses dual 6-channel high-speed AD converter), after FFT transformation, calculate the RMS value, and upload data. According to needs, only 31 or 61 harmonics or higher harmonics are transmitted during data transmission. Information from: www.tede.cn

Perform FFT operation, take 31st (or 61st) harmonics every 0.5s, and calculate the RMS value 6 times every 3s.

3.1.4 Data Transmission

According to the pulse given by the host computer every 0.5s, data is uploaded every 3s. Taking the 31st harmonic as an example, each group of data is as follows.

Each harmonic is divided into real part and imaginary part, with the phase of Ua as the reference phase.

3.2 PC104 part

The PC104 industrial control board uses a highly integrated PCM-3336 board, which has floppy disk and hard disk interfaces, can directly drive a 320×240 LCD monochrome display, 2 RS232C serial interfaces, 1 printer parallel interface, and can directly connect a keyboard and a normal display. The BIO design of the board can connect a hard disk up to 15G. For ease of use and reliability, the hard disk uses an electronic disk or a notebook hard disk.

The industrial control board has a WATCH-DOG function, which will automatically reset when it does not work properly.

The PC104 board is responsible for data processing, storage, and display, as well as the communication connection and data transmission between the power quality monitoring terminal and the central station, and forms a substation report. It sends a 0.5 s pulse to the DSP to collect DSP data.

3.2.1 PC104 software composition

a. Calculate and process various data, including voltage, current, active power, reactive power, positive and negative sequence, voltage imbalance, voltage qualification rate, harmonic content rate, etc.

b. Graphically display the voltage, current fundamental wave and the amplitude and phase angle of each harmonic, the vector diagram of voltage and current, and the voltage and current waveform on the LCD.

c. Communication transmission function, including communication with DSP, communication with MODEM and network communication.

d. Parameter input, including voltage-current ratio, voltage upper and lower limits, over-limit settings of harmonic content, etc.

3.2.2 Receiving DSP Data For information, please visit: Power Transmission and Distribution Equipment Network

The data received from DSP is temporary data, including frequency, three-phase voltage, three-phase current and corresponding positive and negative zero-sequence components and harmonic components (real part and imaginary part, a total of 2×3×64 data).

3.2.3 Calculation of harmonics and unbalance index

The calculation of harmonic and imbalance related indicators is based on the provisions of GB/T 14549-1993 "Harmonics of public power grids for power quality" and GB/T 15543-1995 "Allowable imbalance of three-phase voltage for power quality". The specific formula is as follows.

3.2.3.1 Harmonic calculation (calculated once for each set of data read) Information from: www.tede.cn

a. The hth harmonic voltage content rate Information source: http://tede.cn

Where Uh is the hth harmonic voltage (root mean square value);

U1——fundamental voltage (root mean square value).

b. The hth harmonic current content rate

Where Ih is the hth harmonic current (RMS value); For information, please visit: Power Transmission and Distribution Equipment Network

I1——fundamental current (root mean square value).

c. Harmonic voltage content

f. Total harmonic distortion of current Information source: http://www.tede.cn

g. hth harmonic power and phase

3.2.3.2 Calculation of harmonic maximum and probability values Information source: http://tede.cn

a. Calculation of maximum harmonic value (values ​​of each order and total distortion rate)

b. Calculation of 95% probability value

Calculate the 95% probability value of the measured value of each phase during the measurement period and the value of the largest phase, and store them.

3.2.3.3 Harmonic over-limit alarm

The measured value is compared with the allowed value to determine whether it exceeds the limit. If so, an alarm is issued.

3.2.3.4 Voltage and current imbalance

Calculate the voltage and current unbalance (read a set of data every 3 seconds and calculate once), and calculate the 95% probability value of the voltage and current unbalance. Information source: http://tede.cn

a. Take the maximum value of imbalance

b. 95% probability value. Calculate the 95% probability value within the measurement period (statistical period).

3.2.3.5 Unbalance Exceeding Limit Alarm

The measured value is compared with the allowed value to determine whether it exceeds the limit. If so, an alarm is issued. Information from: Power Transmission and Distribution Equipment Network

3.2.4 Voltage Qualification Rate

3.2.4.1 Calculate voltage (read a set of data and calculate once every 3 seconds)

Calculate the rate of exceeding the upper limit and the rate of exceeding the lower limit, and count the cumulative time of exceeding the upper limit and the cumulative time of exceeding the lower limit; calculate the voltage qualification rate; store the recorded data of the previous month and the current month, the previous day and the current day; record the maximum value, minimum value and average value.

The rated value and limit value of the monitored voltage can be set. The voltage quality monitoring statistical time is in minutes, and the voltage average value of 1 minute is taken as a statistical unit.

The monitored voltage is displayed in real time with a refresh period of 2s. Information source: http://tede.cn

3.2.4.2 Calculation of voltage qualification rate

3.2.5 Frequency

The zero-crossing detection circuit and DSP capture function are used to accurately measure the width of the whole cycle and thus calculate the frequency.

3.2.6 Display

The voltage/current waveform, voltage/current vector diagram, voltage/current fundamental wave and harmonic amplitude and phase angle are displayed in graphics and Chinese characters. The amplitude and phase angle of each harmonic are divided into digital display and bar graph plus angle pointer display.

For information, please visit: Power Transmission and Distribution Equipment Network

3.3 ISA parallel expansion unit for PC104 and DSP communication

In order to facilitate the communication between DSP and PC, a parallel interface with interrupt is extended, occupying the peripheral address and interrupt of PC104. The parallel communication is 8-bit bidirectional (interrupt) communication. Information source: http://www.tede.cn

3.4 MODEM and LAN communication management

The MODEM is connected to the RS232C serial interface, and several control lines are extended to monitor and control the MODEM in real time to ensure that the MODEM communicates normally for a long time. Information from: Power Transmission and Distribution Equipment Network

The extended network card allows LAN network communication. Information from: www.tede.cn

4 Conclusion

a. The power quality monitoring terminal can monitor the power supply and power consumption of the power grid in real time and accurately, especially the excessive harmonics, the asymmetry and the voltage qualification rate at any time, providing convenient monitoring equipment for power supply and power consumption enterprises. Information from: Power Transmission and Distribution Equipment Network

b. The power quality monitoring terminal has the characteristics of high sampling frequency, accurate measurement, and fast calculation speed. Its measurement indicators meet the requirements of the national power quality standards.

c. The Chinese and graphic display interface of the power quality monitoring terminal makes it more convenient and intuitive for users to use. Information source: http://tede.cn

d. The power quality monitoring terminal adopts DSP and PC104 industrial control board design, which is advanced in technology and high in accuracy. It is convenient to carry out software maintenance and upgrade of DSP and PC104. Information source: http://www.tede.cn

e. The power quality monitoring terminals can form a power quality monitoring network in the regional power grid, provincial power grid or joint power grid, and through the dedicated central station software, it can realize the statistical analysis of a large amount of historical data, form various statistical reports, draw harmonic spectrum diagrams and distribution diagrams of various indicators, providing an advanced means for the supervision of power quality.

Reference address:Application of digital power quality online monitoring system in power system

Previous article:The Development and Application of Simulation Technology in China's Electric Power Industry
Next article:Wu Jiandong: China's Smart Interactive Grid Development Strategy Report

Recommended ReadingLatest update time:2024-11-16 19:50

3G video helmet based on ARM11 and DSP collaborative video stream processing technology
  1. Introduction In order to improve the controllability of on-site operations in high-risk workplaces, this paper adopts bionic principles and high-integration design to realize a 3G video helmet with the same viewing angle as the human eye. This design consists of a video helmet and a waist-span data processing te
[Embedded]
3G video helmet based on ARM11 and DSP collaborative video stream processing technology
Design of graphic display system for full attitude indicator based on DSP and FPGA
With the rapid development of modern avionics technology and the improvement of aircraft performance, the parameters displayed by the airborne graphic display system are increasing, and at the same time, high requirements are placed on the quality of the picture display from the perspective of ergonomics. To ensure th
[Embedded]
Design of graphic display system for full attitude indicator based on DSP and FPGA
Design of Multi-channel Video Monitoring System Based on Dual DSP
Abstract: A multi-channel video surveillance system is designed using two TI dedicated video processing chips TMS320DM642. Among them, DSP1 and video acquisition chip SAA7113 complete the acquisition of multiple channels of video and splice them into one video image output; DSP2 completes the acquisition, compressio
[Embedded]
Design of Multi-channel Video Monitoring System Based on Dual DSP
Design of inverter power supply based on ARM Cortex-M3 and DSP
introduction Today, with the development of electrical intelligence everywhere, countless power consumption occasions cannot do without the Inverted Power Supply System (IPS) to provide stable and high-quality power for field equipment, especially in places such as communication rooms, server workstations, transport
[Microcontroller]
Design of inverter power supply based on ARM Cortex-M3 and DSP
Design of SOPC Technology Based on DSP
Combining with the Nios II embedded soft-core processor launched by Altera, a Nios II system SOPC solution with the functions of a conventional DSP processor is proposed; the characteristic of Nios II that it can customize fork instructions is utilized. Complex multipliers, integer multipliers, floating-
[Embedded]
Design of SOPC Technology Based on DSP
Four major misunderstandings developers have about DSP controllers
Motor control designers have recently been faced with a roadblock in applications ranging from home appliances to servo drives, having to choose between controller performance or high price. Most motor control applications are inherently low cost. One of the requirements for market acceptance is an attractive price, w
[Analog Electronics]
Optimization of G.723.1 algorithm on DSP
Microcomputer Information Wang Wei Huang Junheng 1 Introduction G.723.1 is a low-bitrate speech coding algorithm standard launched by the TI in 1996. It is also the lowest bitrate standard among the speech compression standards issued by the organization. G.723.1 is mainly used for the compression of spe
[Embedded]
Research on CRC Check Algorithm of LTE System and Its DSP Implementation
Cyclic Redundancy Check CRC (Cyclic Redundancy Check) is the most commonly used error checking code in the field of data communication. Its characteristic is that the length of the information field and the check field can be arbitrarily selected. In order to complete error detection during signal transmission
[Embedded]
Latest Industrial Control Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号