The online power quality monitoring equipment is the most basic and most important equipment in the power quality supervision and detection network of the power grid. At present, most of the monitoring equipment for some power quality indicators (such as harmonics, imbalance, etc.) produced at home and abroad and sold and used in the market cannot fully meet the actual needs of power quality supervision and management in my country's power grid. In 1996, the southern power grid in Hebei Province began to install harmonic online monitoring devices. The initial devices had many problems in data storage, data transmission and background statistical analysis. In order to meet the growing needs of power quality supervision, based on several years of operating experience and experience, a digital power quality online monitoring terminal was developed.
The new digital power quality online monitoring device has the functions of collecting various power quality parameters according to national standards, high reliability of long-term online operation, convenient and practical on-site operation, and communication with the central station. At the same time, it can also record and store data for a long time and read data conveniently. The device adopts the DSP digital signal processor and high-speed multi-channel AD simultaneous sampling technology equivalent to the latest foreign products, and uses PC104 industrial computer for data processing, display and storage. It has powerful functions, easy operation and software upgrade.
1 Function and composition
The power grid power quality monitoring system consists of power quality monitoring terminals, central stations and analysis software.
1.1 Power quality monitoring terminal For information, please visit: Power Transmission and Distribution Equipment Network
Input three-phase voltage 100V, three-phase current 5A or 1A for data signal processing, and use FFT to calculate the amplitude and phase angle of each harmonic voltage and current. Calculate unbalanced voltage and current, calculate and display technical data such as three-phase voltage, current, voltage qualification rate, frequency, active power, reactive power and power factor. Responsible for data processing, storage, communication connection and data transmission with the central station, and form substation reports.
The main functions of the power quality monitoring terminal are as follows:
a. The input signal is TV, TA secondary side three-phase voltage (100V), three-phase current (5A or 1A).
b. With a public telephone MODEM interface, you can easily dial in and receive data at the central station.
c. Large screen (320×240) backlit LCD graphic display. Information source: http://www.tede.cn
d. Chinese graphics (spectrum diagram, waveform diagram, curve diagram, vector diagram) operation interface.
e. The terminal can store data for more than one year, and the stored data is a group of data packets of 3 minutes or 5 minutes.
f. With LAN connection interface, data can be transcribed on site using a laptop.
g.Multi-parameter comprehensive measurement, real-time fixed-point alarm, and parameter value and parameter alarm status can be set.
h. Harmonic voltage, current, negative sequence voltage, current over-limit alarm output relay. Information from: www.tede.cn
1.2 Central Station and Analysis Software Information from: www.tede.cn
The central station receives data from the processor through a modem or network, performs statistical analysis, forms files, reports and curves, and can display data and graphics (such as spectrum diagrams, waveform diagrams, curve diagrams, vector diagrams, etc.). It can manage multiple power quality monitoring terminals, analyze and process the collected data, analyze and form reports for the power quality of a certain period of time or a certain event process period, automatically form daily, monthly and annual reports, automatically find out the time periods and lines where the harmonic content rate exceeds the standard, and calculate the voltage qualification rate and power supply reliability.
The central station is a client-server mode, and the data is stored in the server's database, which can be easily called and queried.
2 Main technical indicators Information source: http://www.tede.cn
2.1 Measurement items Information from: Power Transmission and Distribution Equipment Network
The device uses (220±15%)Vac or [(220 +10%)~(220-15%)>Vdc power supply. The measurable items include: voltage, current, frequency, voltage qualification rate, active power, reactive power, apparent power, power factor, voltage unbalance, current unbalance, harmonic voltage, harmonic current (up to 31/50 or higher), harmonic phase, harmonic power, distortion rate, etc.
2.2 Measurement accuracy
Voltage measurement: ±0.2%
Current measurement: ±0.2%
Voltage unbalance measurement error: ≤0.2% For information, please visit: Power Transmission and Distribution Equipment Network
Current unbalance measurement error: ≤1%
Frequency measurement: 47~53 Hz, accuracy is ±0.01Hz(50Hz)
Signal conversion accuracy: 14bit
Sampling frequency: 8kHz/channel Information from: www.tede.cn
3. Software/Hardware Composition of Power Quality Monitoring Terminal
The hardware of the power quality monitoring terminal consists of TA/TV and signal preprocessing, DSP processor, PC104 industrial computer, PC104 and DSP parallel communication ISA bus parallel expansion, modem, LCD display (VGA monochrome with backlight), network adapter, power supply, etc.
The software of the power quality monitoring terminal consists of DSP software and PC104 software.
3.1 DSP software
3.1.1 DSP Principle
The monitoring terminal uses the TMS320F240 chip of TI's 320C2XX series. Considering the limited internal storage capacity of the chip, high-speed SRAM and EEPROM are expanded in the DSP part. The final design of the system requires the acquisition of 1024 points (6 channels at the same time) in each power frequency cycle, and the 6-channel radix 2 FFT transformation calculation of 1024 points is required and transmitted to the PC104 processing unit, which requires a faster clock frequency. In this device, the internal clock of the DSP is nearly 40MHz.
A fast 14-bit high-precision AD converter is added to the DSP processing part. This AD converter can perform 6-channel simultaneous sampling, which guarantees the accurate calculation of active power, reactive power, and positive/negative sequence.
3.1.2 Composition and Function of DSP
a. Data acquisition part, including frequency sampling and calculation, and 6-channel simultaneous sampling of AD converter.
b. Data processing, converting the format of collected data.
c.FFT transformation calculation.
d. Data transmission: transfer DSP data to PC104.
3.1.3 Input and Operation Information from: Power Transmission and Distribution Equipment Network
Input three-phase voltage and current, measure frequency, 1024 or 512-point AD conversion (AD uses dual 6-channel high-speed AD converter), after FFT transformation, calculate the RMS value, and upload data. According to needs, only 31 or 61 harmonics or higher harmonics are transmitted during data transmission. Information from: www.tede.cn
Perform FFT operation, take 31st (or 61st) harmonics every 0.5s, and calculate the RMS value 6 times every 3s.
3.1.4 Data Transmission
According to the pulse given by the host computer every 0.5s, data is uploaded every 3s. Taking the 31st harmonic as an example, each group of data is as follows.
Each harmonic is divided into real part and imaginary part, with the phase of Ua as the reference phase.
3.2 PC104 part
The PC104 industrial control board uses a highly integrated PCM-3336 board, which has floppy disk and hard disk interfaces, can directly drive a 320×240 LCD monochrome display, 2 RS232C serial interfaces, 1 printer parallel interface, and can directly connect a keyboard and a normal display. The BIO design of the board can connect a hard disk up to 15G. For ease of use and reliability, the hard disk uses an electronic disk or a notebook hard disk.
The industrial control board has a WATCH-DOG function, which will automatically reset when it does not work properly.
The PC104 board is responsible for data processing, storage, and display, as well as the communication connection and data transmission between the power quality monitoring terminal and the central station, and forms a substation report. It sends a 0.5 s pulse to the DSP to collect DSP data.
3.2.1 PC104 software composition
a. Calculate and process various data, including voltage, current, active power, reactive power, positive and negative sequence, voltage imbalance, voltage qualification rate, harmonic content rate, etc.
b. Graphically display the voltage, current fundamental wave and the amplitude and phase angle of each harmonic, the vector diagram of voltage and current, and the voltage and current waveform on the LCD.
c. Communication transmission function, including communication with DSP, communication with MODEM and network communication.
d. Parameter input, including voltage-current ratio, voltage upper and lower limits, over-limit settings of harmonic content, etc.
3.2.2 Receiving DSP Data For information, please visit: Power Transmission and Distribution Equipment Network
The data received from DSP is temporary data, including frequency, three-phase voltage, three-phase current and corresponding positive and negative zero-sequence components and harmonic components (real part and imaginary part, a total of 2×3×64 data).
3.2.3 Calculation of harmonics and unbalance index
The calculation of harmonic and imbalance related indicators is based on the provisions of GB/T 14549-1993 "Harmonics of public power grids for power quality" and GB/T 15543-1995 "Allowable imbalance of three-phase voltage for power quality". The specific formula is as follows.
3.2.3.1 Harmonic calculation (calculated once for each set of data read) Information from: www.tede.cn
a. The hth harmonic voltage content rate Information source: http://tede.cn
Where Uh is the hth harmonic voltage (root mean square value);
U1——fundamental voltage (root mean square value).
b. The hth harmonic current content rate
Where Ih is the hth harmonic current (RMS value); For information, please visit: Power Transmission and Distribution Equipment Network
I1——fundamental current (root mean square value).
c. Harmonic voltage content
f. Total harmonic distortion of current Information source: http://www.tede.cn
g. hth harmonic power and phase
3.2.3.2 Calculation of harmonic maximum and probability values Information source: http://tede.cn
a. Calculation of maximum harmonic value (values of each order and total distortion rate)
b. Calculation of 95% probability value
Calculate the 95% probability value of the measured value of each phase during the measurement period and the value of the largest phase, and store them.
3.2.3.3 Harmonic over-limit alarm
The measured value is compared with the allowed value to determine whether it exceeds the limit. If so, an alarm is issued.
3.2.3.4 Voltage and current imbalance
Calculate the voltage and current unbalance (read a set of data every 3 seconds and calculate once), and calculate the 95% probability value of the voltage and current unbalance. Information source: http://tede.cn
a. Take the maximum value of imbalance
b. 95% probability value. Calculate the 95% probability value within the measurement period (statistical period).
3.2.3.5 Unbalance Exceeding Limit Alarm
The measured value is compared with the allowed value to determine whether it exceeds the limit. If so, an alarm is issued. Information from: Power Transmission and Distribution Equipment Network
3.2.4 Voltage Qualification Rate
3.2.4.1 Calculate voltage (read a set of data and calculate once every 3 seconds)
Calculate the rate of exceeding the upper limit and the rate of exceeding the lower limit, and count the cumulative time of exceeding the upper limit and the cumulative time of exceeding the lower limit; calculate the voltage qualification rate; store the recorded data of the previous month and the current month, the previous day and the current day; record the maximum value, minimum value and average value.
The rated value and limit value of the monitored voltage can be set. The voltage quality monitoring statistical time is in minutes, and the voltage average value of 1 minute is taken as a statistical unit.
The monitored voltage is displayed in real time with a refresh period of 2s. Information source: http://tede.cn
3.2.4.2 Calculation of voltage qualification rate
3.2.5 Frequency
The zero-crossing detection circuit and DSP capture function are used to accurately measure the width of the whole cycle and thus calculate the frequency.
3.2.6 Display
The voltage/current waveform, voltage/current vector diagram, voltage/current fundamental wave and harmonic amplitude and phase angle are displayed in graphics and Chinese characters. The amplitude and phase angle of each harmonic are divided into digital display and bar graph plus angle pointer display.
3.3 ISA parallel expansion unit for PC104 and DSP communication
In order to facilitate the communication between DSP and PC, a parallel interface with interrupt is extended, occupying the peripheral address and interrupt of PC104. The parallel communication is 8-bit bidirectional (interrupt) communication. Information source: http://www.tede.cn
3.4 MODEM and LAN communication management
The MODEM is connected to the RS232C serial interface, and several control lines are extended to monitor and control the MODEM in real time to ensure that the MODEM communicates normally for a long time. Information from: Power Transmission and Distribution Equipment Network
The extended network card allows LAN network communication. Information from: www.tede.cn
4 Conclusion
a. The power quality monitoring terminal can monitor the power supply and power consumption of the power grid in real time and accurately, especially the excessive harmonics, the asymmetry and the voltage qualification rate at any time, providing convenient monitoring equipment for power supply and power consumption enterprises. Information from: Power Transmission and Distribution Equipment Network
b. The power quality monitoring terminal has the characteristics of high sampling frequency, accurate measurement, and fast calculation speed. Its measurement indicators meet the requirements of the national power quality standards.
c. The Chinese and graphic display interface of the power quality monitoring terminal makes it more convenient and intuitive for users to use. Information source: http://tede.cn
d. The power quality monitoring terminal adopts DSP and PC104 industrial control board design, which is advanced in technology and high in accuracy. It is convenient to carry out software maintenance and upgrade of DSP and PC104. Information source: http://www.tede.cn
e. The power quality monitoring terminals can form a power quality monitoring network in the regional power grid, provincial power grid or joint power grid, and through the dedicated central station software, it can realize the statistical analysis of a large amount of historical data, form various statistical reports, draw harmonic spectrum diagrams and distribution diagrams of various indicators, providing an advanced means for the supervision of power quality.
Previous article:The Development and Application of Simulation Technology in China's Electric Power Industry
Next article:Wu Jiandong: China's Smart Interactive Grid Development Strategy Report
Recommended ReadingLatest update time:2024-11-16 19:50
- Popular Resources
- Popular amplifiers
- Molex leverages SAP solutions to drive smart supply chain collaboration
- Pickering Launches New Future-Proof PXIe Single-Slot Controller for High-Performance Test and Measurement Applications
- CGD and Qorvo to jointly revolutionize motor control solutions
- Advanced gameplay, Harting takes your PCB board connection to a new level!
- Nidec Intelligent Motion is the first to launch an electric clutch ECU for two-wheeled vehicles
- Bosch and Tsinghua University renew cooperation agreement on artificial intelligence research to jointly promote the development of artificial intelligence in the industrial field
- GigaDevice unveils new MCU products, deeply unlocking industrial application scenarios with diversified products and solutions
- Advantech: Investing in Edge AI Innovation to Drive an Intelligent Future
- CGD and QORVO will revolutionize motor control solutions
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
- About the signal input mode of the power amplifier
- My Journey of MCU Development (Part 1)
- How to understand the accuracy parameter (1.5% + 3) of the Fluke F17B+ multimeter?
- Another bottleneck.
- Easy-to-use and cheap microcontroller is here
- Inverting proportional operational amplifier circuit
- Upper computer displays waveform acquisition
- Evaluation Weekly Report 20211129: There are 4 days left for Anxinke NB-IoT and domestic FPGA applications, and the wireless charging mouse pad is waiting to be disassembled (Extra)
- Are there any pmos and nmos tubes with working current |Ids|=1.2A;|Vds|<0.2V, which don't matter if they are enhanced or not, and have low leakage current when turned off?
- EEWORLD University Hall----TI 77GHz millimeter wave radar product introduction and solution display