  • INDUSTRIAL INSTALLATION SECONDARY CONDUCTORS NOT OVER 25 FT (7.5 m) LONG - 240.21(C)(3)
  • Login
  • Duration:5 minutes and 6 seconds
  • Date:2022/09/28
  • Uploader:Lemontree
Introduction
keywords: electronic system
Switchboards are designed with busbars for fuses or circuit breakers that are used for protecting and supplying feeders and branch circuits. Panelboards are designed with a permanently installed main circuit breaker or single set of fuses for disconnecting the number of circuit breakers or fuseholders installed to protect and supply feeders or branch circuits.

SUPPORT AND ARRANGEMENT OF BUSBARS AND CONDUCTORS
408.3

Busbars shall be held firmly in place in the enclosure and shall be arranged in such a way to allow adequate space for conductors to be terminated. Busbars shall be sized with enough capacity to handle the normal currents in amps of the electrical system. In addition, they shall carry safely any type of short-circuit or ground-fault condition.

CONDUCTORS AND BUSBARS ON A SWITCHBOARD OR PANELBOARD
408.3(A)

Conductors and busbars on a switchboard, panelboard, or control board shall be so located as to be free from physical damage. Service sections of such boards shall be separated from the other electrical components. These components shall be properly secured in an approved manner. 

Note, conductors entering a certain section shall terminate in such section, except where it is not practical for control, interconnecting conductors, or other conditions of use.

OVERHEATING AND INDUCTIVE HEATING
408.3(B)

The arrangement of busbars and conductors shall be such as to avoid overheating due to inductive effects. The inductive effect of each conductor is neutralized when grouping all conductors together. To accomplish the minimizing of heating effects, the ungrounded (phase) conductors, grounded (neutral) conductors, and equipment grounding conductors, where used, shall be in the same enclosure, raceway, cable, cord, etc. (See Figure 7-1)

Unfold ↓

You Might Like

Recommended Posts

About the reset function of capacitor in microcontroller
Regarding the reset function of the capacitor in the microcontroller, since the RST reset terminal capacitor can be reset by pulling it low at the moment of power-on, then after the microcontroller's
QWE4562009 Integrated technical exchanges
What is the difference between a DC contactor and an AC contactor?
Different applications, the choice of AC or DC depends on the coil. The coil of the DC contactor can only pass DC, and the coil of the AC contactor can only work with AC. Generally speaking, in the AC
安_然 Analog electronics
[National Technology N32G457 Review] Comparison of two N32G457 development tools and lighting programs
MDK, IAR and RT-Thread are tools that can be used to develop the N32G457 development board. The following only uses MDK and RT-Thread as examples to compare the program changes for lighting up the onb
jinglixixi Domestic Chip Exchange
I actually saw a technical exchange post from my alma mater here
I actually saw a technical exchange post from my alma mater here, and my eyes were filled with tears!
minranyuxin MCU
【Distributed temperature and humidity acquisition system】+temperature and humidity acquisition module
[i=s]This post was last edited by lansebuluo on 2022-9-22 09:12[/i]After a period of getting familiar with the W800 chip configuration and demo code, I finally completed the programming and debugging
lansebuluo DigiKey Technology Zone

Recommended Content

Circuit

可能感兴趣器件

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京B2-20211791 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号