Panasonic inverter is a brand of inverter developed and sold by Panasonic Group of Japan. Panasonic inverter has advanced technology, simple and convenient operation, stable working performance, high safety and reliability, and can also play a lot of self-protection role. However, although it has so many advantages, some faults will still occur during use, which is a common problem of electronic products.
In the maintenance of DV707 series inverters, the fault that is often encountered is no display after power-on. Excluding external power supply, display and other factors, in most cases, it is the damage of the switching power supply. During the maintenance, we can notice that the pulse transformer of the DV707 series inverter is a device that is more easily damaged. Due to the influence of some factors such as high-frequency magnetic conductive materials, load capacity, short-circuit overcurrent protection circuit design of the switching power supply, the primary winding side of the pulse transformer is prone to burnout. Since the skeleton design of the pulse transformer is different from that of the general step-up/step-down transformer, it is not easy to disassemble. Often after disassembly, the magnetic conductive material will crack, and there will be a gap in the closed magnetic field at the connection, and the pulse transformer cannot work normally. Generally, replace the pulse transformer.
In addition, the design of the DV707 series inverter switching power supply is different from other inverters. It uses an integrated block of model MA2810, which integrates switching power tubes, clamping voltage regulator tubes and other components, reducing the peripheral circuits of the switching power supply. However, the probability of damage to MA2810 is still relatively high during maintenance.
(1) No display when the Panasonic inverter is powered on
In the maintenance of DV707 series inverters, the fault that the author often encounters is no display after power-on. Excluding external power supply, display and other factors, in most cases it is the damage of the switching power supply. During the maintenance, we can notice that the pulse transformer of the DV707 series inverter is a device that is more easily damaged. Due to the influence of some factors such as high-frequency magnetic conductive materials, load capacity, short-circuit overcurrent protection circuit design of the switching power supply, the primary winding side of the pulse transformer is prone to burnout. Because the skeleton design of the pulse transformer is different from that of the general step-up/step-down transformer, it is not easy to disassemble. Often after disassembly, the magnetic conductive material will crack, and there will be a gap in the closed magnetic field at the connection, and the pulse transformer cannot work normally. Generally, replace the pulse transformer.
In addition, the design of the DV707 series inverter switching power supply is different from other inverters. It uses an integrated block model MA2810, which integrates switching power tubes, clamping voltage regulator tubes and other components, reducing the peripheral circuits of the switching power supply. However, the probability of damage to MA2810 during maintenance is still relatively high.
(2) Panasonic inverter inverter module is damaged
In VF-7F series inverters, the inverter module is sometimes damaged. A common phenomenon is that the inverter suddenly loses power during normal operation, causing the inverter to be unable to start the motor after powering on again. After checking the inverter module damage, the main reason is that the inverter is still under the control of the running command after the power outage. At this time, due to the consumption of the load carried by the motor and the consumption of the inverter itself, the intermediate DC voltage drops sharply, which easily causes the PWM modulation wave signal to change, resulting in damage to the power module. Generally, in this case, the drive circuit is not easy to be damaged. Replace the inverter module and the inverter can resume normal operation. In such a situation, it is best to take measures on the control circuit to block the inverter output at the moment of power outage.
(3) Panasonic inverter drive circuit is damaged
In the maintenance of DV707 series inverters, it is often encountered that the inverter module is damaged while the drive circuit is also damaged. The lack of negative pressure in the drive circuit is a common phenomenon of drive circuit damage. DV707 series inverters use Fuji's PIM module for power devices, which belongs to the IGBT type. As we all know, IGBT high-power tubes are voltage-conducting types. In the absence of negative pressure, the IGBT will not be able to be effectively turned off, resulting in misconduction. Negative pressure is generally generated by the voltage-stabilizing diode, which is also the most common damage part. Replace it and the drive waveform should return to normal.
(4) Panasonic inverter LV failure
LV failure is also one of the phenomena that can be often encountered during maintenance. Especially in DV700 series inverters. After excluding the external power supply problem, the most common problem should be the detection circuit failure. The sampling is done through the voltage drop resistor, and the optocoupler signal is sent to the main control board for processing after being isolated by the optocoupler. The voltage drop resistor and the isolation optocoupler may be damaged. After replacement, the machine should be able to return to normal.
Previous article:Common faults and judgments of Schneider inverters
Next article:Inverter grounding precautions
- Popular Resources
- Popular amplifiers
- Red Hat announces definitive agreement to acquire Neural Magic
- 5G network speed is faster than 4G, but the perception is poor! Wu Hequan: 6G standard formulation should focus on user needs
- SEMI report: Global silicon wafer shipments increased by 6% in the third quarter of 2024
- OpenAI calls for a "North American Artificial Intelligence Alliance" to compete with China
- OpenAI is rumored to be launching a new intelligent body that can automatically perform tasks for users
- Arm: Focusing on efficient computing platforms, we work together to build a sustainable future
- AMD to cut 4% of its workforce to gain a stronger position in artificial intelligence chips
- NEC receives new supercomputer orders: Intel CPU + AMD accelerator + Nvidia switch
- RW61X: Wi-Fi 6 tri-band device in a secure i.MX RT MCU
Professor at Beihang University, dedicated to promoting microcontrollers and embedded systems for over 20 years.
- LED chemical incompatibility test to see which chemicals LEDs can be used with
- Application of ARM9 hardware coprocessor on WinCE embedded motherboard
- What are the key points for selecting rotor flowmeter?
- LM317 high power charger circuit
- A brief analysis of Embest's application and development of embedded medical devices
- Single-phase RC protection circuit
- stm32 PVD programmable voltage monitor
- Introduction and measurement of edge trigger and level trigger of 51 single chip microcomputer
- Improved design of Linux system software shell protection technology
- What to do if the ABB robot protection device stops
- CGD and Qorvo to jointly revolutionize motor control solutions
- CGD and Qorvo to jointly revolutionize motor control solutions
- Keysight Technologies FieldFox handheld analyzer with VDI spread spectrum module to achieve millimeter wave analysis function
- Infineon's PASCO2V15 XENSIV PAS CO2 5V Sensor Now Available at Mouser for Accurate CO2 Level Measurement
- Advanced gameplay, Harting takes your PCB board connection to a new level!
- Advanced gameplay, Harting takes your PCB board connection to a new level!
- A new chapter in Great Wall Motors R&D: solid-state battery technology leads the future
- Naxin Micro provides full-scenario GaN driver IC solutions
- Interpreting Huawei’s new solid-state battery patent, will it challenge CATL in 2030?
- Are pure electric/plug-in hybrid vehicles going crazy? A Chinese company has launched the world's first -40℃ dischargeable hybrid battery that is not afraid of cold
- 1MHz square wave double frequency
- CC3200 Modify the sprinkler routine of Out of Box
- Upgrading the embedded RISC-V compiler
- You can use FIND to check which library a certain component is in in the PROTEL schematic. You can also check which library a certain package is in. Why is it not there?
- Can RS485 communicate stably using parallel wires (non-twisted pair)? 5m wire length, 9600bps
- TI Wired and Wireless Communications in Electric Vehicle Battery Management
- Do you know the audio and video expansion port and asynchronous serial port expansion of DSPs?
- [CH563L Review] Part 1 Based on the official uCos introductory Hello World
- Why is there a "red dot" on my forum icon?
- Is the signal mentioned in Nyquist sampling theorem limited to sine (cosine) signal form?