When the relay and contactor control lines are very long (for example, AC 220V exceeds 200m), due to the influence of the voltage drop on the control line
and the distributed capacitance of the line, the relay and contactor may malfunction and lose control. Measures must be taken
to prevent this. There are many ways to prevent it, two of them are introduced below.
The remote control circuit is shown in Figure 6-18. The critical length L of the control line to avoid malfunction of relays and contactors and out-of-control control can be
calculated according to the following formula:
two-core cable L 1 pinch etc. × 103 (m)
three-core cable L 1 pinch × 103 (m)
where PH -Rated holding power of relay or contactor, w;
U. ——Rated voltage of relay or contactor coil, V.
- Add one more component to improve the phase failure protection function
- Design and analysis of voice control circuit
- Ultra-short wave item left behind reminder alarm
- Night dog barking anti-theft reminder circuit
- Multi-channel laser anti-theft alarm circuit
- Rolling door anti-theft device
- Practical electric curtain remote control device
- Control two contactors with one wire
- New type of wind and rainproof automatic window that is simple and easy to make
- Ultrasonic mouse repeller
- Motor forward and reverse control wiring diagram (2)
- Agricultural small tractor lighting circuit
- Particle clogging alarm circuit of wheat seeder
- Farmland irrigation automatic control circuit a
- Integrated synchronous detector composed of analog multiplier MC1596
- Multi-frequency resonant high-frequency power amplifier circuit for transmitter stage
- Differential Amplifier Circuit
- color discrimination circuit
- Digital stopwatch display circuit
- Small current generator circuit