Home > Control Circuits > Three-phase motor overcurrent protection circuit

Three-phase motor overcurrent protection circuit

Source: InternetPublisher:桂花蒸 Keywords: Protection circuit three-phase motor overcurrent protection BSP Updated: 2020/02/19

22.<strong>Three-phase motor</strong>Overcurrent<strong>Protection circuit</strong>.gif

It is a three-phase motor overcurrent
protection circuit .
    Working principle: This circuit uses a transformer to induce
current when the current of the three-phase motor exceeds the normal operating current
. The overcurrent relay Kl reaches the set value of the pickup current and is closed
. Its normally closed contact is disconnected, and KM is released when it loses power, causing the main circuit
to lose power, thus protecting the motor and making it disconnect from the power supply when overcurrent occurs
.
    When the motor starts, the current is relatively large. Use
the normally closed contact of the time relay to short-circuit the current transformer first to prevent the motor starting
current from flowing through Kl and causing malfunction. After the motor is started
, the current drops to normal, and the time relay KT acts after a delay
. Its normally closed contact is opened, its normally open contact is closed, and KI is connected to the
current transformer line.


EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号