Design architecture and performance analysis of automotive heat pump systems

Publisher:BlissfulHikerLatest update time:2024-08-15 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

Direct heat pump

Direct heat pumps are designed to move heat energy from two radiators in two directions. This allows heat pumps to provide both heating and cooling functions in vehicles, which is actually achieved in two different architectures.

In the "air-to-air" (ATA) architecture, the refrigerant cycle works as a standard A/C system, and the HVAC module is modified to integrate an additional condenser, which replaces the traditional cabin heater.

In the air-to-water (ATW) architecture, the refrigerant cycle works as a standard A/C system with no modifications to the HVAC module, so a conventional cabin heater can be used thanks to the integration of a water-cooled condenser in the refrigerant circuit.

Both architectures are currently implemented in electric vehicles available on the market; in the following paragraphs, these systems are described in more detail.

Air-to-air (ATA) The layout of the heat pump system using the ATA structure is shown in Figure 3.

The air conditioning refrigerant circuit (green circuit in Figure 3) consists of the following components:

EVP: HEX (refrigerant/air heat exchanger) installed in the HVAC module

CHILLER: Required when refrigerant/coolant HEX is used to cool the battery coolant circuit;

ACOND: Refrigerant/Air HEX is installed in the HVAC module, it transfers heat to the cabin when needed;

OHX: Refrigerant/air external heat exchanger, designed for use as a condenser or evaporator;

EXV: Electronic Expansion Valve;

SOV: Stop valve with on/off control;

E-CMP: Electric compressor.

The coolant circuit (blue and purple in Figure 3) consists of the following components:

LT: Low temperature radiator, coolant/air HEX;

12cc595c-e540-11ee-a297-92fbcf53809c.png

Figure 3 ATA heat pump architecture for pure electric vehicle applications. The standard HVAC module is modified to introduce an internal condenser (ACOND). A/C or heat pump function can be activated through dedicated stop valve (SOV) and expansion valve (EXV) control

Table 4 ATA valve arrangement under summer (A/C) and winter (heat pump) conditions

HV HTR: A high-voltage coolant heater dedicated to the battery heating function;

Dedicated coolant pump for battery and PWT circuits;

Coolant Valve: Three-way valve (V1 and V2) used to open or close the coolant path connecting the battery circuit to the LT.

In "hot summer conditions", the HP system works as a standard A/C system; the low temperature is transferred to the cabin via the EVP and to the battery via the cooler, the OHX works as a condenser, and the ACOND has no effect (but cannot be circumvented). In "cold winter conditions", the heat pump system achieves its true purpose: heat is transferred to the cabin via the ACOND and the OHX works as an evaporator to recover heat from the outside environment. Finally, in this case, if additional or faster heating heat is eventually needed, the HV PTC for the cabin and the HV coolant HTR for the battery are activated to achieve this.

12d49b30-e540-11ee-a297-92fbcf53809c.png

Table 4 summarizes the EXV and SOV valve arrangements for the above two cases.

This architecture also allows waste heat to be recovered from the vehicle battery when it is necessary to heat the cabin and cool the battery simultaneously, such as during fast charging operations. In this case, the heat is lost from the battery via the cooler and is excluded from the cabin due to ACOND. To achieve this configuration, the EXV of the OHX is closed and SOV1 is open.

Air-to-Water (ATW) The layout of the heat pump system using ATW configuration is shown in Figure 4.

The air conditioning refrigerant circuit (green circuit in Figure 4) consists of the following components:

EVP: Refrigerant/Air HEX installed in HVAC module

CHILLER: Refrigerant/coolant HEX cools the battery coolant circuit when needed;

WCOND: Refrigerant/coolant HEX, transfers heat to the cabin when needed;

OHX: Refrigerant/air HEX, designed for use in condensers or evaporators;

EXV: Electronic Expansion Valve;

SOV: Stop valve with on/off control;

E-CMP: Electric compressor.

12e71bac-e540-11ee-a297-92fbcf53809c.png

Figure 4 ATW heat pump architecture for pure electric vehicle applications. The standard HVAC module remains unchanged, but an additional plate heat exchanger (WCOND) is introduced. The air conditioning can be activated by controlling the dedicated stop valve (SOV) and the expansion valve EXV.

The coolant circuit (blue and purple in Figure 4) consists of the following components:

LT: Low temperature radiator, coolant/air HEX;

HV HTR: High-voltage coolant heater for battery and cabin heating;

Dedicated coolant pumps for cabin, battery and PWT circuits

Coolant Valves: Two three-way valves and one four-way valve to enable or disable the coolant path, connecting the cabin and battery return, or the PWT and battery return to the LT radiator.

In “summer or hot conditions”, the HP system works as a standard A/C system; the low temperature is transferred to the cabin through the EVP and to the battery through the cooler, the OHX works as a condenser, and WCOND has no effect (it is not bypassed by the refrigerant). In “winter cold conditions”, the heat pump system achieves its true purpose: heat is transferred to the coolant through WCOND through the refrigerant and released to the cabin through the CBN HTR. In this case, if additional or faster heating power is eventually required, the high-pressure PTC for the cabin and the high-pressure coolant HTR for the battery will be activated to achieve the target. Finally, in this case, the OHX works as an evaporator to recover heat from the external environment. The EXV and SOV valve arrangements for the above two cases are shown in Table 4, while the coolant valve (V1, V2 and V3) arrangements are shown in Tables 5 and 6.

As an ATA, the architecture can also recover waste heat from the vehicle battery when cabin heating and battery cooling are required simultaneously (e.g. during fast charging operations). In this case, the heat released from the battery, through the cooler, is discharged in the cabin thanks to WCOND and then CBN HTR. To achieve this configuration, the EXV of the OHX is closed, SOV1 is opened and the three-way valve on the cabin coolant circuit is closed towards the line connected to the battery.

In the ATA configuration, the ATW architecture can also recover waste heat from the electric motor through the coolant circuit. In this case, the active grille shutters at the front of the vehicle are closed, so the heat that would normally be rejected through the LT radiator can be used to heat the battery. To achieve this configuration, the three-way valve on the PWT coolant circuit is only open for the line connected to the battery, while the four-way valve is only open for the line connected to the PWT.

12eb5da2-e540-11ee-a297-92fbcf53809c.png

Table 5 ATW coolant valve arrangement

12fa2576-e540-11ee-a297-92fbcf53809c.png

Table 6 ATW coolant valve arrangement under mixed working conditions

Virtual performance comparison

A mathematical model of the ATA and ATW system architectures was implemented using a commercial simulation software SW (AMESim17.0) in order to compare the performance of these HP solutions, taking into account the different functional objectives discussed in the previous paragraphs. In particular, a performance comparison was performed through an energy analysis that takes into account the energy consumption of all electrical components and the contribution of thermal energy exchanged with the different users, according to the following definition of system and HP COP:

130c74ba-e540-11ee-a297-92fbcf53809c.png

The energy used by the user for cabin conditioning and battery conditioning is different:

Cabin Conditioning - The time integral of the change in enthalpy of air between the HVAC inlet and the cabin inlet.

Battery Conditioning – Changes in the Energy Stored Within a Battery

Through this analysis, the efficiency of the HP system is evaluated taking into account the boundary conditions described in Table 7 and taking a D-class electric vehicle as an example.

In the following paragraphs the results of the simulations are discussed ; the relative contributions of the different electrical components are discussed (Figures 13-16-18-20-23); these contributions can vary with changes in the system control strategy.

131417e2-e540-11ee-a297-92fbcf53809c.png

Table 7 Simulation boundary conditions

(1) Measure temperature @ cabin inlet (HVAC outlet)

(2) Coolant temperature @ chiller outlet, excluding battery heating target, where the reference is the battery temperature

13279948-e540-11ee-a297-92fbcf53809c.png

Figure 5. Layout of the heat pump simulation model in AMESim. Each component of the HP is modeled as a block called a supercomponent. Each block is calibrated according to the detailed component data sheet.

Cabin cooling

In cabin cooling mode, the performance of the HP ATA architecture is slightly better than that of the ATW (ΔE ~ -3%, see Figure 6): at the same EVP outlet air temperature, the energy consumption is reduced and both the system and HP COP are increased due to the lower refrigerant pressure difference generated by the ACond heat exchanger relative to the Wcond heat exchanger.

13303e7c-e540-11ee-a297-92fbcf53809c.png

Figure 6 Cabin cooling In terms of COP and energy consumption, the performance of the ATA architecture is slightly better than that of the ATW

Battery cooling (fast charging)

The worst case for battery cooling occurs during fast charging of the battery. A specific current profile was used to simulate this situation as shown in Figure 7 and implemented in the battery simulation model, considering the charge rate decreasing from 1.6 C at SOC = 0% of the battery to 0.72 C when the SOC increases to 80%.

During the simulation, until the heat released by the battery is higher than the cooling power of the chiller, the HP will not cool the battery but limit its temperature rise. Then, when the cooling potential of the chiller exceeds the heat release of the battery (up to a certain SOC value), the battery starts to cool (Figure 8).

During the simula ti on , until the battery thermal release is higher than the chiller cooling power, the HP does not cool down the battery, but limits its temperature increase. Then, when the chiller cooling potential overcomes the battery heat losses (up to a cert ai n SOC value), battery starts to cool down (Figure 8). The original text is here for fear of misunderstanding.

[1] [2] [3] [4]
Reference address:Design architecture and performance analysis of automotive heat pump systems

Previous article:A brief discussion on Bosch's cockpit monitoring technology
Next article:A brief discussion on the driving force of the development of the flat wire motor industry for new energy vehicles

Recommended ReadingLatest update time:2024-11-15 05:34

Uncovering the secrets of PTC protection circuit design for smart home appliances
  In household appliances such as soybean milk machines, blenders, and egg beaters, in order to avoid the motor stalling and burning due to the "tough" big guys, design engineers usually design temperature or overcurrent protection measures, commonly used are: one-time overcurrent protection, recoverable temperature p
[Power Management]
Uncovering the secrets of PTC protection circuit design for smart home appliances
Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号