Analysis of common faults of frequency converter

Publisher:rnm888Latest update time:2021-12-29 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

With the increasing application of variable frequency speed regulation technology in my country's cement industry, it has become an inevitable trend to replace voltage regulation, slip regulation and DC speed regulation with AC variable frequency speed regulation in many links of production processes that require speed regulation, such as rotary kilns, grate coolers, feeders, batching scales, fans, water pumps, etc.


The inverter contains a large number of electronic components, each of which plays a vital role.


Internal components of the inverter

According to the function, it is divided into main circuit, auxiliary switching power supply, control board and driver board.


Analysis of common faults of frequency converter

(1) Overcurrent fault: Overcurrent fault can be divided into acceleration, deceleration, and constant speed overcurrent. It may be caused by too short acceleration and deceleration time of the inverter, sudden load change, uneven load distribution, output short circuit, etc. At this time, it can generally be solved by extending the acceleration and deceleration time, reducing sudden load changes, adding energy-consuming braking elements, designing load distribution, and checking the circuit. If the inverter still has an overcurrent fault after disconnecting the load, it means that the inverter inverter circuit has looped and the inverter needs to be replaced.


(2) Overload fault: Overload fault includes frequency conversion overload and motor overload. It may be caused by too short acceleration time, too low grid voltage, too heavy load, etc. It can generally be solved by extending the acceleration time, extending the braking time, checking the grid voltage, etc. The load is too heavy, the selected motor and inverter cannot drag the load, or it may be caused by poor mechanical lubrication. In the former case, a high-power motor and inverter must be replaced; in the latter case, the production machinery must be repaired.


(3) Undervoltage: This indicates that there is a problem with the inverter power input part and it needs to be checked before it can be operated.


Reference address:Analysis of common faults of frequency converter

Previous article:Classification, functions and control methods of frequency converters
Next article:How to calculate the wires and switches based on the capacity of the motor?

Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号