Radar level meters are widely used in the level measurement of high-temperature, high-pressure, flammable, explosive, and condensable media. This is inseparable from the advantages of radar level meters, such as simple structure, convenient installation, easy maintenance, and corrosion resistance. Nevertheless, due to the influence of improper selection, installation, and use, various faults and problems often occur during the use of radar level meters. In order to avoid affecting production and help instrument users better use radar level meters, this article briefly describes the common faults and treatments of radar level meters as follows.
High frequency ultrasonic radar level meter
1. Failures and treatments caused by instrument problems
If the meter measures abnormally, and inspection shows that the antenna is in good condition and installation and there are no obstacles inside the tank, it can be basically determined that the cause of the fault is the meter itself.
The more common ones are the following:
1. Instrument software or hardware failure. Upgrade the software, replace the instrument, or return the instrument for processing.
2. The current signal is greater than 22mA or 0mA. This fault is mostly caused by damage to electronic components. Solution: Replace the instrument in time or send it to the factory for repair.
3. 4-20mA signal is unstable. This fault is mostly caused by level fluctuation. Solution: Set a suitable integration time by adjusting the module or PACTware software.
4. 4-20mA signal is lost. This fault is mostly caused by incorrect wiring of the power supply, no power connection, or the power supply voltage is too low or the load resistance is too high.
Solution: Check the wiring to see if the power supply is reliably connected and correct the installation wiring diagram; check if the cable is disconnected and the fuse is burned out. If there is any cable breakage, repair it in time; if the voltage is too low or the load resistance is too high, pay attention to check and correct it.
2. There are false echoes in the radar level meter with bypass pipe
Cause of the failure: Because there are burrs, welding slag, welding seals and attached impurities on the wall of the bypass pipe, there are false echo signals that can be detected, which affect the detection of the real echo signal and cause the radar level meter to display a false liquid level.
Solution: Using computer software to store and eliminate false echoes is only a temporary solution. To completely solve the problem of false echoes and false liquid levels in radar level gauges, the bypass pipe should be cleaned and frosted. And pay attention to purchasing radar level gauges with relatively good quality to minimize measurement failures caused by such problems.
3. The instrument circuit fails due to poor sealing
Cause of failure: Most instrument circuit parts fail because the cable inlet and instrument cover are not tightly sealed, causing rain or other liquids, dust, humid gases, etc. to enter the instrument.
Solution: Therefore, when purchasing, you must give priority to radar level meters with better sealing performance. At the same time, you should pay attention to correct installation. If necessary, you can install a protective cover for the instrument to seal the entire instrument.
4. Antenna scarring affects the accurate measurement of radar level meter
Fault phenomenon: Hanging materials with very small dielectric constant have no effect on measurement in dry state, while hanging materials with very high dielectric constant have a great influence on measurement.
Solution: At this time, the antenna scarring can be eliminated by blowing with compressed air or flushing with clean water, or by regularly cleaning the scarring with an acidic cleaning solution (but it should be noted that measurements cannot be performed during the cleaning period).
5. Radar level meter antenna condenses or freezes in winter
Solution: In addition to regular inspection and cleaning, it is recommended to install insulation and heating devices on the outside of the radar level gauge to keep the temperature near the tank mouth basically constant.
6. Establish a sound daily maintenance system
In the process of using the radar level meter, in addition to timely handling of faults, daily correct maintenance is also essential. Generally speaking, in the daily use and maintenance of the radar level meter, pay attention to checking the following items:
1. Regularly check whether the power supply voltage and output current of the instrument are normal.
2. Regularly check whether the instrument's antenna is adhered to dirt.
3. Check whether the connection between the instrument and the tank is firm.
4. Check whether the sealing conditions of the joints of each component are good.
5. Perform calibration regularly.
In fact, as long as the radar level meter can be correctly selected and installed, it can ensure long-term stable and reliable operation. Therefore, the instrument users should first start from the root causes such as selection and installation, and then take the best interference elimination measures during use to minimize the probability of instrument failure, truly reflect its reliable and high-precision characteristics, better use of radar level meter, and provide accurate basis for production process control.
Previous article:Instructions for use of rotary level switch
Next article:What is the measurement blind area of ultrasonic level meter?
- Popular Resources
- Popular amplifiers
- How to Select a Compensated Silicon Pressure Sensor
- Compensated silicon pressure sensors and precision Delta-Sigma analog-to-digital converters for liquid level control and delivery systems
- How to Select a Compensated Silicon Pressure Sensor
- Software measures for single chip microcomputer system \"PC\" out of control
- Modern manufacturing strategies drive continuous improvement in ICT online testing
- Methods for Correlation of Contact and Non-Contact Measurements
- Keysight Technologies Helps Samsung Electronics Successfully Validate FiRa® 2.0 Safe Distance Measurement Test Case
- From probes to power supplies, Tektronix is leading the way in comprehensive innovation in power electronics testing
- Seizing the Opportunities in the Chinese Application Market: NI's Challenges and Answers
- Tektronix Launches Breakthrough Power Measurement Tools to Accelerate Innovation as Global Electrification Accelerates
- Not all oscilloscopes are created equal: Why ADCs and low noise floor matter
- Enable TekHSI high-speed interface function to accelerate the remote transmission of waveform data
- How to measure the quality of soft start thyristor
- Intel promotes AI with multi-dimensional efforts in technology, application, and ecology
- ChinaJoy Qualcomm Snapdragon Theme Pavilion takes you to experience the new changes in digital entertainment in the 5G era
- Infineon's latest generation IGBT technology platform enables precise control of speed and position
- Two test methods for LED lighting life
- Don't Let Lightning Induced Surges Scare You
- Application of brushless motor controller ML4425/4426
- Easy identification of LED power supply quality
- World's first integrated photovoltaic solar system completed in Israel
- Sliding window mean filter for avr microcontroller AD conversion
- What does call mean in the detailed explanation of ABB robot programming instructions?
- Europe's three largest chip giants re-examine their supply chains
- Breaking through the intelligent competition, Changan Automobile opens the "God's perspective"
- The world's first fully digital chassis, looking forward to the debut of the U7 PHEV and EV versions
- Design of automotive LIN communication simulator based on Renesas MCU
- When will solid-state batteries become popular?
- Adding solid-state batteries, CATL wants to continue to be the "King of Ning"
- The agency predicts that my country's public electric vehicle charging piles will reach 3.6 million this year, accounting for nearly 70% of the world
- U.S. senators urge NHTSA to issue new vehicle safety rules
- Giants step up investment, accelerating the application of solid-state batteries
- Guangzhou Auto Show: End-to-end competition accelerates, autonomous driving fully impacts luxury...
- Power supply management specifications and applications
- MSP FRAM MCUs Reduce Volatility for the IoT
- 5 years of experience in MCU development, looking for sponsor
- MSP430 FAQ: Instruction System
- Repair a Bull socket
- Increase performance in imaging applications by integrating DSP functions in FPGAs
- 7-inch capacitive screen, 4.3-inch resistive screen, plus WLE200N2-23 PCIE 2.4G wireless network card
- CC1310 Two-wire Serial Bootloader Solution
- If oil prices rise further...
- The first step after getting the GD350 development board