Current Transducer HAIS 50 .. 400-P
HAIS 50 .. 150-TP
For the electronic measurement of currents: DC, AC, pulsed..., with
galvanic separation between the primary circuit and the secondary
circuit.
I
PN
= 50 .. 400 A
I
PN
= 50 .. 150 A
All data are given with
R
L
= 10 kΩ
Electrical data
Primary nominal Primary current
Type
rms current
I
PN
(A)
measuring range
I
PM
(A)
50
±150
HAIS 50-P/50-TP
1)
100
±300
HAIS 100-P/100-TP
1)
150
±450
HAIS 150-P/150-TP
1)
200
±600
HAIS 200-P
400
±600
HAIS 400-P
G
Th
Theorical sensitivity @
I
PN
0.625
V/
I
PN
V
out
Analog output voltage @
I
P
V
OE
+(0.625·I
P
/
I
PN
) V
2)
V
ref
Reference voltage
Output voltage
2.5 ±0.025
V
Output impedance
typ. 200
Ω
Load impedance
≥200
kΩ
R
L
Load resistance
≥2
kΩ
R
out
Output internal resistance
<5
Ω
C
L
Capacitive loading (±20 %)
4.7
nF
3)
U
C
Supply voltage (±5 %)
5
V
I
C
Current consumption @
U
C
= 5 V
<19
mA
Features
● Hall effect measuring principle
● Galvanic separation between
primary and secondary circuit
● Insulation test voltage 2500 V
● Low power consumption
● Single power supply +5 V
● Fixed offset & sensitivity
● Insulating plastic case recognized
according to UL 94-V0.
Advantages
● Small size and space saving
● Only one design for wide current
ratings range
● High immunity to external
interference
●
V
ref
IN/OUT.
Accuracy - Dynamic performance data
X
ε
L
TCV
OE
TCV
ref
Accuracy
4)
@
I
PN
,
T
A
= 25° C
Linearity error 0 ..
I
PM
Temperature coefficient of
V
OE
Temperature coefficient of
V
ref
≤± 1
% of
I
PN
≤±0.5
% of
I
PN
≤±0.3
mV/K
≤±0.01
%/K
≤±0.015
%/K
≤±0.2
mV/K
≤±0.05 % of reading/K
V
ref
±0.025
V
% of
I
PN
% of
I
PN
µs
µs
A/µs
mVpp
mVpp
kHz
Applications
● AC variable speed drives and
servo motor drives
● Static converters for DC motor
drives
● Battery supplied applications
● Uninterruptible Power Supplies
(UPS)
● Switched Mode Power Supplies
(SMPS)
● Power supplies for welding
applications.
(+25 .. +85 °C)
(-40 .. +25 °C)
TCV
OE
/V
ref
Temperature coefficient of
V
OE
/V
ref
TCG
Temperature coefficient of
G
V
OE
Electrical offset voltage @
I
P
= 0,
T
A
= 25 °C
V
OM
Magnetic offset voltage @
I
P
= 0
after an overload of
I
PM
HAIS 50-P/TP
<±0.5
HAIS 100-P/TP..400-P<±0.4
t
ra
Reaction time to 10 % of
I
PN
step
<3
t
r
Step response time to 90 % of
I
PN
<5
di/dt
di/dt
accurately followed
>100
V
no
Output voltage noise (DC .. 10 kHz)
<15
(DC .. 1 MHz)
<40
5)
BW
Frequency bandwidth (-3 dB)
DC .. 50
Notes:
1)
Application domain
● Industrial.
-TP version is equipped with a primary bus bar; Temperature of primary bus bar
should not exceed 100 °C
2)
It is possible to overdrive
V
ref
with an external reference voltage between
1.5 V - 2.8 V providing its ability to sink or source approximately 5 mA
3)
Maximum supply voltage (not operating) <6.5 V
4)
Excluding offset and magnetic offset voltage
5)
Small signal only to avoid excessive heatings of the magnetic core.
Page 1/3
74.83.25.000.0, 74.83.34.000.0, 74.83.39.000.0, 74.83.44.000.0, 74.83.48.000.0, 74.70.25.000.0, 74.70.34.000.0, 74.70.39.000.0
26November2014/Version 13
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Current Transducer HAIS 50 .. 400-P and HAIS 50 .. 150-TP
General data
T
A
T
S
m
Ambient operating temperature
Ambient storage temperature
Mass (in brackets: TP version)
Standard
-40 .. +85
°C
-40 .. +85
°C
20 (30)
g
EN 50178: 1997
Insulation coordination
U
d
U
e
Û
W
d
Cp
d
CI
CTI
Rms voltage for AC insulation test, 50 Hz, 1 min
Partial discharge extinction rms voltage @ 10 pC
HAIS 50 .. 400-P
HAIS 50 .. 150-TP
Impulse withstand voltage 1.2/50 µs
Creepage distance
Clearance distance
Comparative Tracking Index (group I)
2.5
>1
>1.4
8
Min
>8
>8
>600
kV
kV
kV
kV
mm
mm
Applications examples
According to EN 50178 and IEC 61010-1 standards
and following conditions:
● Over voltage category OV 3
● Pollution degree PD2
● Non-uniform field
EN 50178
d
Cp
,
d
CI
,
Û
W
Basic insulation
Reinforced insulation
Rated insulation voltage
1000 V
600 V
IEC 61010-1
Nominal voltage
1000 V
300 V
Safety
This transducer must be used in limited-energy secondary circuits according to
IEC 61010-1.
This transducer must be used in electric/electronic equipment with respect to
applicable standards and safety requirements in accordance with the manufacturer’s
operating instructions.
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can carry hazardous
voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury
and/or cause serious damage.
This transducer is a build-in device, whose conducting parts must be inaccessible
after installation.A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
Page 2/3
26November2014/Version 13
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice
www.lem.com
Dimensions HAIS 50 .. 400-P and HAIS 50 .. 150-TP
(in mm)
HAIS 50..400-P
Front view
33
15
HAIS 50..150-TP
Front view
33
Right view
8
29
16
29
0.5
3.5
3
0.5
3
2-D 1.0
4-0.25x0.45
1.5
6
2-D 1.0
Bottom view
3-P 1.8
Bottom view
3-P 1.8
1.5
10
19.9
5
1
1
3.5
4.3
4
14.5
11
11
6.5
4.3
5
6.5
11
4
1.5
14.5
11
T ermina l P in Identifica tion
1. . . +5 V
2. . . 0 V
3. . . OUTP UT
4. . .
V
(IN/OUT)
5. . . C ore E arth (*)
6. . . NC
ref
Required Connection Circuit
circuit
R ecommended connection
1
2
3
4
5
47nF
4.7nF
47nF
+5 V
0V
O UT P UT
1.5
6
V
ref
(IN/OUT)
Recommended PCB hole:
Pin 1-4: 0.7
±0.1mm
Pin 5-6: 1.5
±0.1mm
Primary bus bar: 2.3
±0.1mm
Operation Principle
+
25.9
14
6
6
U
c
out
ref
V
V
I
P
(IN/OUT)
General tolerance:
±0.2mm
Unit : mm
(*)
0V
should be connected to 0 V of Power Supply for better dv/dt immunity.
Arrow indicates positive current direction.
Page 3/3
26November2014/Version 13
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without prior notice