Transformer gas protection circuit
Source: InternetPublisher:通通 Keywords: Protection circuit transformer contact intermediate relay Updated: 2021/07/09
Oil-immersed transformer gas protection circuit . When a minor fault (light gas) occurs inside the transformer, the
upper contact KGl-2 of the gas relay KG is closed and acts as an alarm signal. When a serious fault (heavy gas) occurs inside the transformer . The lower contact KG3-4 of KG
is closed, usually acting on the tripping mechanism YR of the circuit breaker QF through the intermediate relay
KM, and at the same time sending out a trip
signal through the signal relay KS. But when KG3-4 is closed, you can also use the switching piece XB to switch, so that the KS coil is connected in series with the current limiting resistor R and acts on the alarm signal.
Since the lower contact KG3-4 of the gas relay may "jib" (poor contact) during a severe gas fault, therefore. In order to
connect the tripping circuit stably and the circuit breaker to trip reliably, the upper contact KMl-2 of the intermediate relay KM is used as a "self-holding" contact
. As soon as KG3-4 is closed due to heavy gas action, KM is activated, and the upper contact KM1-2 is closed to maintain the operating state.
At the same time, the lower contact KM3-4 is also closed, causing the circuit breaker QF to trip. After the circuit breaker trips, its auxiliary contact QFl-2 disconnects the tripping circuit to reduce
the work of the intermediate relay contact, while its other pair of auxiliary contacts QF3-4 cuts off the self-holding circuit of the intermediate relay KM, so that the intermediate relay KM Relay
returns.
- How to Make a Simple Chicken Incubator
- Homemade Bluetooth controlled car using HC-05 Bluetooth module to communicate with mobile phone
- A simple door handle touch alarm circuit
- Introduction to the internal structure of the Delta winding motor
- Squirrel cage asynchronous motor reverse braking control circuit
- Controlling stepper motors with wireless remote control transceiver and PE-51 board
- Motor control circuit for starting and running without phase loss
- Design and production of wireless multi-location control switch circuit
- Homemade short circuit alarm device
- Ultra-short wave item left behind reminder alarm
- Low voltage circuit breaker protection circuit e
- Overload protection circuit for high-voltage motors
- Thyristor resistance-capacitance protection circuit c
- The structure and working principle diagram of various protection circuits d
- The structure and working principle diagram of various protection circuits b
- Motor waterproof protection circuit
- Stabilized power supply undervoltage protection circuit
- One of the series-type regulated power supply circuit protection circuits
- Thyristor overcurrent protection circuit 2
- Typical control circuit of CT8 type spring operating mechanism