Application of PROFIBUS hub of Yitong Chuanglian in sewage treatment station

Publisher:甜美瞬间Latest update time:2024-10-09 Source: elecfansKeywords:PROFIBUS  hub Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

Deep sewage treatment refers to the further water treatment process of urban sewage or industrial wastewater after primary and secondary treatment in order to meet certain reuse water standards so that the sewage can be reused as water resources in production or life.


The following figure is a data acquisition network topology diagram of the equipment in the expanded sewage deep treatment station. The system uses Siemens CPU315-2 DP as the PROFIBUS-DP network master station; three Siemens CPU226 as PROFIBUS-DP network slave stations; one Siemens CPU314-2DP as a PROFIBUS-DP network slave station; and a CP5611 card installed on the PC as a PROFIBUS-DP network slave station. The PROFIBUS hub YT-PB-HUB is used to connect all the slave station segment networks in parallel, and then connect to the master station.


YT-PB-HUB is a PROFIBUS hub suitable for industrial environments. The product has passed the EMC electromagnetic compatibility test standard. It provides a communication solution that uses twisted pair as the communication transmission cable when the PROFIBUS signal is in the communication state of 0-12MBPS, transforms the bus into a star network, and extends the PROFIBUS communication distance to about 1200 meters. Another significant function is to isolate the PROFIBUS bus, especially for bus structures without any surge protection measures. In order to avoid equipment operation risks, a PROFIBUS hub needs to be connected in series. On the bus with the PROFIBUS hub, YT-PB-HUB also enhances the driving ability of the PROFIBUS signal to drive the bus to connect more PROFIBUS devices. YT-PB-HUB requires external power supply, 10--30V DC wide voltage input, and withstand voltage of 4000V. At the same time, the built-in transient suppression components and 16KV ESD surge protection can effectively prevent the PROFIBUS bus from being damaged by surges such as lightning strikes and surges, ensuring that the PROFIBUS equipment and PROFIBUS bus operate in a safe and reliable state.


Keywords:PROFIBUS  hub Reference address:Application of PROFIBUS hub of Yitong Chuanglian in sewage treatment station

Previous article:Modbus communication protocol 4-20ma/0-10v to RS485 digital analog signal isolation AD conversion module
Next article:Application of PROFIBUS gateway in chemical engineering projects

Recommended ReadingLatest update time:2024-11-23 11:24

PROFIBUS-DP communication between SIMATIC S7-1500 PLC and ET200MP
It is very convenient to use CPU1516-3PN/DP as the master station and the distributed modules as slave stations to establish communication with these modules (such as ET200MP, ET200S, EM200M and EM200B, etc.) through PROFIBUS fieldbus. Such solutions are mostly used in distributed control systems. This PROFIBUS comm
[Embedded]
PROFIBUS-DP communication between SIMATIC S7-1500 PLC and ET200MP
Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号