How to eliminate signal interference when repairing a frequency converter

Publisher:幸福之路Latest update time:2024-03-07 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

The inverter is divided into three types of electromagnetic interference:

1. Harmonic interference: The rectifier circuit will generate harmonic current, which will cause voltage drop on the impedance of the power supply system, resulting in voltage waveform distortion. This distorted voltage will interfere with many electronic devices (because most electronic devices can only work under sine wave voltage conditions). Common voltage distortion is that the top of the sine wave becomes flat. When the harmonic current is constant, the voltage distortion is more serious in the case of weak power supply. The characteristic of this interference is that it will interfere with the equipment using the same power grid, regardless of the distance between the equipment and the inverter;

2. Radio frequency conduction interference: Since the load voltage is pulsed, the inverter draws current from the power grid in a pulsed form. This pulsed current contains a large amount of high-frequency components, forming radio frequency interference. The characteristic of this interference is that it will interfere with the equipment using the same power grid, regardless of the distance between the equipment and the inverter.

3. RF radiation interference: RF radiation interference comes from the input and output cables of the inverter. In the above-mentioned RF conducted emission interference, when there is RF interference current on the input and output cables of the inverter, since the cable is equivalent to an antenna, electromagnetic wave radiation will inevitably be generated, resulting in radiation interference. The PWM voltage transmitted on the inverter output cable also contains a lot of high-frequency components, which will generate electromagnetic wave radiation and form radiation interference. The characteristic of radiation interference is that when other electronic devices are close to the inverter, the interference phenomenon becomes serious.

The following are the main steps to resolve on-site interference:

1. Use software anti-interference measures: Specifically, adjust the carrier frequency of the inverter through the inverter's human-machine interface to a suitable range. If this method does not work, the following hardware anti-interference measures can only be taken.

2. Correct grounding: Through the specific investigation on site, we can see that the grounding situation on site is not ideal. Correct grounding can effectively suppress external interference in the system and reduce the interference of the equipment itself to the outside world. It is the most effective measure to solve the interference of the inverter. Specifically, it is to do the following:

(1) The main circuit terminal PE (E, G) of the inverter must be grounded. The grounding can be shared with the motor of the inverter, but not with other equipment. A separate grounding stake must be driven, and the grounding point should be as far away from the grounding point of weak current equipment as possible. At the same time, the cross-sectional area of ​​the inverter grounding wire should be no less than 4mm2, and the length should be controlled within 20m.

(2) For the ground wires of other electromechanical equipment, the protective ground and working ground should be separately grounded and finally connected to the electrical grounding point of the distribution cabinet. The shielding ground of the control signal and the shielding ground of the main circuit conductor should also be separately grounded and finally connected to the electrical grounding point of the distribution cabinet.

3. Shielding interference sources: Shielding interference sources is a very effective way to suppress interference. Usually, the inverter itself is shielded with an iron shell to prevent its electromagnetic interference from leaking, but the output line of the inverter is best shielded with a steel pipe, especially when the inverter is controlled by an external signal (outputting a 4~20mA signal from the controller), the control signal line is required to be as short as possible (generally within 20m), and a shielded twisted pair must be used, and it must be completely separated from the main circuit line (AC380) and the control line (AC220V). In addition, the electronic sensitive equipment lines in the system are also required to use shielded twisted pairs, especially pressure signals. And all signal lines in the system must not be placed in the same piping or cable trough as the main circuit line and control line. In order to make the shielding effective, the shielding layer must be reliably grounded.

4. Reasonable wiring: The specific methods are:

(1) The power cord and signal cord of the equipment should be kept as far away from the input and output cords of the inverter as possible.

(2) The power lines and signal lines of other equipment should not be parallel to the input and output lines of the inverter.

If the above methods still don’t work, try the following:

5. Interference isolation: The so-called interference isolation refers to isolating the interference source and the part susceptible to interference from the circuit so that they do not have electrical contact. Usually, an isolation transformer is used on the power line between the power supply and the amplifier circuits such as the controller and the transmitter to avoid conducted interference. The power isolation transformer can also be a noise isolation transformer.

6. Set up filters in the system line: The function of the equipment filter is to suppress the interference signal from the inverter through the power line to the power supply and motor. To reduce electromagnetic noise and loss, an output filter can be set on the output side of the inverter; to reduce interference to the power supply, an input filter can be set on the input side of the inverter. If there are sensitive electronic devices such as controllers and transmitters in the line, a power noise filter can be set on the power line of the device to avoid conducted interference. Filters can be divided into the following types according to their use locations:

(1) Input filter

There are usually two types:

a. Line filter: It is mainly composed of an inductor coil, which weakens the high-frequency harmonic current by increasing the impedance of the line at high frequencies.

b. Radiation filter: Mainly composed of high-frequency capacitors, it will absorb high-frequency harmonic components with radiation energy.

(2) The output filter is also composed of an inductor coil. It can effectively weaken the high-order harmonic components in the output current. It not only plays an anti-interference role, but also can weaken the additional torque caused by the harmonic current generated by the high-order harmonics in the motor. For the anti-interference measures at the output end of the inverter, the following aspects must be paid attention to:

a. The output end of the inverter is not allowed to be connected to a capacitor, so as to avoid generating a large peak charging (or discharging) current at the moment when the power tube is turned on (off), thereby damaging the power tube;

b. When the output filter is composed of an LC circuit, the side of the capacitor connected to the filter must be connected to the motor side.

7. Use reactors: The proportion of low-frequency harmonic components (5th harmonic, 7th harmonic, 11th harmonic, 13th harmonic, etc.) in the input current of the inverter is very high. In addition to interfering with the normal operation of other equipment, they also consume a lot of reactive power, which greatly reduces the power factor of the line. Connecting a reactor in series in the input circuit is an effective way to suppress low-harmonic currents. Depending on the wiring position, there are mainly two types:

(1) AC reactor: connected in series between the power supply and the input side of the inverter. Its main functions are:

a. Improve the power factor to (0.75-0.85) by suppressing harmonic current;

b. Reduce the impact of surge current in the input circuit on the inverter;

c. Reduce the impact of power supply voltage imbalance.

(2) DC reactor: It is connected in series between the rectifier bridge and the filter capacitor. Its function is relatively simple, which is to weaken the high-order harmonic components in the input current. However, it is more effective than AC reactor in improving the power factor, which can reach 0.95, and has the advantages of simple structure and small size.

Therefore, the anti-interference measures of the inverter mainly include installing AC reactors and filters on the incoming line of the inverter, using shielded cables for incoming and outgoing lines, and grounding the shielding layers of all cables together with the protective ground of the reactor, filter, inverter and motor, and keeping this grounding point separate from other grounding points and keeping a sufficient distance. At the same time, the signal cable and the power cable of the inverter should not be laid in parallel.

In addition, to prevent the inverter from interfering with signals and control loops, the controller, instrument and industrial computer need to be powered by a separate isolated power supply.

When there are high-frequency impact loads such as welding machines, electroplating power supplies, electrolytic power supplies, or places with slip ring power supply near the power supply system of the inverter, the inverter instruments themselves are prone to protection due to interference. Users are recommended to take the following measures:

1. On the input side of the inverter, add inductors and capacitors to form an LC filter network.

2. The power cord of the inverter is powered directly from the transformer side.

3. If conditions permit, a separate transformer can be used.

4. When using external switches and quantity control terminals for control, it is recommended to use shielded cables when the connection line is long. When the control line, main circuit, and power supply are all buried in the trench, in addition to the control line, which must use shielded cables, the main circuit line must use steel pipe shielding to reduce mutual interference and prevent malfunction of the inverter.

[1] [2]
Reference address:How to eliminate signal interference when repairing a frequency converter

Previous article:Based on RS60E series robot dedicated servo drive
Next article:Suppression of conducted noise interference sources in electric drive systems

Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号