In a factory, a human-machine interface usually needs to establish communication with multiple PLCs, and the locations of the devices are different. If wiring is required, it needs to be constructed in multiple places, which is troublesome. In this case, it is more convenient to establish communication between the human-machine interface and the PLC wirelessly. Because the wireless PPI protocol has a fast response speed and does not require programming, only configuration is required, so the PPI protocol network has more advantages. However, a special wireless data terminal is required to realize wireless PPI communication, and the matching of the setting parameters must also be considered during configuration.
This solution takes the human-machine interface (Weluntong touch screen) as an example to introduce the wireless PPI communication implementation process between the Weluntong touch screen and two S7-200Smart PLCs. In this solution, the Siemens PLC dedicated wireless communication terminal DTD434M is used as the hardware device to realize wireless communication.
1. Overview of the Solution
Through the European and American PLC dedicated wireless communication terminal DTD434M, the wireless PPI network can be stably and conveniently realized without changing the network parameters or the original program, and directly replacing the wired RS485 communication.
Wireless network diagram▼
2. Test equipment and parameters
● Touch screen: TK6071IQ × 1 unit
● 200SMART model: CPU SR20 × 2 units
● Wireless communication terminal: European and American PLC dedicated wireless communication terminal - DTD434MC × 3 pieces
● Data line: Siemens PLC dedicated 485 line × 1
● Touch screen data cable: Touch screen dedicated RS485 data cable × 1
● Master-slave relationship: 1 master and 2 slaves
● Communication interface: RS485 interface (two-wire system)
● Communication parameters: 9600, 8, E, 1
● Power supply: 9-24VDC
● Transmission distance: 100m, 500m, 1KM, 3KM, 20KM
3. Detailed explanation of the functions of wireless communication terminals for European and American PLCs
Wireless data communication terminal DTD434M, with built-in RS232/RS485 dual interface, can directly replace traditional wired solutions such as RS232/RS485 without programming. It can form a wireless measurement and control network with Siemens PLC, configuration software, human-machine interface, touch screen, measurement and control terminal and other industrial control products.
■ Main features of DTD434M:
◆ Directly replace the wired RS485 solution to achieve wireless networking communication;
◆ Fully digital wireless encryption method ensures data security and reliability;
◆ Powered by DC 9~24V wide power supply voltage, average working current is less than 50mA;
◆ Communication interface: RS232/RS485;
◆ Support standard serial port protocols: Modbus RTU protocol, PPI protocol.
4. Wiring method
1. Wiring between touch screen and wireless device
Step 1: Connect the red wire of the touch screen RS485 data line to the A port of DTD434MC; connect the black wire of the touch screen RS485 data line to the B port of DTD434MC.
Step 2: Set the last digit (K8-8) of the wireless communication terminal switch to the top
Step 3: Connect the wireless communication terminal to the antenna
Step 4: After all wiring is completed, power the touch screen and wireless communication terminal
2. Wiring between PLC and wireless devices
5. Weiluntong touch screen realizes PPI master station
Open "Wei Lun Tong touch screen 1 master 2 slave PPI routine.emtp"
1. System parameter settings
2. Touch screen screen production
3. I point setting of slave station No. 1
4. Q point setting of slave station No. 1
5. I point setting of slave station No. 2
6. Q point setting of slave 2
7. Physical wiring diagram
6. Siemens PLC realizes PPI slave
1. PLC parameter setting
2. Set the PLC address
Set one PLC address to 1 and the other PLC address to 2
Select "Parameters - Module Parameters - 485 Serial Port"
3.CPU mode
Select: RUN to download the program to the PLC
4. Physical wiring diagram
7. Wireless communication test
1. Touch screen output signal
Use the button on the touch screen to give the Q point signal to slave station No. 1 and see if the Q point corresponding to 200SMART is lit. If it is lit, it means the communication is normal.
2. PLC input signal
Give a signal to slave station No. 1 externally to see if the corresponding point on the touch screen is lit. If it is lit, it means the communication is normal.
Previous article:PLC Control Circuit Example Analysis
Next article:What does an AC contactor consist of?
Recommended ReadingLatest update time:2024-11-17 00:46
- Popular Resources
- Popular amplifiers
- Huawei's Strategic Department Director Gai Gang: The cumulative installed base of open source Euler operating system exceeds 10 million sets
- Analysis of the application of several common contact parts in high-voltage connectors of new energy vehicles
- Wiring harness durability test and contact voltage drop test method
- Sn-doped CuO nanostructure-based ethanol gas sensor for real-time drunk driving detection in vehicles
- Design considerations for automotive battery wiring harness
- Do you know all the various motors commonly used in automotive electronics?
- What are the functions of the Internet of Vehicles? What are the uses and benefits of the Internet of Vehicles?
- Power Inverter - A critical safety system for electric vehicles
- Analysis of the information security mechanism of AUTOSAR, the automotive embedded software framework
Professor at Beihang University, dedicated to promoting microcontrollers and embedded systems for over 20 years.
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
- [Project source code] Regenerate hps_0.h file after changing Qsys based on FPGA Altera SOC
- Conflict between css8 and IEC60730_msp430g2553_example project, clock aspect
- Designing a smarter skylight
- Experience in Application Test of DSP External SRAM
- ADS amplifierMRF8P9040N verification simulation
- Problems with current sinking and current sourcing of the I/O port of the msp430 microcontroller
- C language structure pointer definition problem help
- From fail to pass, what does DDR debugging go through?
- Understand 20 types of analog circuits in one article
- Human life status monitoring controller based on GD32E231