The No. 1 main transformer SFSZ8-25000/110 of a 110kV substation was damaged due to an accident. The company returned the transformer to the manufacturer and formed a joint investigation team to analyze the cause of the accident and formulate a repair plan. The weather was clear on the day of the accident, with a temperature of up to 39°C. At 13:26, the operator suddenly heard an explosion and abnormal sounds inside the No. 1 main transformer. Then the heavy gas and differential protection of the No. 1 main transformer were activated, disconnecting the three-side circuit breakers of the main transformer, and the transformer was out of operation.
Transformer damage
(1) Winding. The upper 3-4 turns of the low-voltage winding a and b phases were short-circuited and burned, and arched upward, with the insulation at the upper end damaged.
(2) Iron core. The edges of the core columns of the corresponding low-voltage winding phases a and b were burned. Two pressure nail limbs of the upper clamp phase a fell off from the weld, and one pressure nail limb of phase c also fell off.
(3) Insulation of the device body. The 50mm thick laminated wood board at the end of phase a was broken, and two Φ42 pressure nails together with the Φ55 pressure nail bowl penetrated. Phase b also had a pressure nail that penetrated the pressure nail limb board. The paper tubes inside the low-voltage windings of phases a and b were also partially damaged.
Accident Analysis
Based on the damage of the transformer, after intuitive analysis, it is believed that the transformer
The accident caused overvoltage and short circuit shock.
1 Overvoltage shock
The low-voltage winding of this transformer is continuous, as shown in Figure 1. When the continuous winding is subjected to the wave, the potential difference between the first few segments is high, especially the axial and radial synthetic electric fields at K are very strong, which is very easy to be broken down when overvoltage occurs. From the short-circuit burning of 3-4 turns of the low-voltage winding a phase and b phase and the burning of the core column edge, it can be explained that the low-voltage winding a phase and b phase are subjected to overvoltage impact, which breaks down the core and forms a turn-to-turn breakdown short circuit.
2 Short circuit shock
Figure 1 Schematic diagram of continuous winding line segment
The transformer will generate large axial and radial forces when short-circuited. The radial force Fd causes the outer winding to be subjected to outward tension and the inner winding to be subjected to inward pressure (as shown in Figure 2a). The axial force can be divided into axial internal force and axial external force. The axial internal force Fq1 compresses the winding (as shown in Figure 2b), and the axial external force Fq2 is caused by the imbalance of the ampere-turns of the inner and outer windings. It causes the inner and outer windings to produce relative displacement and increase the asymmetry (as shown in Figure 2c). The pressure nail limbs on the transformer clamp fall off, the laminated wood board breaks, and the pressure nails penetrate the pressure plate, indicating that a large electric force is generated in the axial direction; and the low-voltage inner paper tubes of phases a and b break, which is caused by the low-voltage windings being subjected to inward pressure. These phenomena indicate that the transformer is impacted by the short-circuit current. The transformer is short-circuited because the low-voltage windings of phases a and b break through the core under overvoltage.
With the above two basic analyses, the remaining question is what causes the overvoltage of phases a and b. On the day of the fault, the weather was clear, there was no atmospheric overvoltage caused by lightning, and there was no temporary overvoltage. It might be an operating overvoltage, and there are only several types of operating overvoltage: ① arc grounding overvoltage of neutral point ungrounded system; ② overvoltage of no-load line closing; ③ overvoltage of no-load line cutting off; ④ overvoltage of no-load transformer cutting off, etc. According to the operation records of the day, it can be seen that ②③④ are impossible to occur, leaving only ①. The 10kV side of the transformer adopts D-type connection, without neutral point, and belongs to the neutral point ungrounded system. When single-phase intermittent arc grounding occurs, arc overvoltage will be formed on the non-fault phase, and the overvoltage on the non-fault phase can reach up to 3.5 times the rated voltage. The transformer a and b phases are subjected to overvoltage, and it may be single-phase intermittent arc grounding of phase c. Therefore, we searched the transformer's low-voltage phase C line and found that the wall bushing from the 10kV line to the switch room had exploded and the metal conductor was partially grounded.
So far, the cause of the accident has been found: first, there is a defect in the 10kV c-phase wall bushing, which exploded under high temperature and heavy load, forming a 10kVc-phase single-phase intermittent arc grounding, thereby forming arc overvoltage on phase a and phase b, causing the end of the low-voltage winding of phase a and phase b to break through the iron core, causing the transformer to short-circuit. Phase a and phase b then form a turn-to-turn short circuit, the main transformer differential protection and heavy-watt period protection are activated, disconnecting the three-side circuit breakers of the transformer, and the transformer is out of operation.
Figure 2 Winding stress
5 Emergency repair plan and corrective measures
In view of the damage of the transformer, a detailed emergency repair plan was formulated, including rewinding the winding, reprocessing and replacing the core silicon steel sheets, and remaking and processing the insulation parts of the transformer body. At the same time, the following rectification measures were formulated.
(1) From this accident, it can be seen that the transformer has the weakness of weak resistance to overvoltage and short-circuit impact. When the manufacturer repaired the transformer, the following suggestions were put forward. ① Add a capacitor ring at the head end of the low-voltage winding, increase the insulation of the end and tail turns, and increase the oil channel to ensure that it will not break down during overvoltage impact and improve the impact electrical strength. ② Achieve "axial compression and radial support". For axial compression requirements: a. Replace the laminated wood board with epoxy laminated glass cloth board with higher hardness and better insulation strength; b. Perform a close pressure treatment on the winding pads and end ring pads; c. Dry the winding at constant pressure; d. The welding control of the nail limb plate must be strengthened, and a support plate must be added. For radial support requirements: the soft paper tube inside the low-voltage winding is replaced with a hard paper tube as the skeleton to prevent radial electric force from compressing the low-voltage winding and causing the core to break down and ground.
(2) Transformer operators of power supply companies should strengthen equipment inspection and equipment defect management during operation to prevent accidents.
Previous article:Analysis of overload capacity of dry-type transformer
Next article:Transformer energy meters develop from mechanical to electronic
Recommended ReadingLatest update time:2024-11-16 19:37
- Popular Resources
- Popular amplifiers
- Introduction to Transformer Natural Language Processing: Solving Problems with Hugging Face Libraries and Models
- CVPR 2023 Paper Summary: Vision Applications and Systems
- CVPR 2023 Paper Summary: Video: Low-Level Analysis, Motion, and Tracking
- CVPR 2023 Paper Summary: Photogrammetry and Remote Sensing
- MathWorks and NXP Collaborate to Launch Model-Based Design Toolbox for Battery Management Systems
- STMicroelectronics' advanced galvanically isolated gate driver STGAP3S provides flexible protection for IGBTs and SiC MOSFETs
- New diaphragm-free solid-state lithium battery technology is launched: the distance between the positive and negative electrodes is less than 0.000001 meters
- [“Source” Observe the Autumn Series] Application and testing of the next generation of semiconductor gallium oxide device photodetectors
- 采用自主设计封装,绝缘电阻显著提高!ROHM开发出更高电压xEV系统的SiC肖特基势垒二极管
- Will GaN replace SiC? PI's disruptive 1700V InnoMux2 is here to demonstrate
- From Isolation to the Third and a Half Generation: Understanding Naxinwei's Gate Driver IC in One Article
- The appeal of 48 V technology: importance, benefits and key factors in system-level applications
- Important breakthrough in recycling of used lithium-ion batteries
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
- [ESP32-S2-Kaluga-1 Review] 1. Click on the screen?
- Looking for a chip
- [Xingkong Board Python Programming Learning Main Control Board] Part 3: Comparison of Several Programming Methods Recommended by Xingkong Board
- Blog post: How to design high voltage system solutions with higher reliability, smaller size and lower cost
- Understanding of variable frequency power supply: What types of loads does variable frequency power supply have?
- Drive control design
- 【Multi-function thermal imager】Extension board production
- What are the similarities and differences between pulse transformers, power frequency transformers, and high frequency transformers?
- The Academic Degrees Committee of the State Council voted to approve the proposal to "establish integrated circuit as a first-level discipline"!
- Digital Signal Processor (DSP) – Machine Vision Applications