1. When repairing a switching power supply , first use a multimeter to check whether each power component is short-circuited, such as the power supply rectifier bridge, switch tube , high-frequency high-power rectifier tube; whether the high-power resistor that suppresses surge current is burned out. Then check whether the resistance of each output voltage port is abnormal. If the above components are damaged, they need to be replaced.

2. After completing the first step, if it still cannot work normally after turning on the power, then you need to test the power factor module (PFC) and pulse width modulation component (PWM), consult relevant information, and be familiar with the functions of each pin of the PFC and PWM modules and the necessary conditions for the normal operation of the modules.

3. Then, for the power supply with PFC circuit, it is necessary to measure whether the voltage across the filter capacitor is about 380VDC. If there is a voltage of about 380VDC, it means that the PFC module is working properly. Then detect the working status of the PWM component, measure whether its power input terminal VC, reference voltage output terminal VR, start control Vstart/Vcontrol terminal voltage is normal, use 220VAC/220VAC isolation transformer to power the switching power supply, and use an oscilloscope to observe whether the waveform of the CT terminal of the PWM module to the ground is a well-linear sawtooth wave or triangle, such as the TL494 CT terminal is a sawtooth wave, and the FA5310 CT terminal is a triangle wave. Whether the waveform of the output terminal V0 is an orderly narrow pulse signal.

4. In the practice of switching power supply maintenance, many switching power supplies use UC38×× series 8-pin PWM components. Most power supplies cannot work because the power supply startup resistor is damaged or the chip performance is degraded. When R is disconnected and there is no VC, the PWM component cannot work and needs to be replaced with a resistor with the same power resistance as the original. When the starting current of the PWM component increases, the R value can be reduced until the PWM component can work normally. When repairing a GE DR power supply, the PWM module is UC3843, and no other abnormalities are found in the detection. After connecting a 220K resistor to R (220K), the PWM component works and the output voltage is normal. Sometimes due to a peripheral circuit failure, the 5V voltage at the VR end is 0V, and the PWM component does not work. When repairing the Kodak 8900 camera power supply, this situation is encountered. Disconnect the external circuit connected to the VR end, VR changes from 0V to 5V, the PWM component works normally, and the output voltage is normal.

5. When there is no voltage of about 380VDC on the filter capacitor, it means that the PFC circuit is not working properly. The key detection pins of the PFC module are the power input pin VC, the start pin Vstart/control, the CT and RT pins and the V0 pin. When repairing a Fuji 3000 camera, there is no 380VDC voltage on the filter capacitor on the test board. The VC, Vstart/control, CT and RT waveforms and the V0 waveform are all normal. The field effect power switch tube G pole has no V0 waveform. Since FA5331 (PFC) is a patch component, the machine has a cold solder joint between the V0 terminal and the board after a long time of use, and the V0 signal is not sent to the field effect tube G pole. Solder the V0 terminal to the solder joint on the board, and use a multimeter to measure the filter capacitor to have a 380VDC voltage. When the Vstart/control terminal is low, the PFC cannot work, so it is necessary to detect the relevant circuits connected to its terminal and the periphery.

In short, the switching power supply circuits are easy or difficult, the power is large or small, and the output voltage is varied. As long as you grasp the core things, that is, fully familiar with the basic structure of the switching power supply and the characteristics of the PFC and PWM modules, their basic working conditions, follow the above steps and methods, and do more hands-on maintenance of the switching power supply, you can quickly eliminate the switching power supply fault and achieve twice the result with half the effort.

The general situation is:

1. If the switching power supply does not start oscillating, generally check whether the switching frequency is correct, whether the protection circuit is blocked, whether the voltage feedback circuit and current feedback circuit are OK, and whether the switch tube is broken down.

2. The transformer heats up or makes a buzzing sound, which is usually caused by incorrect switching frequency;

3. Output voltage Power supply If the indicator light flashes, it usually means there is a short circuit on the secondary side.



Reference address:Switching power supply maintenance steps and experience

Previous article:LED lighting power supply system based on PFC controller
Next article:The inspiration brought to us by the principle of high-frequency switching power supply

Latest Power Management Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号