Study on Active DC Filter for HVDC Transmission---Research on Hysteresis Comparison Control

Publisher:快乐旅人Latest update time:2011-11-15 Source: 互联网Keywords:DC Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere
Study on control method using hysteresis comparison

High-voltage direct current (HVDC) transmission systems generate a large number of harmonics during the rectification and inversion process. These harmonics not only interfere with the audio communication system along the line, but also cause some adverse consequences within the power system. The traditional solution is to connect multiple groups of LC resonant passive filters in parallel on the AC and DC sides of the converter station. With the increasing requirements for the equivalent harmonic interference current index of the HVDC transmission system, it is difficult to solve the harmonic interference problem on the DC side of the HVDC system by simply adding multiple groups of passive filters. With the development of power electronics and computer technology, active filtering technology has gradually been applied to filtering on the DC side of the HVDC transmission system. Compared with the passive filter on the DC side, the DC active filter (ADF) has many advantages, mainly:

(1) In the audio range (300 Hz to 3000 Hz), the DC active filter has a strong suppression effect on each harmonic;

(2) The smaller the equivalent harmonic interference current that needs to be suppressed, the higher the performance-price ratio of the ADF;

(3) When the frequency changes or the resonance is out of tune, the ADF can also accurately track and compensate without any overload problem;

(4) Small footprint.

At present, active and passive hybrid DC active filters are mostly used in projects. This can reduce the insulation level and capacity of ADF, give full play to the advantages of passive filters in absorbing high-power harmonic currents and the high efficiency of active filters in suppressing changing frequencies and multiple harmonic currents, and achieve the best filtering effect and economic benefits.

The filtering effect of a DC active filter depends on whether it can accurately track harmonic currents and generate compensation currents in real time. This requires that the DC active filter not only has good detection accuracy, but also requires it to have a fast dynamic response speed. Reference [4] studied the tracking PWM control method. The simulation and experimental results show that the tracking effect of the hysteresis instantaneous value comparison method is the best. This paper adopts the hysteresis instantaneous value PWM comparison method in the DC active filter, and conducts experimental and simulation research on the tracking and compensation effects of this control method.

1 System structure of DC active filter

The harmonic voltage and harmonic current on the DC side of the high-voltage direct current transmission system are mainly 12th, 24th, 36th, etc. There are two ways to install active filters in the system: series or parallel. The DC filter in this article is shown in Figure 1. It is a hybrid filter system composed of a 12/24th double-tuned passive filter and an active filter in series, which are connected in parallel between the DC busbars. In the system, the active filter is connected in series to the bottom of the passive filter, and the other end is connected to the DC neutral line to reduce the insulation level of the active filter. The role of the active filter here is to reduce the double-tuned filter in

Study on the hysteresis comparison control method of DC active filter for high voltage DC transmission

The impedance of the resonance point improves its filtering effect. In addition, it filters out other harmonics that the passive filter cannot filter out (such as the 18th harmonic and some higher harmonics that seriously interfere with communication lines). The content of these harmonic components is relatively small.

2 Working principle of DC active filter Figure 2 shows the equivalent circuit diagram of the DC side of the high-voltage DC transmission system. In the figure, is the harmonic voltage source in the system, ZS is the internal impedance of the harmonic source, ZL is the DC transmission line impedance, Zf is the impedance of the passive filter (including the leakage reactance of the coupling transformer), is the harmonic voltage source injected into the system by the active filter, and this voltage source is related to the harmonic current on the DC bus. As can be seen from Figure 2, the harmonic current on the line consists of two parts: the harmonic current generated by and the harmonic current generated by. According to the superposition principle, when it works, the harmonic current on the line is: ==·(1) When it works, the harmonic current on the line is: ==·(2)

Therefore, the total harmonic current on the line is: =+=(3) By detecting the current on the line, the signal for PWM control of the inverter of the active filter is output, and then the equivalent voltage source required for compensating the harmonic current on the line and the active filter injection system is obtained. Let =-k(4)

From equations (3) and (4), we can get: =·(5)

It can be seen from formula (5) that when k=0, the active filter does not work, and the harmonic current on the line depends on the filtering effect of the passive filter; when k>0, the active filter and the passive filter form a hybrid filter to jointly suppress the harmonic current on the line. It can also be seen that when k is large enough, the harmonic current on the line can be completely filtered out. In fact, k cannot be large enough, so the harmonic current can only be suppressed and eliminated to a certain extent.

3 DC active filter control system structure diagram According to the above analysis of the working principle of the active filter, the control system structure diagram of the active filter can be obtained as shown in Figure 3. The current on the line is detected by the current detection circuit, and the harmonic current signal on the line is obtained through the Butterworth low-pass filter circuit. The harmonic current signal is used as a given signal to generate a PWM control signal, and a deviation signal is obtained by comparing it with the active filter feedback signal. The hysteresis comparator obtains the PWM signal for controlling the on and off of the main circuit switch device according to the deviation signal, thereby obtaining a voltage that suppresses the line harmonic current, so as to achieve the purpose of suppressing harmonics by the active filter.

4 DC active current using hysteresis instantaneous value comparison method

Simulation of filter compensation performance

This paper uses the power electronic circuit automatic control system simulation software PECS developed by this research group for simulation. The voltage on the DC bus of this system is about 500V, the load is a resistive load, the current on the bus is about 51A, and the loop width of the hysteresis comparator in the control circuit is about 5% of the input error signal (the difference between the given signal and the feedback signal). The simulation results of the active filter are given below. Figure 4 shows the current waveform and spectrum of the line when only the passive filter is working, and Figure 5 shows the current waveform on the line when the passive and active filters are working at the same time, the compensation voltage waveform output by the active filter, and the spectrum of the current waveform.

Figure 1 Structure diagram of hybrid DC active filter system

Figure 2 Equivalent circuit diagram of DC active filter

Figure 3 DC active filter control system structure diagram

Figure 4 Current waveform and spectrum of the line when only the passive filter is working

(a) Current waveform on the line (b) Spectrum of the current waveform

Figure 5 Simulation results when passive and active filters work simultaneously

(a) Compensation voltage waveform output by active filter

(b) Current waveform on the line when passive plus active filter

(c) Current waveform spectrum of the line when passive plus active filter is used

Figure 6 Experimental waveform with only passive filter

Figure 7 Experimental waveform of passive plus active filter

5 DC active filtering using hysteresis instantaneous value comparison method

Experimental study on compensation performance of the

Using Tektronix's TD340 digital oscilloscope, the experimental waveforms of passive filter only and passive plus active filter are obtained, as shown in Figure 6 and Figure 7. It can be seen from the figure that the addition of active filter has a significant effect on eliminating low-order harmonics, but increases the high-order harmonic components, which is consistent with the simulation results.

6 Conclusion

This paper aims at the hybrid filter system of passive-active filter, and adopts the hysteresis loop instantaneous value comparison method to obtain the PWM signal to control the on and off of the switch device of the active filter inverter. This paper analyzes the working principle of the DC active filter and designs the corresponding control circuit. The simulation experiment results show that the DC active filter using the hysteresis loop instantaneous value comparison control method has a fast dynamic response speed, good tracking effect, and obvious compensation effect for low-order harmonics, but it increases the component of high-order harmonics. This control method

Study on the hysteresis comparison control method of DC active filter for high voltage DC transmission

The biggest disadvantage of this method is that the switching frequency of the device is not fixed, and further research is needed in this regard.

Keywords:DC Reference address:Study on Active DC Filter for HVDC Transmission---Research on Hysteresis Comparison Control

Previous article:Current status and prospects of small and medium power inverters for photovoltaic systems
Next article:Analysis of Equivalent Inductance in AC Regulated Voltage Stabilized Power Supply

Recommended ReadingLatest update time:2024-11-16 19:33

Comparison of Regulated Charge Pumps and Inductive DC/DC Converters
A charge pump (also called an inductorless DC/DC converter) is a special type of switching DC/DC converter that uses capacitors as energy storage elements. Compared to inductive switching DC/DC converters that use inductors as energy storage elements, charge pump converters have unique characteristics that make them v
[Power Management]
Comparison of Regulated Charge Pumps and Inductive DC/DC Converters
WWDC22 holds offline event lottery selection and registration has begun
     News on the morning of May 10th, developers can now participate in the offline activities of the 2022 Apple Worldwide Developers Conference (WWDC22 for short) through a lottery, and registration is now available on the Apple developer website.   This year's WWDC conference will open on June 6th local time in th
[Mobile phone portable]
Accurately measure ADC driver circuit settling time
introduction Many modern data acquisition systems are composed of high-speed and high-precision ADCs. CMOS switched capacitor-based ADCs are often used in such designs due to their low cost and low power consumption. The ADC uses an unbuffered front end that is directly coupled to the sampling network. To effec
[Test Measurement]
Accurately measure ADC driver circuit settling time
Pre-stage DC isolation power supply and inverter power supply circuit
The main circuit of the power supply is shown in Figure 1. It is divided into two parts, the upper part is the voltage source part, and the lower part is the current source part. Each part adopts a two-stage structure. After the AC input is rectified and filtered, it is first converted by DC/DC and then output through
[Power Management]
Pre-stage DC isolation power supply and inverter power supply circuit
Step-Down DC/DC Controller with Differential Output Sensing—LTC3833
describe: The LTC®3833 is a synchronous step-down DC/DC switching regulator controller for high power applications. The device is designed to drive all N-channel power MOSFETs. The controlled on-time valley current mode architecture enables fast transient response and constant frequency switching in stea
[Power Management]
Step-Down DC/DC Controller with Differential Output Sensing—LTC3833
Design of low harmonic and high power factor AC/DC switching power converter
1 Problem Statement With the development of production and the advancement of technology, especially the widespread application of various power electronic loads with rectifier inlets, that is, the emergence of a large number of nonlinear time-varying loads and equipment, a large number of harmonics are generated in
[Power Management]
Design of low harmonic and high power factor AC/DC switching power converter
Research on dual-output dual-closed-loop current-controlled DC/DC converter
introduction At present, multi-output power supplies generally adopt a closed-loop PWM control method for one output, while other auxiliary outputs adopt indirect voltage regulation. Since only the main output is closed-loop controlled, the change in duty cycle has a greater impact on the load of the auxili
[Power Management]
TYPE-C to DC adapter solution FS8024A supports 9V, 12V, 15V, 20V voltage output
With the popularity of USB-C PD adapters in recent years, PD adapters are becoming more and more common in consumers' hands. How can we make the previous power adapters work with PD adapters? In this way, if the previous power adapter is broken, there is no need to go through the trouble of looking for the same adap
[Embedded]
TYPE-C to DC adapter solution FS8024A supports 9V, 12V, 15V, 20V voltage output
Latest Power Management Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号