Due to the characteristics of its own structure and working characteristics, the power supply
device works in a complex and diverse electromagnetic environment and is easily affected by various interference sources, which may disrupt the transmission of signals or cause signal distortion, resulting in the system powered by the power supply device not being able to work properly. The use of grounding technology is an extremely important measure to ensure the reliable operation of the power supply device, and is also an important means to ensure the safe and stable operation of the power supply.
1. Classification of grounding of power supply devices
At present, there are many types of grounding of various power supply devices used in China, which can be summarized into the following categories?
(1) The working ground of the neutral point of the power supply to the power supply device: refers to the grounding of the neutral point potential of the stable power supply system; (2) The lightning protection grounding of the power supply device: refers to the protective grounding to prevent lightning
overvoltage in the thunderstorm season ; (3) The safety protection ground of the power supply device: refers to the grounding of the metal shell of the microelectronic device set to prevent contact voltage and step voltage from endangering the safety of people and equipment; (4) The DC system ground of the power supply device? Also known as the logic ground, working ground?, it provides a stable reference potential (generally zero point) for each part and link of the microelectronic device. This ground can be connected to the earth or just a common point. If the system ground is not connected to the earth, that is, the system ground is in a suspended working state, it is called a floating ground; (5) Shielded ground of the power supply device: It is set up to suppress various interference signals. There are many types of shielding, but they all need reliable grounding. Shielded ground is the grounding of the shielding network. Although the power supply devices in actual applications are produced by different companies, and the products of each company have different requirements for the type of grounding and the resistance of the grounding resistor , the system ground requirements of the power supply device are much stricter than the other grounding requirements, and there is a trend of increasing. In order to avoid mutual interference between the "grounds", the above-mentioned "grounds" should set up their own independent grounding networks. The grounding wire must be an insulated copper wire connected to a unified grounding point to form a common potential point. 2. Grounding principles of microelectronic devices In the grounding design of the automation control system, the principle of one point ground must be followed. Because the system is composed of multiple automation equipment, the entire system must be grounded at one place. However, the system grounding wire and grounding resistance cannot be zero, especially in high frequency or transient state; in addition, when a large current is injected into the earth from the grounding electrode, the grounding electrode and the ground potential near it will rise. If there are multiple ground points, there will be a potential difference between the grounding points, forming interference. Even the system ground wire in the same device should follow the principle of one point grounding, otherwise a grounding loop will be formed, and the grounding potential difference between the points will form interference and be introduced into other circuits . In order to study the relationship between the above-mentioned various grounding systems, analyze the many factors of the grounding network system and the effective ways and specific methods to reduce the grounding resistance, in recent years, "automation equipment grounding engineering" has been valued in the field of automation control as a new discipline, and has also laid a theoretical foundation for the research and practice of the grounding system of automation equipment. The grounding types and technical indicators of various power supply devices vary depending on the manufacturer and equipment function. Grounding plays a vital role in the safe and reliable operation of the power supply device. Different grounds have different processing technologies. The following introduces the grounding processing principles that the power supply device should follow. 1. Application of the principle of one-point grounding and multi-point grounding As far as electronic technology common sense is concerned, in low-frequency electronic circuits, the inductance between wiring and components does not seem to be serious. In order to avoid ground loops caused by ground wires, it is recommended to adopt the principle of one-point grounding. For high-frequency electronic circuits, the influence of inductance will be more prominent, because the increase in the impedance of the ground wire will lead to inductive coupling between the wires. Generally speaking, one-point grounding can be used when the frequency is less than 1MHz, while multi-point grounding should be used when it is higher than 10MHz. When the frequency is between 1MHz and 10MHz, if one-point grounding is used, the length of the ground wire should not exceed 1/20 of the wavelength, otherwise, multi-point grounding should be used. 2. Comparison between floating grounding and true grounding Floating grounding means that each grounding end of the system is not connected to the earth. This grounding method is simple, but it has high requirements for the insulation resistance with the ground, generally requiring more than 50MΩ, otherwise interference will occur due to insulation degradation. In addition, floating is prone to electrostatic interference. True grounding means that the grounding end of the system is directly connected to the earth. As long as the grounding is good, this method has a strong anti-interference ability. However, the grounding process is complicated, and once the grounding is poor, it will cause unnecessary interference. 3. The composition of grounding resistance Any power supply device produced by any manufacturer has strict requirements on the grounding resistance value of its product. When designing its grounding, the grounding resistance value of the power supply device should be used as the technical basis for designing its grounding. Therefore, the composition of grounding resistance is analyzed here so that corresponding measures can be taken in the main links in the design to reduce the grounding resistance value. (1) Grounding lead resistance refers to the resistance of the lead itself from the grounding body to the grounding busbar of the power supply device. Its resistance value is related to the geometric size and material of the lead; (2) The resistance of the grounding body (horizontal grounding body, vertical grounding body) itself, its resistance value is related to the material and geometric size of the grounding body; (3) The contact resistance between the surface of the grounding body and the soil, its resistance value is related to the nature, particles, water content of the soil, and the contact surface and tightness of the soil and the grounding body; (4) The soil resistance of the path through which the current spreads from the grounding body to a distance (20m), that is, the stray current resistance. The main factor determining the stray current resistance is the water content of the soil. 4. Main measures to reduce grounding resistance Although the grounding resistance is composed of four parts, the first two parts account for a small proportion of the grounding resistance, and the contact resistance and the scattered current resistance play a decisive role. Therefore, the work of reducing the grounding resistance should be carried out from these two parts, and the methods of reducing the contact resistance and the scattered current resistance should be discussed from the aspects of the optimal burial depth of the grounding body, the technology of unequal length grounding bodies and chemical resistance reducing agents. 1. The optimal burial depth of the vertical grounding body The optimal burial depth of the vertical grounding body refers to the burial depth that can make the scattered current resistance as small as possible and easy to reach. The factors of the three-dimensional grounding network should be taken into account when determining the optimal depth of the vertical grounding body. The so-called three-dimensional grounding network refers to a grounding network in which the burial depth of the grounding body and the equivalent radius of the grounding network are in the same order of magnitude (that is, the ratio of the burial depth to the equivalent radius is greater than 1/10). The burial depth should be as large as possible within the possible range, but it is not the case that the deeper the burial depth, the better. If the vertical grounding body is approximated as a hemispherical grounding body, its resistance is: R = ρ / 2πr = ρ / 2πL In the formula: ρ - soil resistivity; L - burial depth of the vertical grounding body. It can be seen from the formula that R is inversely proportional to L. In order to reduce R, the larger L, the better. However, the partial differential of the above formula: aR / aL = -ρ / 2πL2
It can be concluded that as L increases, the resistance reduction rate aR/aL decreases inversely with L2. When L is increased to a certain extent, it is basically saturated and the resistance reduction rate is close to zero. The optimal burial depth of the vertical grounding body is not fixed. It should be determined according to the equivalent radius of the grounding grid and the geological conditions in the area in the design. Generally, it is appropriate to take 1.5m~2.5m.
2. Unequal length grounding body technology
Since the spacing between the buried single grounding bodies in the grounding grid is generally only about twice the length of each single grounding body, when the current flows into each single grounding body, it is mutually restricted and prevents the current from dissipating, which is equivalent to increasing the dissipation resistance of each single grounding body. This phenomenon that affects the current dissipation becomes a shielding effect. As shown in the figure. Due to the shielding effect, the stray resistance of the grounding body is not equal to the parallel value of the stray resistance of each single grounding body. At this time, the stray resistance of the grounding body group is: Ra=RL/nη, where: RL—stray resistance of a single grounding body; n—the number of single grounding bodies in parallel in the grounding body group; η—the utilization coefficient of the grounding body, which is related to the shape and position of the grounding body. Theoretically, the distance 20m from the grounding body is the electrical "ground", that is, when the distance between the two grounding bodies is greater than 40m, the utilization coefficient η of the grounding body can be considered to be 1. However, in the arrangement of the grounding body of the grounding grid, it is difficult to make two single grounding bodies 40m apart. In order to solve the contradiction between design practice and theoretical analysis, the unequal length grounding body technology is adopted to achieve good results. The unequal length grounding body technology means that the lengths of each vertical grounding body are not equal. In the arrangement of the grounding body, the vertical grounding bodies are arranged as two long and one short or one long and two short, so as to minimize the shielding effect between the grounding body groups. The technology of unequal length grounding body, from theory to practice, has solved the problem of shielding effect between multiple single grounding bodies, improved the utilization coefficient of each single grounding body, and reduced the scattered flow resistance of the grounding body group. 3. Application of chemical resistance reducing agent The resistance reducing mechanism of chemical resistance reducing agent is that it seeps from the grounding body to the outer soil in liquid state, and after solidification for several minutes, it plays the role of increasing the contact area of the scattered flow electrode. Because the resistance reducing agent itself is a good conductor, it is used between the grounding body and the soil. On the one hand, it can be in close contact with the metal grounding body, reduce the contact resistance between the grounding body and the soil, and form a sufficiently large current flow cross section; on the other hand, it can penetrate into the surrounding soil, reduce the resistivity of the soil, and form a variable low resistance area around the grounding body. Thereby significantly expanding the equivalent diameter and effective length of the grounding body, it has a significant effect on reducing the contact resistance and scattered flow resistance. For example, the service life of JZG-02 long-term anti-corrosion resistance reducing agent can reach more than 20 years. During its life cycle, its performance is stable and does not require maintenance. It can still have good electrolyte performance and water absorption, and maintain its good physical and chemical mechanism. 5. Conclusion Power supply The design of grounding of the device should be based on the technical requirements of the power supply device and the geographical and geological conditions of the area where it is located. Different measures should be taken to achieve the highest performance-price ratio and try to use new technologies and new materials for design. Because "grounding engineering" is a multidisciplinary marginal subject, it involves geology, electromagnetic field theory, electrical measurement, applied chemistry, drilling technology, construction technology and other disciplines. Therefore, it is still necessary to study it in future work and explore it continuously in practice to ensure the safe and reliable operation of the power supply device.
Reference address:Grounding system for power supply units
1. Classification of grounding of power supply devices
At present, there are many types of grounding of various power supply devices used in China, which can be summarized into the following categories?
(1) The working ground of the neutral point of the power supply to the power supply device: refers to the grounding of the neutral point potential of the stable power supply system; (2) The lightning protection grounding of the power supply device: refers to the protective grounding to prevent lightning
overvoltage in the thunderstorm season ; (3) The safety protection ground of the power supply device: refers to the grounding of the metal shell of the microelectronic device set to prevent contact voltage and step voltage from endangering the safety of people and equipment; (4) The DC system ground of the power supply device? Also known as the logic ground, working ground?, it provides a stable reference potential (generally zero point) for each part and link of the microelectronic device. This ground can be connected to the earth or just a common point. If the system ground is not connected to the earth, that is, the system ground is in a suspended working state, it is called a floating ground; (5) Shielded ground of the power supply device: It is set up to suppress various interference signals. There are many types of shielding, but they all need reliable grounding. Shielded ground is the grounding of the shielding network. Although the power supply devices in actual applications are produced by different companies, and the products of each company have different requirements for the type of grounding and the resistance of the grounding resistor , the system ground requirements of the power supply device are much stricter than the other grounding requirements, and there is a trend of increasing. In order to avoid mutual interference between the "grounds", the above-mentioned "grounds" should set up their own independent grounding networks. The grounding wire must be an insulated copper wire connected to a unified grounding point to form a common potential point. 2. Grounding principles of microelectronic devices In the grounding design of the automation control system, the principle of one point ground must be followed. Because the system is composed of multiple automation equipment, the entire system must be grounded at one place. However, the system grounding wire and grounding resistance cannot be zero, especially in high frequency or transient state; in addition, when a large current is injected into the earth from the grounding electrode, the grounding electrode and the ground potential near it will rise. If there are multiple ground points, there will be a potential difference between the grounding points, forming interference. Even the system ground wire in the same device should follow the principle of one point grounding, otherwise a grounding loop will be formed, and the grounding potential difference between the points will form interference and be introduced into other circuits . In order to study the relationship between the above-mentioned various grounding systems, analyze the many factors of the grounding network system and the effective ways and specific methods to reduce the grounding resistance, in recent years, "automation equipment grounding engineering" has been valued in the field of automation control as a new discipline, and has also laid a theoretical foundation for the research and practice of the grounding system of automation equipment. The grounding types and technical indicators of various power supply devices vary depending on the manufacturer and equipment function. Grounding plays a vital role in the safe and reliable operation of the power supply device. Different grounds have different processing technologies. The following introduces the grounding processing principles that the power supply device should follow. 1. Application of the principle of one-point grounding and multi-point grounding As far as electronic technology common sense is concerned, in low-frequency electronic circuits, the inductance between wiring and components does not seem to be serious. In order to avoid ground loops caused by ground wires, it is recommended to adopt the principle of one-point grounding. For high-frequency electronic circuits, the influence of inductance will be more prominent, because the increase in the impedance of the ground wire will lead to inductive coupling between the wires. Generally speaking, one-point grounding can be used when the frequency is less than 1MHz, while multi-point grounding should be used when it is higher than 10MHz. When the frequency is between 1MHz and 10MHz, if one-point grounding is used, the length of the ground wire should not exceed 1/20 of the wavelength, otherwise, multi-point grounding should be used. 2. Comparison between floating grounding and true grounding Floating grounding means that each grounding end of the system is not connected to the earth. This grounding method is simple, but it has high requirements for the insulation resistance with the ground, generally requiring more than 50MΩ, otherwise interference will occur due to insulation degradation. In addition, floating is prone to electrostatic interference. True grounding means that the grounding end of the system is directly connected to the earth. As long as the grounding is good, this method has a strong anti-interference ability. However, the grounding process is complicated, and once the grounding is poor, it will cause unnecessary interference. 3. The composition of grounding resistance Any power supply device produced by any manufacturer has strict requirements on the grounding resistance value of its product. When designing its grounding, the grounding resistance value of the power supply device should be used as the technical basis for designing its grounding. Therefore, the composition of grounding resistance is analyzed here so that corresponding measures can be taken in the main links in the design to reduce the grounding resistance value. (1) Grounding lead resistance refers to the resistance of the lead itself from the grounding body to the grounding busbar of the power supply device. Its resistance value is related to the geometric size and material of the lead; (2) The resistance of the grounding body (horizontal grounding body, vertical grounding body) itself, its resistance value is related to the material and geometric size of the grounding body; (3) The contact resistance between the surface of the grounding body and the soil, its resistance value is related to the nature, particles, water content of the soil, and the contact surface and tightness of the soil and the grounding body; (4) The soil resistance of the path through which the current spreads from the grounding body to a distance (20m), that is, the stray current resistance. The main factor determining the stray current resistance is the water content of the soil. 4. Main measures to reduce grounding resistance Although the grounding resistance is composed of four parts, the first two parts account for a small proportion of the grounding resistance, and the contact resistance and the scattered current resistance play a decisive role. Therefore, the work of reducing the grounding resistance should be carried out from these two parts, and the methods of reducing the contact resistance and the scattered current resistance should be discussed from the aspects of the optimal burial depth of the grounding body, the technology of unequal length grounding bodies and chemical resistance reducing agents. 1. The optimal burial depth of the vertical grounding body The optimal burial depth of the vertical grounding body refers to the burial depth that can make the scattered current resistance as small as possible and easy to reach. The factors of the three-dimensional grounding network should be taken into account when determining the optimal depth of the vertical grounding body. The so-called three-dimensional grounding network refers to a grounding network in which the burial depth of the grounding body and the equivalent radius of the grounding network are in the same order of magnitude (that is, the ratio of the burial depth to the equivalent radius is greater than 1/10). The burial depth should be as large as possible within the possible range, but it is not the case that the deeper the burial depth, the better. If the vertical grounding body is approximated as a hemispherical grounding body, its resistance is: R = ρ / 2πr = ρ / 2πL In the formula: ρ - soil resistivity; L - burial depth of the vertical grounding body. It can be seen from the formula that R is inversely proportional to L. In order to reduce R, the larger L, the better. However, the partial differential of the above formula: aR / aL = -ρ / 2πL2
It can be concluded that as L increases, the resistance reduction rate aR/aL decreases inversely with L2. When L is increased to a certain extent, it is basically saturated and the resistance reduction rate is close to zero. The optimal burial depth of the vertical grounding body is not fixed. It should be determined according to the equivalent radius of the grounding grid and the geological conditions in the area in the design. Generally, it is appropriate to take 1.5m~2.5m.
2. Unequal length grounding body technology
Since the spacing between the buried single grounding bodies in the grounding grid is generally only about twice the length of each single grounding body, when the current flows into each single grounding body, it is mutually restricted and prevents the current from dissipating, which is equivalent to increasing the dissipation resistance of each single grounding body. This phenomenon that affects the current dissipation becomes a shielding effect. As shown in the figure. Due to the shielding effect, the stray resistance of the grounding body is not equal to the parallel value of the stray resistance of each single grounding body. At this time, the stray resistance of the grounding body group is: Ra=RL/nη, where: RL—stray resistance of a single grounding body; n—the number of single grounding bodies in parallel in the grounding body group; η—the utilization coefficient of the grounding body, which is related to the shape and position of the grounding body. Theoretically, the distance 20m from the grounding body is the electrical "ground", that is, when the distance between the two grounding bodies is greater than 40m, the utilization coefficient η of the grounding body can be considered to be 1. However, in the arrangement of the grounding body of the grounding grid, it is difficult to make two single grounding bodies 40m apart. In order to solve the contradiction between design practice and theoretical analysis, the unequal length grounding body technology is adopted to achieve good results. The unequal length grounding body technology means that the lengths of each vertical grounding body are not equal. In the arrangement of the grounding body, the vertical grounding bodies are arranged as two long and one short or one long and two short, so as to minimize the shielding effect between the grounding body groups. The technology of unequal length grounding body, from theory to practice, has solved the problem of shielding effect between multiple single grounding bodies, improved the utilization coefficient of each single grounding body, and reduced the scattered flow resistance of the grounding body group. 3. Application of chemical resistance reducing agent The resistance reducing mechanism of chemical resistance reducing agent is that it seeps from the grounding body to the outer soil in liquid state, and after solidification for several minutes, it plays the role of increasing the contact area of the scattered flow electrode. Because the resistance reducing agent itself is a good conductor, it is used between the grounding body and the soil. On the one hand, it can be in close contact with the metal grounding body, reduce the contact resistance between the grounding body and the soil, and form a sufficiently large current flow cross section; on the other hand, it can penetrate into the surrounding soil, reduce the resistivity of the soil, and form a variable low resistance area around the grounding body. Thereby significantly expanding the equivalent diameter and effective length of the grounding body, it has a significant effect on reducing the contact resistance and scattered flow resistance. For example, the service life of JZG-02 long-term anti-corrosion resistance reducing agent can reach more than 20 years. During its life cycle, its performance is stable and does not require maintenance. It can still have good electrolyte performance and water absorption, and maintain its good physical and chemical mechanism. 5. Conclusion Power supply The design of grounding of the device should be based on the technical requirements of the power supply device and the geographical and geological conditions of the area where it is located. Different measures should be taken to achieve the highest performance-price ratio and try to use new technologies and new materials for design. Because "grounding engineering" is a multidisciplinary marginal subject, it involves geology, electromagnetic field theory, electrical measurement, applied chemistry, drilling technology, construction technology and other disciplines. Therefore, it is still necessary to study it in future work and explore it continuously in practice to ensure the safe and reliable operation of the power supply device.
Previous article:Switching Power Supply Control Loop Design Principles
Next article:Research on Intelligent Network UPS Power Supply Monitoring Technology
Recommended Content
Latest Power Management Articles
- MathWorks and NXP Collaborate to Launch Model-Based Design Toolbox for Battery Management Systems
- STMicroelectronics' advanced galvanically isolated gate driver STGAP3S provides flexible protection for IGBTs and SiC MOSFETs
- New diaphragm-free solid-state lithium battery technology is launched: the distance between the positive and negative electrodes is less than 0.000001 meters
- [“Source” Observe the Autumn Series] Application and testing of the next generation of semiconductor gallium oxide device photodetectors
- 采用自主设计封装,绝缘电阻显著提高!ROHM开发出更高电压xEV系统的SiC肖特基势垒二极管
- Will GaN replace SiC? PI's disruptive 1700V InnoMux2 is here to demonstrate
- From Isolation to the Third and a Half Generation: Understanding Naxinwei's Gate Driver IC in One Article
- The appeal of 48 V technology: importance, benefits and key factors in system-level applications
- Important breakthrough in recycling of used lithium-ion batteries
MoreSelected Circuit Diagrams
MorePopular Articles
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
MoreDaily News
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
Guess you like
- TI full range of component libraries (component library, package library, 3D library) collection
- [NXP Rapid IoT Review] Week 2: Get familiar with the online GUI Rapid IoT Studio
- National College Student Electronic Design Competition Quadcopter UAV Data Album
- Today at 10:00 AM, there will be a prize live broadcast: [ADI will meet you for TOF (Time Of Flight) technology introduction and product applications]
- Second-order filter, how to ensure that the data does not overflow when performing fixed-point operations?
- GD32E231 DIY Competition (7) - Human infrared sensor module and music IC driver completed
- About the problem of data transmission between AD7768 evaluation board and sdp-h1 board
- Free e-book download | "ADI System Solutions Selection Volume 6"
- Hello everyone
- CC2541 Mini Development Kit and CC2540 by Original You