DRB Series
www.uk.tdk-lambda.com/drb
15W to 100W Single Output
DIN Rail Mount Power Supplies
Features
• Compact Footprint
• Efficiency up 91%
• ErP Compliant Design
Benefits
• Saves Space on Rail & Cabinet Cost
• Cooler Applications - Improved Thermal Performance
• Better “Environmental Footprint”
Specification
Model
ITEMS
AC input voltage range
Input frequency
Inrush cold (typ)
Power factor (typ) (110/230VAC)
Input current (typ)
Output voltage
Output current
Line regulation
Load regulation
Ripple & noise (max) (typ)
Over current protection
Over voltage protection (1)
Hold up time (230VAC)
Efficiency (typ) (230VAC)
Average efficiency (230VAC)
No load power
Parallel operation
Serial operation
LED indicators
Operating temperature (2, 3, 5)
Storage temperature
Operating humidity
Cooling
(4)
Withstand voltage
Isolation resistance
Vibration
Shock
Safety agency approvals
Emissions
Immunity
Weight (typ)
Size (W x H x D)
Case material
Warranty
VAC
Hz
A
A
V
A
mV
mV
mV
DRB15
DRB30
DRB50
DRB100
ms
%
%
W
°C
°C
MΩ
g
mm
yrs
85-264 (withstand 300VAC for 5 sec)
47-63
35A
40A
50A
40A
0.55/0.42
0.56/0.46
0.6/0.5
0.98/0.93
0.27/0.17
0.55/0.33
0.9/0.55
1.2/0.6
24
12 / 24
5 / 12 / 24 / 48
24
0.63
2.5 / 1.25
6 /3.4 / 2.1 / 1.05
4.2
240
120 / 240
50 / 150 / 240 / 480
240
240
120 / 240
50 / 150 / 240 / 480
240
20
40 / 30
30 / 20 / 30 / 40
30
Hiccup with auto recovery
5V: 115%-135%, 12V: 133%-156%, 24V: 125%-140%, 48V: 112%-142% (latch mode)
20 @100VAC, full load, 25°C
90
88 / 90
80 / 90 / 90 / 91
91
88
87/89
5V:n/a, 12V:88, 24V:87, 48V:87
87
<0.3
<0.3
<0.3
<0.5
Not available
Possible
DC OK signal - green
-20°C to +70°C ( see derating curves)
-40°C to +85°C
5-95% RH (non condensing)
Convection
Input - Output : 3.0kVAC (20mA), Input - FG : 1.5kVAC (20mA)
Output - FG : 500VAC (100mA) 1 min.
Input-FG, Input-Output & Output-FG: More than 100MΩ (500VDC) at 25°C and 70%RH
Non-operating,10-55Hz(sweep for 1 min.):19.6 m/s
2
(2G) Constant, X,Y,Z each 1hr
294m/s2(30G) 11ms half sine
UL60950-1, CSA22.2 No.60950-1 (2nd edition), EN60950-1, UL508
EN55022, CISPR22 class B
EN61000-4-2,-3,-4,-5,-6,-8,-11
85
95
175
300
18 x 75 x 90
21x75x90
30x75x90
45x75x100
Flame Retardant Polycarbonate (UL94 V-0)
3
2
4
Refer to output derating curves
See installation instructions for mounting orientation
Notes:
1
Output will shutdown, manual reset required (power off then on)
3
For UL508 operating temperature refers to surrounding air temperature
5
Low temperature start up: -40°C typical
DRB Series
1
Model Selector
Model
DRB15-24-1
DRB30-12-1
DRB30-24-1
DRB50-5-1
DRB50-12-1
DRB50-24-1
DRB50-48-1
DRB100-24-1
Output
Voltage
24
12
24
5
12
24
48
24
Output Adjust Max Output
Range (V)
Current (A)
24-28
12-15
24-28
5-5.5
12-15
24-28
48-52.8
24-28
0.63
2.5
1.25
6
4.2
2.1
1.05
4.2
Max Output
Power (W)
15.12
30
30
30
50.4
50.4
50.4
100.8
Efficiency at
115/230 VAC (%)
87/90
86/88
88/90
79/80
88/90
88/90
90/91
90/91
Terminal Explanation Example
Connection
Pin
1
2
3
4
5
6
7
+V: + Output terminal
-V: - Output terminal
V. adj: Output voltage adjust trimmer. The output voltage rises when the trimmer is turned clockwise
L: AC Input terminal live line (fuse in line)
N: AC Input terminal neutral line
E: Protective earth connect to safety ground of apparatus or equipment
DC OK: Green LED lights when output voltage on
Output Derating DRB15 Series
Output Derating DRB30 Series
Ts (Surrounding air temperature)
°C
Ts (Surrounding air temperature)
°C
Output Derating DRB50 Series
Output Derating DRB100 Series
Ts (Surrounding air temperature)
°C
Ts (Surrounding air temperature)
°C
2
DRB Series
TDK-Lambda France SAS
ZAC des Delaches
CS 41077
9 rue Thuillere
91978 Villebon Courtaboeuf
France
Tel: +33 1 60 12 71 65
Fax: +33 1 60 12 71 66
france@fr.tdk-lambda.com
www.fr.tdk-lambda.com
TDK-Lambda UK Ltd.
Kingsley Avenue
Ilfracombe
Devon EX34 8ES
United Kingdom
Tel: +44 (0) 12 71 85 66 66
Fax: +44 (0) 12 71 86 48 94
powersolutions@uk.tdk-lambda.com
www.uk.tdk-lambda.com
Italy Sales Office
Via dei Lavoratori 128/130
20092 Cinisello Balsamo (MI)
Italy
Tel: +39 02 61 29 38 63
Fax: +39 02 61 29 09 00
info.italia@it.tdk-lambda.com
www.it.tdk-lambda.com
TDK-Lambda Ltd.
Kibbutz
Givat Hashlosha 48800
Israel
Tel: +9 723 902 4333
Fax: +9 723 902 4777
info@tdk-lambda.co.il
www.tdk-lambda.co.il
Netherlands
info@tdk-lambda.nl
www.tdk-lambda.nl
Russia
Technical Support:
St Petersburg
Tel: +7 (812) 6580463
Sales:
Moscow
info@tdk-lambda.ru
www.tdk-lambda.ru
TDK-Lambda Germany GmbH
Karl-Bold-Strasse 40
77855 Achern
Germany
Tel: +49 7841 666 0
Fax: +49 7841 5000
info.germany@de.tdk-lambda.com
www.de.tdk-lambda.com
Local Distribution
Austria Sales Office
Aredstrasse 22
2544 Leobersdorf
Austria
Tel: +43 2256 655 84
Fax: +43 2256 645 12
info.germany@de.tdk-lambda.com
www.de.tdk-lambda.com
Scandinavia Sales Office
Valdemarsgade 7
4100 Ringsted
Denmark
Tel: +45 24 63 95 65
Fax: +45 69 80 44 99
info@de.tdk-lambda.com
www.emea.tdk-lambda.com
RSG Electronic Components GmbH
Sprendlinger Landstr. 115
D-63069 Offenbach / Germany
Tel. +49.69.984047-0
Fax +49.69.984047-77
info@rsg-electronic.de
www.rsg-electronic.de
Änderungen vorbehalten / subject to change without notice.
Switzerland Sales Office
Bahnhofstrasse 50
8305 Dietlikon
Switzerland
Tel: +41 44 850 53 53
Fax: +41 44 850 53 50
info@de.tdk-lambda.com
www.de.tdk-lambda.com
DRB Series Dec13 v3
www.emea.tdk-lambda.com
DRB Series
5