1/4" x 1-1/4" Fuses
MDA Series, Time Delay, Ceramic Tube
Description
• Time Delay, ceramic tube
• Optional leaded version available
• 1/4 x 1-1/4 (6.3mm x 32mm) physical size
• Ceramic tube, nickel-plated brass endcap construction
• UL Listed product meets standard 248-14
ELECTRICAL CHARACTERISTICS
Rated Current
Amp Rating
Opening Time
100%
None
1/4 - 30A
135%
60 Minutes Max.
200%
120 Seconds Max.
Dimensions
(
mm
⁄
in
)
Drawing Not to Scale
Approvals
• UL Listed Card: MDA 2/10 - 20A (Guide JDYX,
File E19180)
• UL Recognized Card: MDA 25 - 30A (Guide JDYX2,
File E19180)
• CSA Certification Card: MDA 2/10 - 15
(Class No. 1422-01)
Environmental Data
• Shock: 1/100A and 8/10A – MIL-STD-202,
Method 213, Test Condition I;
1A thru 30A – MIL-STD-202, Method 207,
(HI Shock)
• Vibration: 1/100A and 8/10A – MIL-STD-202,
Method 201; 1/4A thru 30A – MIL-STD-202,
Method 204, Test Condition C (Except 5g, 500HZ)
Ordering
• Specify product code, option code and packaging code
SPECIFICATIONS
Product
Code
MDA-1/4
MDA-1/2
MDA-3/4
MDA-1
MDA-1-1/2
MDA-2
MDA-2-1/2
MDA-3
MDA-4
MDA-5
MDA-6
MDA-7
MDA-8
MDA-10
MDA-15
MDA-20
MDA-25
MDA-30
*
**
†
‡
Voltage
Rating
AC
DC
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
-
250V
125V
250V
125V
250V
125V
AC Interrupting
Rating*
250V
125V
35A
10000A
35A
10000A
35A
10000A
35A
10000A
100A
10000A
100A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
200A
10000A
750A
10000A
1500A
10000A
1500A
10000A
1500A
10000A
DC Interrupting
Rating
125V
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
10000A
10000A
10000A
Typical DC Cold
Resistance**
(ohms)
9.325
1.925
0.8555
0.560
0.2585
0.1645
0.06685
0.0507
0.0346
0.02355
0.01850
0.01475
0.01230
0.00858
0.00543
0.00405
0.00309
0.00243
Typical
Melting I
2
t†
AC
0.68
2.3
7.8
11.1
25.0
64.0
28.9
40.9
134.0
345.9
534.3
580.3
944.0
1491.3
206.2
439.5
667.9
997.0
Typical
Voltage
Drop‡
4.00
1.42
1.31
1.03
0.691
0.623
0.213
0.182
0.162
0.145
0.141
0.137
0.134
N/A
0.107
0.095
0.105
0.110
Interrupting Ratings (Measured at 70% - 80% power factor on AC. The interrupting ratings for 25Amp, 30Amp were measured at 90% - 100% power factor on AC)
DC Cold Resistance (Measured at
≤10%
of rated current)
Typical Melting I
2
t (A
2
Sec) (I
2
t was measured at listed interrupting rating and rated voltage)
Typical Voltage Drop (Voltage drop was measured at 25°C ambient temperature at rated current)
1/4" x 1-1/4" Fuses
MDA Series, Time Delay, Ceramic Tube
TIME CURRENT CURVE
CURRENT IN AMPERES
3-2/10
4
5
6-1/4
1/4
1/2
TIME IN SECONDS
10
12
15
20
25
30
1
2
TIME IN SECONDS
CURRENT IN AMPERES
OPTION CODE
Option Code
B
V
Description
Board Washable - Hermetically sealed to withstand aqueous cleaning
Axial leads - brass overcaps with copper and nickel flash, plated in tin lead
PACKAGING CODE
Packaging Code
BK
BK1
BK8
Description
100 pieces of fuses packed into a cardboard carton with flaps folded
1,000 pieces of fuses packed into a cardboard carton with flaps folded
8,000 pieces of fuses packed into a cardboard carton with flaps folded
OC-2545 10/01
© Cooper Electronic
Technologies 2001
Visit us on the Web at www.cooperET.com
3601 Quantum Boulevard Boynton Beach, Florida 33426-8638
Tel: +1-561-752-5000 Toll Free: +1-888-414-2645 Fax: +1-561-742-1178
This bulletin is intended to present product design solutions and technical information that will help the end user with design applications. Cooper
Electronic Technologies reserves the right, without notice, to change design or construction of any products and to discontinue or limit distribution of
any products. Cooper Electronic Technologies also reserves the right to change or update, without notice, any technical information contained in this
bulletin. Once a product has been selected, it should be tested by the user in all possible applications.