Three-phase three-wire active energy meter direct connection circuit
Source: InternetPublisher:柯南道尔 Keywords: Wiring energy meter three-phase three-wire Updated: 2020/03/20
Requirements for direct wiring of three-phase active energy meters.
1) Before wiring, check the model, specification and load rated parameters of the electric energy meter. The rated voltage of the electric energy meter should be consistent with the power supply voltage. The rated current should
not be less than the load current, and the appearance of the meter should be intact.
2) The wires connected to the electric energy meter must use copper-core insulated wires. The cross-sectional area of the wires meets the mechanical strength
requirements . The cross-sectional area of the voltage return wires is not less than 1. 5mmZ. For the current loop wires The cross-sectional area should not be less than 2. 5mmz.
The conductors with a cross-sectional area of 6mmz and below should use single-strand wires. There should be no joints in the conductors.
3) The polarity must be connected correctly. The first end of the voltage coil should be connected to the phase line together with the first end of the current wire. The neutral line of the blue phase four-wire must go in and out of the energy
meter.
4) Wiring must be in positive phase sequence, and the switch and fuse
should be connected to the load side of the energy meter.
Wiring circuit ; three-phase three-wire active energy meter plug-
in wiring is shown in the figure. This figure shows the
direct connection method of DS type 5-10A three-phase three-wire active energy meter . For three-phase three-wire
active energy meters
above 10A , the internal wiring is different, but
the external wiring is basically the same.
- Analysis of the working principle of switching regulator
- How to improve the accuracy and precision of power supplies through low frequency thermal noise?
- INA155/INA156 is used to form a single-supply high-side current monitor for detecting load current
- Op amp power supply decoupling bypass measures
- Detailed explanation of 5v charger circuit diagram
- Dual forward converter schematic diagram
- Voltage-current converter constructed with XTR110
- Design of electric vehicle charger
- Production of backup power supply for cordless phone
- Reconstruction of the tube pre-stage by using low voltage difference power supply
- Temporary power lines
- Single-phase active energy meter wiring with current transformer
- Tree-trunk main wiring system diagram a
- Connection between PLC and frequency converterb
- Lightning protection wiring of oil switch on pole a
- Lightning protection wiring for direct-match generators of 300kW and below a
- Wiring c of leakage protectors with different action modes
- Wiring c when the leakage protector supplies power to single-phase loads in the TN system
- Wiring a when the leakage protector in the TN system supplies a three-phase balanced load
- DS8 type 380V, 5A current mutual induction three-phase three-wire electricity meter wiring