Three-phase three-wire active energy meter direct connection circuit
Source: InternetPublisher:柯南道尔 Keywords: Wiring energy meter three-phase three-wire Updated: 2020/03/20
Requirements for direct wiring of three-phase active energy meters.
1) Before wiring, check the model, specification and load rated parameters of the electric energy meter. The rated voltage of the electric energy meter should be consistent with the power supply voltage. The rated current should
not be less than the load current, and the appearance of the meter should be intact.
2) The wires connected to the electric energy meter must use copper-core insulated wires. The cross-sectional area of the wires meets the mechanical strength
requirements . The cross-sectional area of the voltage return wires is not less than 1. 5mmZ. For the current loop wires The cross-sectional area should not be less than 2. 5mmz.
The conductors with a cross-sectional area of 6mmz and below should use single-strand wires. There should be no joints in the conductors.
3) The polarity must be connected correctly. The first end of the voltage coil should be connected to the phase line together with the first end of the current wire. The neutral line of the blue phase four-wire must go in and out of the energy
meter.
4) Wiring must be in positive phase sequence, and the switch and fuse
should be connected to the load side of the energy meter.
Wiring circuit ; three-phase three-wire active energy meter plug-
in wiring is shown in the figure. This figure shows the
direct connection method of DS type 5-10A three-phase three-wire active energy meter . For three-phase three-wire
active energy meters
above 10A , the internal wiring is different, but
the external wiring is basically the same.
- Driving circuit of switching power supply field effect tube
- Step-down power supply for driving relays
- Constant current LED lamp driver circuit with soft start and anti-shock
- Low cost and high performance LED constant current power supply
- Adjustable voltage regulated power supply circuit
- A low-cost, high-reliability battery charger for electric vehicles
- Battery powered switching circuit diagram
- MAX762 Solar Sealed Lead-Acid Battery Charger
- Simple battery charging protection circuit
- RF2131 optimal efficiency power amplifier circuit when powered by 4.8V power supply
- Radial wiring power supply circuit b
- Lightning protection wiring of 3150 to 6300kV·A substation
- Wiring of lightning protection belts, voltage equalizing rings, etc. in high-rise buildings
- Wiring c of leakage protectors with different action modes
- Wiring b when leakage protector supplies power and lighting load in TN system
- Wiring a when the leakage protector supplies power and lighting loads in the TN system
- Wiring b when leakage protector in TN system supplies three-phase balanced load
- Wiring a when the leakage protector supplies power to unbalanced loads in the TT system
- The three-phase three-wire active energy meter is connected to the circuit through the current transformer (2)
- DX8 type 100V, 5A universal mutual inductance three-phase three-wire 60 degree reactive power meter wiring