Home > Control Circuits >Motor Control > XJ01 type automatic starting compensation control circuit

XJ01 type automatic starting compensation control circuit

Source: InternetPublisher:同住地球村 Keywords: Control circuit compensation control BSP coil Updated: 2021/03/20

39.XJ01 automatic starting compensation<strong>control circuit</strong>.gif


In situations where automatic control of starting is required in industries, mining, enterprises, and township factories , XJ01 type automatic starting
compensator is often used, which is mainly composed of autotransformer, AC contactor
, intermediate relay, time relay and control button
.
    The xlol type automatic starting compensator circuit
is shown in Figure 4-39. Turn on the power, the light EL1 lights up, press the start
button SB1, the KM1 coil is energized, the KM1 main contact is closed
, and the motor is decompressed and started. KM1 is closed and self-locking, and the light
EL2 is on. The moving breaking contact of KM1 is disconnected, the light EL1 is off,
KT is energized, and its moving closing contact is delayed to close. When the KA coil
is energized, the KA moving contact is disconnected, KM1 is powered off, and
the KM1 moving contact is disconnected. At the same time, the KA moving contact is closed
. The KMZ coil is energized, the main contact of KM2 is closed, the motor
runs at full voltage, the moving and closing contacts of KM2 are closed, and the light
EL3 is on.


EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号