Home > Control Circuits >Motor Control > Energy consumption braking circuit with inching brake

Energy consumption braking circuit with inching brake

Source: InternetPublisher:兰博 Keywords: Energy consumption braking braking circuit contacts BSP Updated: 2021/06/30

143.<strong>Energy consumption braking</strong> circuit with inching brake.gif

The circuit is shown in Figure 3-143. This circuit not only enables the motor to have a braking effect during normal shutdown, but
also has a better braking effect during inching.
    In the figure, SBz is the start button, SBz is the stop button, and SB3 is the inching button. The normal stopping braking time
is determined by the time relay KTi (3-4s, adjustable). During inching control, if the interval between two inching movements is less than the setting
time of KTz (2~3s, adjustable), its delayed opening normally closed contact will not open. At this time, pressing SB3 is inching. Release Opening SB3 is
braking; if the interval between two inching operations is greater than the setting time of KT2, or the inching positioning is completed, the KTz normally closed contact
will be disconnected at regular intervals, and the relays KAz and KA3 will lose power and release one after another, and the KA3 normally open contact will Disconnected, contactor KM2 is de-energized and released, and
the braking process ends.


EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号