Detailed explanation of the detailed steps of PLC and inverter communication

Publisher:upsilon30Latest update time:2023-04-24 Source: elecfansKeywords:PLC Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

1. Find an S7-1200PLC with RS485 communication module and a V20 inverter.

2. Connect the RS485 module to the V20 inverter. The wiring method is to connect the red wire to P+ and the green wire to N-.

wKgaomQGlLmASGqIAAIqY9z_Dfk115.png

picture

3. Set the inverter parameters of V20.

wKgaomQGlLmAHK6TAAEn0L14jSo996.jpg

picture

4. Create a TIA Portal project and upload the S7-1200PLC hardware configuration.

wKgZomQGlLmAauvOAAK_bT6jHU8067.png

picture

wKgZomQGlLmAV7dgAANpqPa24G0637.png

picture

wKgaomQGlLmALNMOAACc9WReVws513.png

picture

wKgaomQGlLmAGli_AAC9Y6Kq_U4795.png

picture

5. Set the parameters of the RS485 module. The communication parameters of the module must be consistent with the communication parameters set in V20. I set them to 9600, 8, even.

wKgZomQGlLmAIRo7AAIkIRGq9dA472.png

picture

6. Add Modbus communication instructions.

wKgaomQGlLmADj2AAANyEsemHmc917.png

picture

7. Change the mode parameter in the initialization instruction background DB to 4.

wKgZomQGlLmAHCvmAAMwo2Ios2c278.png

picture

8. Program test, motor Normal start and stop, where the modbus address 40100 is the command source, 047E is stop, 047F is forward, 0C7F is reverse, the address 40100 is the frequency source, 16#0-16#4000 corresponds to 0Hz-50Hz.

9. You can check whether the communication is successful by observing the communication indicator light of the module. If TX and RX flash alternately, the communication is successful.

1. Find an S7-1200PLC with RS485 communication module and a V20 inverter.

2. Connect the RS485 module to the V20 inverter. The wiring method is to connect the red wire to P+ and the green wire to N-.

wKgaomQGlLmASGqIAAIqY9z_Dfk115.png

picture

3. Set the inverter parameters of V20.

wKgaomQGlLmAHK6TAAEn0L14jSo996.jpg

picture

4. Create a TIA Portal project and upload the hardware configuration of the S7-1200PLC.

wKgZomQGlLmAauvOAAK_bT6jHU8067.png

picture

wKgZomQGlLmAV7dgAANpqPa24G0637.png

picture

wKgaomQGlLmALNMOAACc9WReVws513.png

picture

wKgaomQGlLmAGli_AAC9Y6Kq_U4795.png

picture

5. Set the parameters of the RS485 module. The communication parameters of the module must be consistent with the communication parameters set in V20. I set them to 9600, 8, even.

wKgZomQGlLmAIRo7AAIkIRGq9dA472.png

picture

6. Add Modbus communication instructions.

wKgaomQGlLmADj2AAANyEsemHmc917.png

picture

7. Change the mode parameter in the initialization instruction background DB to 4.

wKgZomQGlLmAHCvmAAMwo2Ios2c278.png

picture

8. Program test, the motor starts and stops normally, where the modbus address 40100 is the command source, 047E is stop, 047F is forward, 0C7F is reverse, the address 40100 is the frequency source, 16#0-16#4000 corresponds to 0Hz-50Hz.

9. You can check whether the communication is successful by observing the communication indicator light of the module. If TX and RX flash alternately, the communication is successful.


Keywords:PLC Reference address:Detailed explanation of the detailed steps of PLC and inverter communication

Previous article:Operating Principle of Three-Phase Induction Motor
Next article:What is the servo drive? The role and function of the servo drive

Recommended ReadingLatest update time:2024-11-16 12:49

Application of Profibus-DP, Siemens touch screen and PLC devices in bucket wheel stacker and reclaimer
1. Introduction Bucket wheel stacker reclaimer is a large bulk material handling machine, widely used in ports, mines, steel mills, power plants and other bulk materials such as ore, coal, sand and gravel in the storage yard stacking and extraction operations, its work continuity is strong, the operation is fre
[Embedded]
Application of Profibus-DP, Siemens touch screen and PLC devices in bucket wheel stacker and reclaimer
Can understand electrical diagrams but not PLC ladder diagrams?
Many people say that PLC is difficult, and even if you have basic knowledge of electrical engineering, it is still difficult to learn! But is it really so? How can you quickly learn PLC if you have basic knowledge of electrical engineering? Today, let's take a look at how to quickly convert electrical diagrams into
[Embedded]
Can understand electrical diagrams but not PLC ladder diagrams?
The difference between electrical control and PLC
Electrical Control and PLC What is the difference between PLC control system and electrical control? There are many similarities between these two control systems, which makes many beginners and even experienced electricians confused! But in fact, there are also big differences between the two. Let's take a loo
[Embedded]
The difference between electrical control and PLC
Maxim Integrated Launches Ultra-Low-Power, High-Precision Analog Output Solution
    Maxim Integrated provides designers with a micro-PLC analog output system for Industry 4.0 designs.     Beijing, China, October 9, 2014. Maxim Integrated Products, Inc. (NASDAQ: MXIM) has introduced the MAXREFDES60#, a 16-bit analog output system that helps designers implement Industry 4.0 factory automation des
[Industrial Control]
PLC's conversion process of analog signals
Analog signals are the most basic input form of process signals (pressure, temperature, flow, etc.) in automated process control systems. The process signals in the system are converted into unified voltage and current signals through transmitters, and these signals are transmitted to the controller (PLC) in real ti
[Embedded]
PLC's conversion process of analog signals
Introduce the implementation process of wireless Profinet protocol communication between Kingview and multiple PLCs
Wireless Ethernet communication Between KingView and S7-1200 -Profine protocol- In the actual system, there are multiple PLCs distributed in the workshop, which need to be centrally controlled by the host computer software. Usually, the distance between all devices ranges from tens of meters to hundre
[Embedded]
Introduce the implementation process of wireless Profinet protocol communication between Kingview and multiple PLCs
200ppi to Ethernet without programming to achieve 200 224XP and 200SMART PLC data exchange
This example takes S7-200 (CPU224XP) and SMART200 as examples to introduce how to exchange data between 200 and smartPLC through Xingda Easy Control PPI-ETH-XD1.0PLUS PLC Ethernet. The DB9 male port (X1) of Xingda Easy Control PPI-ETH-XD1.0PLUS is connected to the PPI port of S7-200. The Ethernet po
[Embedded]
200ppi to Ethernet without programming to achieve 200 224XP and 200SMART PLC data exchange
Expression of PLC instructions Types of PLC instruction systems
PLC instructions are the instruction set of a programmable logic controller (PLC), also known as PLC programming instructions. These instructions are the basic building blocks for writing and controlling PLC programs. They include input and output instructions, logic instructions, data processing instructions, timer
[Embedded]
Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号