Share an example of constant pressure water supply controlled by frequency converter and touch screen

Publisher:bin0990Latest update time:2023-02-01 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

In water supply equipment, when the water tank supplies water to the outside, the water pressure may be unstable and fluctuate. In response to this situation, we can perform constant liquid level control on the water tank and build a constant pressure water supply control system. Here is a common example:

When the water level of the water tank is set to 150mm, no matter how much water is discharged from the water tank, the water level of the water tank can be kept at 150mm by adjusting the water inlet. Since the liquid level is proportional to the pressure at the bottom of the water tank, a remote pressure gauge can be used to detect the pressure at the bottom of the water tank to determine the liquid level, and the PID algorithm can be used to automatically adjust the water level. The water level analog signal detected by the remote pressure gauge is sent to the inverter, which performs PID calculation on the deviation between the given value and the actual detection value, and adjusts the speed of the water pump motor through the calculation output result, thereby adjusting the water inlet.


In the whole control system, the core components are the inverter and touch screen, the selection is as follows:

1. Inverter selection

The Eurofins EV510A series inverter has a common power range of 5.5~30kw and is used to receive analog input signals from remote pressure gauges and adjust the speed of the water pump motor, thereby adjusting the water intake.


2. Touch screen

Kunlun Tongtai TPC 7022

System circuit diagram and related parameters:

1. Circuit diagram

The Eurofins EV510A series inverter has a common power range of 5.5~30kw and is used to receive analog input signals from remote pressure gauges and adjust the speed of the water pump motor, thereby adjusting the water intake.

f10f5d68-94ce-11ed-bfe3-dac502259ad0.png

2. Inverter parameter setting

EV510A inverter parameter setting

Function code name Settings
P0-02 Run command channel 2
PP-05 Inverter function macro 1
P8-47 Sleep mode selection 0

Touch screen write address

Parameter name Write address
Set pressure FA01H
Feedback Pressure 1011H
Start and stop 2000H

Touch screen monitoring

f129e8ea-94ce-11ed-bfe3-dac502259ad0.png


Reference address:Share an example of constant pressure water supply controlled by frequency converter and touch screen

Previous article:A brief analysis of S7-1500 control servo drive
Next article:Research and analysis of the machine vision industry and four typical application scenarios

Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号