Below we list in detail the factors that affect UPS operation:
Battery
According to data analysis, among the UPS returned for repair, the proportion of UPS not working properly due to battery failure is about one-third. Therefore, we should pay special attention to whether the battery is faulty.
There are several types of faults caused by battery problems:
1. The UPS cannot start.
Because Smart-UPS is started by DC, it cannot start when there is no battery connected, the battery is low or there is a problem with the battery. There are several similar situations below:
The first situation: The newly installed UPS cannot start.
If the UPS is a SUA1000ICH model, please check whether the battery connection plug on the rear panel of the UPS is connected. If it is a rack-mounted UPS such as SU3000RMI3U, please open the front panel to check whether the battery is connected.
Since new batteries will self-discharge during storage, the UPS cannot start when the battery is in a low-power state. At this time, you need to connect the UPS to the battery and the mains, and press the Test button on the front panel of the UPS. Although the UPS panel display light will not light up, the UPS will charge the battery. After charging for a period of time, press the test button again and the UPS will start working.
The second situation: After the UPS inverter has been working for a period of time, the UPS cannot start.
Also because the battery is low, it needs to be charged.
The third situation: The battery has been used for about 2 years and the UPS cannot start.
According to the usage of most customers, the battery will generally have a capacity reduction problem to a greater or lesser extent after two years of use. If the battery cannot play the role of delaying the use, it needs to be replaced with a new one.
The fourth situation: The voltage of each battery is normal, but the UPS cannot start.
At this time, although the voltage of a single battery is normal, 1. It is likely that there is a problem with the connection between the batteries or between the battery and the UPS, such as: the connection point is not firm or the connection point is oxidized. At this time, you need to remove the oxide and reconnect. 2. The fuse connecting the UPS and the battery may be broken. If the fuse is broken, just replace it. 3. The connection between the UPS and the battery is very long and thin or there is a connection point in the middle, which produces a large voltage drop, causing the UPS to fail to start.
2. After the mains power is cut off, the UPS cannot switch to inverter mode.
Let the UPS work under the mains power, set the multimeter to the voltage range, connect the test leads to the inside of the Anderson plug on the back of the UPS, and directly measure the DC voltage reaching the UPS. At this time, one person observes the multimeter display, and the other person unplugs the input line of the UPS and observes the multimeter display at the moment of power failure. If the voltage value drops a lot instantly, it means that there is a problem with the battery. If the connection problem can be eliminated and the battery has been used for about two years, it is necessary to consider replacing the battery pack.
3. The UPS inversion time is short and cannot meet customer requirements.
First, the battery parameters of the Smart-UPS long-duration model must be set at the beginning of installation. If the battery parameters are not set, the problem of short inverter time will occur.
Second, the battery parameters have been set, but the UPS inversion time is still very short. You can measure the battery voltage when the UPS low-power alarm sounds. If the measured value shows that the battery is indeed in a low-power state, you need to replace the battery. If the measured value shows that the battery is not in a low-power state, you need to perform a charge and discharge verification. Note that during the charge and discharge verification, the battery must be fully charged and needs to carry about 50% of the load when discharging.
Third, after installing the PowerChutePlus software, the default setting of the software is: the computer will shut down 5 minutes after the mains power is interrupted, so you need to modify the parameters in the software.
Mains power environment
1. Grid interference.
If there is a very serious interference in the power grid, such as voltage sag and other power interference, it may cause UPS to fail and other faults. Below we list some such mains interference. You can install PowerChutePlus software and use the software's event log to understand whether there is power interference in the power grid. If you see a lot of such records in the event log, it means that there is a serious interference in your mains power grid, which will also reduce the service life of the battery. If conditions permit, it is recommended that you replace one mains input or transform the power grid.
PowerChutePlus event logging can record the following mains disturbances:
UPSONbattery: Deepmomentarysag deep voltage sag
UPS on battery: Large momentary spike, deep high voltage pulse
UPSonbattery:Brownout continuous low voltage
UPSonbattery:HighinputLinevoltageHigh input voltage
UPS on battery: Small momentary spike Mild high voltage pulse
UPS on battery: Small momentary sag Mild voltage sag
2. A leakage protector is installed at the UPS input end.
When the UPS is turned on, the leakage protector will trip. If you need to install a leakage protector, you need to connect the leakage protector to the output line of the UPS.
3. The air switch at the UPS input end trips.
This phenomenon may be caused by the small capacity of the air switch at the UPS input end. Since the starting current of the UPS is relatively large, the capacity of the air switch at the front end is required to be large enough.
4. The UPS inverter state and online state are frequently switched.
First, it could be caused by fluctuations in the mains electricity. Second, if you are using a generator, this could happen.
How to do it:
1. Smart-UPS cannot cold start, but can work as an inverter normally.
This is an incorrect operation method. The correct cold start procedure is: press and hold the Test key for about 4 seconds, and release it immediately after hearing a "beep" sound. The UPS can then cold start. If the key is pressed for too long or too short, the UPS cannot cold start. It is recommended that you try this procedure several times.
2. UPS and computer communication is abnormal.
This problem can occur if you are not using an APC original communication cable.
4. Connection method of SU5000UXI, SU5000INET, SU5000RMINET input line.
These three models do not come with input cables when they leave the factory, but they have dedicated input cable terminals. Input cable connection steps: Find the UPS input cable terminal (for SU5000INET, the input cable terminal is at the upper right corner of the back of the UPS, and for SU5000RMINET, it is at the upper left corner of the back of the UPS). It is hidden in the cover, which is fixed by a screw. You need to use a screwdriver to loosen the screw and remove the cover to connect the input line.
5. The fan starts frequently when Smart-UPS is working online.
This situation is caused by the high temperature inside the UPS. You can install PowerChutePlus to observe the internal temperature of the UPS. Generally, the fan starts when the temperature inside the machine reaches 40 degrees Celsius. This design is to improve the service life and operational reliability of the UPS.
Other factors:
1.Smart-UPS often has overload alarm.
Please check whether there is a printer connected to the UPS. It is not recommended to connect the printer behind the UPS, because the working current of the printer will suddenly increase a lot when printing, which may cause the UPS to overload and power off. It is also not recommended to connect the power socket behind the UPS, because the power socket may cause a momentary short circuit and cause the UPS to overload.
2. The LCD display of Matrix5000 and Matrix3000 shows: NoBatteryCommunications
This is because the original SmartCell or SmartCellXR battery pack is not configured. This message only shows "no battery communication" and will not affect the normal operation of the UPS.
Previous article:Simple and practical charger non-polarity connection device
Next article:Delay Block/Debouncer—LTC6994
Recommended ReadingLatest update time:2024-11-16 20:47
- Popular Resources
- Popular amplifiers
- MathWorks and NXP Collaborate to Launch Model-Based Design Toolbox for Battery Management Systems
- STMicroelectronics' advanced galvanically isolated gate driver STGAP3S provides flexible protection for IGBTs and SiC MOSFETs
- New diaphragm-free solid-state lithium battery technology is launched: the distance between the positive and negative electrodes is less than 0.000001 meters
- [“Source” Observe the Autumn Series] Application and testing of the next generation of semiconductor gallium oxide device photodetectors
- 采用自主设计封装,绝缘电阻显著提高!ROHM开发出更高电压xEV系统的SiC肖特基势垒二极管
- Will GaN replace SiC? PI's disruptive 1700V InnoMux2 is here to demonstrate
- From Isolation to the Third and a Half Generation: Understanding Naxinwei's Gate Driver IC in One Article
- The appeal of 48 V technology: importance, benefits and key factors in system-level applications
- Important breakthrough in recycling of used lithium-ion batteries
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
- Comparison of CC2540 and nRF51822 application development
- Application of TI current detection device INA series in TWS battery box
- Now we need to produce a batch of calibration cards (EEPROM 24C128 + pull-up resistors for SCL and SDA signals, a total of three components...
- CAN (Controller Area Network) bus batch data transmission based on SAEJ1939 wireless communication data transmission protocol
- Power supply output power problem
- STM32MP157A-DK1 Evaluation (4) UART and SPI Device Access
- WLAN radio frequency and channels
- What kind of IoT card is reliable?
- [RVB2601 Creative Application Development] Initially implement the perpetual calendar function of NTP clock synchronization
- Practical Tips | How to learn hardware design well? Experts teach you from theory to practice