Linhuai Substation of Bengbu Power Supply Company is an old substation with a history of 40 years. In May 2011, it carried out the last comprehensive automation transformation of the interval - the comprehensive automation transformation of the 1# main transformer protection.
On the third day of the renovation work, the 10kV 01 circuit breaker on the low-voltage side of the main transformer was verified for opening and closing and signal verification. When the operating power supply or the measurement and control power supply (motion signal and measuring device power supply) of the 01 circuit breaker was supplied separately, there was no crosstalk between the operating circuit and the signal circuit. However, during the actual closing operation of the 01 circuit breaker, the protective screen 01 operating power supply air switch and the 1# main transformer measurement and control power supply air switch were tripped at the same time, but the 01 circuit breaker had been successfully closed; the opening was normal after the power was supplied again; the above process was repeated and the fault still existed. When the operating power supply of the protective screen was supplied separately but the measurement and control power supply was not supplied, the opening and closing were normal. Because the original 01 circuit breaker "spring no energy storage" signal was not used, the newly equipped wiring used this signal during this comprehensive automation renovation, which caused this phenomenon. It shows that the closing circuit was caused by the instantaneous short circuit of the contact point caused by the spring no energy storage (when the circuit breaker releases energy during the closing process), which caused the operating power supply air switch and the 1# main transformer measurement and control power supply air switch to trip at the same time.
Based on the above judgment, we disconnected the power supply of each circuit and shook the insulation of the spring energy-stored contacts in the protection closing circuit and the spring non-energy-stored contacts in the remote signal circuit. The result was good. We further checked the secondary wiring of the 01 circuit breaker and found that there was an error. The details are as follows:
The incorrect wiring is as follows (original wiring):
HQ—closing coil; TQ—tripping coil; DL—circuit breaker auxiliary contact; CK—spring energy storage contact
The wiring after correction is as shown below (correct wiring):
Figure 2
Based on the above fault phenomenon, we analyze as follows:
1. The circuit breaker opened and closed normally before the comprehensive automation transformation, but the above phenomenon occurred after the transformation. This is due to the connection of the newly connected "spring without energy storage" contact.
2. The circuit breaker is open normally and the separate operating power supply is open and closed normally. Only the air switch trips at the moment of closing, which means that the switch fails during the process of spring energy release at the moment of closing.
3. The spring contact of the closing circuit and the contact of the signaling circuit use a normally open contact and a normally closed contact in the same section of the travel contact. During the closing process of the circuit breaker, the spring contact of the closing circuit and the spring contact of the signal circuit are instantly adhered due to the rapid release of the spring energy. At the same time, due to the incorrect connection method of the circuit breaker wiring as shown in the figure above, the negative power supply of the circuit breaker operation is short-circuited to the positive power supply of the remote signal.
4. After correcting the wiring, even if the above adhesion occurs, short circuit is not allowed due to the existence of closing coil HQ. The specific contact points are as shown in the figure below:
Spring energy storage contact diagram:
Spring contact installation diagram:
Figure 4
After the wiring is corrected as shown in the figure above, the circuit breaker opens and closes normally. At the same time, it also exposes the irregularity of the wiring of the circuit breaker manufacturer, reminding the protection personnel to be careful and careful when constructing the secondary circuit to prevent accidents or potential accidents.
Previous article:A new detection method for insulator faults in power lines
Next article:A brief analysis of wiring cases in the smart home industry
- MathWorks and NXP Collaborate to Launch Model-Based Design Toolbox for Battery Management Systems
- STMicroelectronics' advanced galvanically isolated gate driver STGAP3S provides flexible protection for IGBTs and SiC MOSFETs
- New diaphragm-free solid-state lithium battery technology is launched: the distance between the positive and negative electrodes is less than 0.000001 meters
- [“Source” Observe the Autumn Series] Application and testing of the next generation of semiconductor gallium oxide device photodetectors
- 采用自主设计封装,绝缘电阻显著提高!ROHM开发出更高电压xEV系统的SiC肖特基势垒二极管
- Will GaN replace SiC? PI's disruptive 1700V InnoMux2 is here to demonstrate
- From Isolation to the Third and a Half Generation: Understanding Naxinwei's Gate Driver IC in One Article
- The appeal of 48 V technology: importance, benefits and key factors in system-level applications
- Important breakthrough in recycling of used lithium-ion batteries
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
- Communication between EMIF and FPGA of TMS320C6455
- 【GD32L233C-START Review】12. Hardware IIC drive OLED
- EEWORLD University Hall----Live Replay: TI 60G mmWave Sensor Overview and Application Introduction
- Short Range Communication Protocol
- Full-wave precision rectifier circuit composed of comparators
- NUCLEO-474 Download the official example prompt No debug probe... Solution
- SERDES interface circuit design
- TMS320C55x DSP Library
- Antenna Basics and Introduction to 40+ Antennas
- Brief analysis: RF power meter principle, classification, index and application