Comparison between DA series inverter and UPS modified inverter: The biggest feature of the so-called telecommunication inverter is that the DC supply voltage is 48V, but the inverter modified from the UPS with a supply voltage of 48V is not actually suitable for communication systems.
First: The input noise of the DA series inverter is small. The battery pack equipped with the UPS is used alone, and the parallel use of its battery pack is not considered. Therefore, for the UPS, the feedback noise of the input end, which is the most important thing for the communication system, is not considered, and the noise at the input end is extremely large. If the UPS battery pack is shared with the communication system, interference will occur, affecting the call quality.
Second: The DA series inverter has a specially designed DC buffer circuit. The general UPS only has an AC buffer circuit design, that is, to prevent the UPS from being impacted when the AC is turned on, but it is not enough for the communication system and is dangerous. Because the battery pack used in the communication room generally has a capacity of more than several thousand AH, when the DC switch is started, the surge generated by the battery pack is very easy to damage the components in the UPS and also easily consume the battery life. Therefore, a buffer startup circuit must be added between the battery pack and the inverter to solve the above problems.
Third: The capacity of the DA series inverter is doubled compared to the inverter of the general UPS. When the load of the general UPS is started, in order to prevent the cold start effect of the computer capacitive load, that is, the huge load current will be generated at the moment of startup (about 10ms), so it jumps to the bypass when starting and is powered by the mains. However, the DA series inverter is not the case. When the load is started or cold-started, all the impacts generated by the cold start are borne by the inverter. Therefore, the capacity factor of the DA series inverter is twice that of the UPS inverter. The DA series inverter has battery reverse connection protection. The capacity of the battery in the computer room is very large. If the inverter modified from the UPS is accidentally reversed when the battery is connected, not only the UPS will be damaged, but also the battery will be permanently damaged. However, the reverse connection protection of the DA series will prevent the startup when an error occurs, which can avoid the above problems.
Some users think that using a 48V UPS inverter, under normal circumstances, the power supply of the machine is supplied by the mains, instead of the battery pack, which seems to reduce the burden on the battery. In fact, the capacity of the battery pack used in the communication room is generally more than several thousand AH, and the battery pack is usually float-charged by the communication switch power supply (with a capacity of several hundred amperes). Therefore, there is no need to worry that the DA series inverter will add a great burden to the battery pack. In addition, due to the great interference, distortion and mutation of the industrial power grid, the UPS inverter that is usually powered by the mains will inevitably interfere with its load and affect the good operation of the load. At the same time, due to the harmonic current generated by the rectifier, it will cause backflow pollution to the power grid. Because the mains power is suddenly interrupted, the battery pack power supply current changes from zero to a large value, which will cause the battery pack voltage to drop instantly. The DA series communication dedicated inverter has nothing to do with the mains power, so the interference of the mains power does not affect the computer load. DA series inverters use the bypass system only when the inverter is damaged to supply the load with AC power. Therefore, when the inverter is used normally, the AC power is also isolated and purified.
Keywords:Communications
Reference address:Comparison between dedicated communication inverter and UPS modified inverter
First: The input noise of the DA series inverter is small. The battery pack equipped with the UPS is used alone, and the parallel use of its battery pack is not considered. Therefore, for the UPS, the feedback noise of the input end, which is the most important thing for the communication system, is not considered, and the noise at the input end is extremely large. If the UPS battery pack is shared with the communication system, interference will occur, affecting the call quality.
Second: The DA series inverter has a specially designed DC buffer circuit. The general UPS only has an AC buffer circuit design, that is, to prevent the UPS from being impacted when the AC is turned on, but it is not enough for the communication system and is dangerous. Because the battery pack used in the communication room generally has a capacity of more than several thousand AH, when the DC switch is started, the surge generated by the battery pack is very easy to damage the components in the UPS and also easily consume the battery life. Therefore, a buffer startup circuit must be added between the battery pack and the inverter to solve the above problems.
Third: The capacity of the DA series inverter is doubled compared to the inverter of the general UPS. When the load of the general UPS is started, in order to prevent the cold start effect of the computer capacitive load, that is, the huge load current will be generated at the moment of startup (about 10ms), so it jumps to the bypass when starting and is powered by the mains. However, the DA series inverter is not the case. When the load is started or cold-started, all the impacts generated by the cold start are borne by the inverter. Therefore, the capacity factor of the DA series inverter is twice that of the UPS inverter. The DA series inverter has battery reverse connection protection. The capacity of the battery in the computer room is very large. If the inverter modified from the UPS is accidentally reversed when the battery is connected, not only the UPS will be damaged, but also the battery will be permanently damaged. However, the reverse connection protection of the DA series will prevent the startup when an error occurs, which can avoid the above problems.
Some users think that using a 48V UPS inverter, under normal circumstances, the power supply of the machine is supplied by the mains, instead of the battery pack, which seems to reduce the burden on the battery. In fact, the capacity of the battery pack used in the communication room is generally more than several thousand AH, and the battery pack is usually float-charged by the communication switch power supply (with a capacity of several hundred amperes). Therefore, there is no need to worry that the DA series inverter will add a great burden to the battery pack. In addition, due to the great interference, distortion and mutation of the industrial power grid, the UPS inverter that is usually powered by the mains will inevitably interfere with its load and affect the good operation of the load. At the same time, due to the harmonic current generated by the rectifier, it will cause backflow pollution to the power grid. Because the mains power is suddenly interrupted, the battery pack power supply current changes from zero to a large value, which will cause the battery pack voltage to drop instantly. The DA series communication dedicated inverter has nothing to do with the mains power, so the interference of the mains power does not affect the computer load. DA series inverters use the bypass system only when the inverter is damaged to supply the load with AC power. Therefore, when the inverter is used normally, the AC power is also isolated and purified.
Previous article:A practical design of vehicle-mounted inverter (Figure)
Next article:Design of 500W solar inverter using IGBT as power switch
Recommended ReadingLatest update time:2024-11-16 21:59
In-depth analysis of the working principle of UPS power rectifier
Modern rectifier chargers are divided into two types: buck type and boost type. The buck type is mainly used when the UPS battery pack voltage is lower than a certain value of the input AC peak voltage, while the boost type is mainly used when the UPS battery pack voltage is higher than the input AC peak voltage.
[Power Management]
Analysis of the impact of UPS battery capacity and discharge rate
When UPS manufacturers configure
batteries
, the design capacity they choose fully meets or even exceeds the power capacity and power supply time requirements of the load without power outages. However, after
the UPS
is put into operation, users often find that the actual time the UPS can prov
[Power Management]
UPS power system product classification and market demand details
UPS power system equipment technology refers to a comprehensive technology that relies on advanced power conversion technology, digital control technology, high-frequency switching conversion technology, pulse width modulation technology, electromagnetic compatibility technology, redundant parallel technology, intellig
[Power Management]
How to optimize UPS availability in data centers
So, how can data center operators optimize UPS availability? UPS reliability is the ultimate design factor in the overall UPS power system design function. Whether you are in your UPS or power protection solution, the most reliable way to increase UPS availability is to focus on reducing maintenance time and maximizin
[Power Management]
Preventing data center UPS power supply from going offline
The UPS AC power supply system is different from the conventional -48V DC power supply system. Its characteristics are that the UPS power supply equipment has the requirements of initial phase angle and frequency synchronization, and the output voltage is high, which is the AC 380V power supply voltage. The parallel op
[Power Management]
Four factors for small and medium-sized enterprises to choose suitable UPS products
At present, there are many brands of UPS products in the market, with uneven product quality and chaotic competition. In order to choose the right UPS product, end users need to improve their understanding of UPS. Experts say that when choosing a UPS, you can start with four major standards and choose products that
[Power Management]
Detailed explanation of UPS power supply purchase tips and steps
UPS stands for Uninterruptible Power Supply . It can ensure that the computer system continues to work for a period of time after a power outage so that users can save files urgently and avoid affecting work or losing data due to power outages. So what factors should be considered when purchasing? 1. Factors to c
[Power Management]
Technical Analysis: Intelligent Network UPS System
The rapid development of the Internet, the mutual promotion of communications and computers, has put higher and higher requirements on the power supply quality of the precision electronic equipment used in them, such as computers, programmable switches, industrial process control and real-time control and computing
[Power Management]
- Popular Resources
- Popular amplifiers
Recommended Content
Latest Power Management Articles
- MathWorks and NXP Collaborate to Launch Model-Based Design Toolbox for Battery Management Systems
- STMicroelectronics' advanced galvanically isolated gate driver STGAP3S provides flexible protection for IGBTs and SiC MOSFETs
- New diaphragm-free solid-state lithium battery technology is launched: the distance between the positive and negative electrodes is less than 0.000001 meters
- [“Source” Observe the Autumn Series] Application and testing of the next generation of semiconductor gallium oxide device photodetectors
- 采用自主设计封装,绝缘电阻显著提高!ROHM开发出更高电压xEV系统的SiC肖特基势垒二极管
- Will GaN replace SiC? PI's disruptive 1700V InnoMux2 is here to demonstrate
- From Isolation to the Third and a Half Generation: Understanding Naxinwei's Gate Driver IC in One Article
- The appeal of 48 V technology: importance, benefits and key factors in system-level applications
- Important breakthrough in recycling of used lithium-ion batteries
MoreSelected Circuit Diagrams
MorePopular Articles
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
MoreDaily News
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
- New real-time microcontroller system from Texas Instruments enables smarter processing in automotive and industrial applications
Guess you like
- 【National Technology N32G430】LCD-ST7735
- The STM32 video account and B station account have been opened. Are you paying attention?
- 【RT-Thread Reading Notes】Reflections on RT-Thread Chapter 9
- 100% gift for a limited time: Download and share Keysight millimeter wave radar data to win a gift
- About GUI_Init stuck when emwin is ported to stm32f2
- Huawei Static Timing Analysis and Logic Design.pdf
- Where does the TTL on the laser driver board connect to the CNC shield V3 board?
- [ART-Pi Review] Part 3: Serial terminal and msh component of RTT Studio project
- DLP6500 light crafter uses USB synchronous trigger signal to play the next picture
- Why Python hasn't taken off on mobile devices or in the browser