Fault diagnosis ideas for liquid level instruments

Publisher:czl55555Latest update time:2022-09-13 Source: csdn Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

Differential pressure level meters account for a large proportion of level meters, so we will focus on introducing them. The speed of change of the level parameter is closely related to the volume of the container, and whether its change speed is normal should be judged based on the actual situation. For example, the drum level of a boiler changes very quickly, but the level of a liquid storage tank changes slowly. If the level display suddenly changes and fluctuates greatly, such as when it indicates the maximum or minimum, the instrument is likely to be faulty.


When the liquid level display value reaches the maximum or minimum, the differential pressure transmitter should be checked first. If the transmitter is normal, the display instrument is mostly faulty. If the output of the transmitter is consistent with the display of the display instrument, the liquid level control system can be changed to manual operation, that is, manually change the opening of the regulating valve to observe whether the liquid level changes. If the liquid level changes, it is generally due to process reasons. If there is no change, the instrument is faulty.


When the liquid level record curve fluctuates greatly and quickly, it may be that the PID parameters are improperly set or the parameters have changed. The damping of the transmitter is not adjusted properly, and the pressure pipeline leaks, which may cause the liquid level record curve to fluctuate.


The most feared thing when measuring liquid level is the occurrence of false liquid level. If you suspect a false liquid level phenomenon, you must make a calm judgment. You can switch the control system to manual operation, then check or calibrate the transmitter and system, and check all pressure pipes and valves for problems until the problem is found.


Reference address:Fault diagnosis ideas for liquid level instruments

Previous article:Phase measurement
Next article:The relationship between the speed of the megohmmeter and the insulation resistance value being measured

Latest Test Measurement Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号