1. Pointer jitter:
Reference address:Application failure of metal tube flowmeter of electronic measuring instrument
1. Slight pointer jitter: generally caused by medium fluctuations. This can be overcome by increasing damping.
2. Moderate pointer jitter: generally caused by the flow state of the medium. For gas, it is generally caused by unstable medium operating pressure. A pressure stabilizing or flow stabilizing device can be used to overcome or increase the gas damping of the float flowmeter.
3. Severe pointer jitter: mainly due to medium pulsation, unstable air pressure or the pressure, temperature and flow rate of the gas operating state given by the user do not match the actual state of the float flowmeter. There is a large difference causing the float flowmeter to over-range.
2. The main reason why the pointer stops at a certain position and does not move is that the float of the float flowmeter is stuck.
Generally, when the metal tube float flowmeter is used, the valve is opened too quickly, causing the float to quickly impact the stopper, causing the stopper to deform and jam the float. However, it is not ruled out that the float is jammed due to the non-concentricity of the float guide rod and the stop ring.
When handling, the instrument can be disassembled, the deformed stopper can be removed and reshaped, and check whether it is concentric with the guide rod. If not, it can be corrected. Then the float can be installed and the float can be pushed by hand until it feels that the float can move up and down smoothly without obstruction. In addition, the float flowmeter must be installed vertically or horizontally and cannot be tilted, otherwise it will easily cause the meter to get stuck and bring errors to the measurement.
3. Large measurement error
1. Installation does not meet the requirements. For vertically installed metal tube float flowmeters, they must be kept vertical, with an inclination of no more than 20 degrees. For horizontally installed float flowmeters, they must be kept horizontal, with an inclination of no more than 20 degrees. There must be no ferromagnetic objects in the 100mm space around the float flowmeter. The installation location should be far away from the valve reducer, pump outlet, process pipeline bend, etc. The straight pipe section requirement of 5D in front and 250mm in the back should be maintained.
2. Large changes in the density of liquid media are also a reason for large errors. Before calibration, the instrument converts the medium into the density given by the user and converts it into the water flow rate under the calibration state for calibration. Therefore, if the medium density changes greatly, it will cause a large error in the measurement. The solution is to bring the changed medium density into the formula, convert it into an error correction coefficient, and then multiply the flow measured by the flowmeter by the coefficient to convert it into the actual flow.
3. Since gas media are greatly affected by temperature and pressure, it is recommended to use temperature and pressure compensation to obtain the actual flow rate.
4. Due to long-term use and pipeline vibration and other factors, the active parts of the metal tube float flowmeter such as the sensor magnet, pointer, counterweight, rotating magnet, etc. are loose, resulting in large errors. Solution: You can first verify by pushing the pointer by hand. First, press the pointer at the RP position to see if the output is 4mA and the flow display is 0%, and then verify according to the scale. If it is found to be inconsistent, the position of the component can be adjusted. Generally, professional personnel are required to adjust, otherwise the position will be lost and it needs to be returned to the manufacturer for correction.
4. No current output
1. First check whether the wiring is correct.
2. Check whether the LCD has any display. If there is display but no output, it is probably that the output tube is broken and the circuit board needs to be replaced.
3. Loss of calibration value. Due to E2PROM failure, the calibration data of the instrument is lost, which will also cause no output current, and the current will remain unchanged. Solution: You can use the data recovery operation. If it does not work, you can first set the data in password 2000, and then set the data in password 4011. The method is to use the hand-pushing pointer to calibrate the data from RP to 100%.
5. No on-site display
1. Check whether the wiring is correct.
2. Check whether the power supply is correct.
3. Reinstall the LCD module and check for loose contact.
4. For multi-wire power supply mode, check whether terminals 12 and 13 are connected to an ammeter or short-circuited.
6. The on-site LCD always displays 0 or full scale
1. Check the range and zero parameters set in the password 2000. It is required that ZERO should be smaller than SPAN and the two values cannot be equal.
2. Check whether the sampling data is coming up, push the pointer by hand to see the sampling value change. If there is no change, it is generally due to a circuit board sampling circuit failure, and the circuit board needs to be replaced.
7. Incorrect alarm
1. Check that the deviation setting d value is not too large.
2. In the FUN function, is the logic function correct? HA-A indicates upper limit positive logic. LA-A indicates lower limit positive logic.
3. Check the alarm value setting in SU.
4. If the LCD barcode indication is correct and the output has no action, check the external power supply and whether the negative pole of the external power supply is connected to the negative pole of the instrument power supply.
5. The circuit board is faulty, please replace it.
8. The cumulative pulse output is incorrect
1. Check whether the alarm value of the channel that selects the cumulative pulse output is set to zero.
2. The circuit board is faulty, please replace it.
Previous article:Importance of Toxic and Hazardous Gas Detectors
Next article:In-phase interference and suppression method of electromagnetic flowmeter
Recommended Content
Latest Test Measurement Articles
- Keysight Technologies Helps Samsung Electronics Successfully Validate FiRa® 2.0 Safe Distance Measurement Test Case
- From probes to power supplies, Tektronix is leading the way in comprehensive innovation in power electronics testing
- Seizing the Opportunities in the Chinese Application Market: NI's Challenges and Answers
- Tektronix Launches Breakthrough Power Measurement Tools to Accelerate Innovation as Global Electrification Accelerates
- Not all oscilloscopes are created equal: Why ADCs and low noise floor matter
- Enable TekHSI high-speed interface function to accelerate the remote transmission of waveform data
- How to measure the quality of soft start thyristor
- How to use a multimeter to judge whether a soft starter is good or bad
- What are the advantages and disadvantages of non-contact temperature sensors?
MoreSelected Circuit Diagrams
MorePopular Articles
- Innolux's intelligent steer-by-wire solution makes cars smarter and safer
- 8051 MCU - Parity Check
- How to efficiently balance the sensitivity of tactile sensing interfaces
- What should I do if the servo motor shakes? What causes the servo motor to shake quickly?
- 【Brushless Motor】Analysis of three-phase BLDC motor and sharing of two popular development boards
- Midea Industrial Technology's subsidiaries Clou Electronics and Hekang New Energy jointly appeared at the Munich Battery Energy Storage Exhibition and Solar Energy Exhibition
- Guoxin Sichen | Application of ferroelectric memory PB85RS2MC in power battery management, with a capacity of 2M
- Analysis of common faults of frequency converter
- In a head-on competition with Qualcomm, what kind of cockpit products has Intel come up with?
- Dalian Rongke's all-vanadium liquid flow battery energy storage equipment industrialization project has entered the sprint stage before production
MoreDaily News
- Allegro MicroSystems Introduces Advanced Magnetic and Inductive Position Sensing Solutions at Electronica 2024
- Car key in the left hand, liveness detection radar in the right hand, UWB is imperative for cars!
- After a decade of rapid development, domestic CIS has entered the market
- Aegis Dagger Battery + Thor EM-i Super Hybrid, Geely New Energy has thrown out two "king bombs"
- A brief discussion on functional safety - fault, error, and failure
- In the smart car 2.0 cycle, these core industry chains are facing major opportunities!
- Rambus Launches Industry's First HBM 4 Controller IP: What Are the Technical Details Behind It?
- The United States and Japan are developing new batteries. CATL faces challenges? How should China's new energy battery industry respond?
- Murata launches high-precision 6-axis inertial sensor for automobiles
- Ford patents pre-charge alarm to help save costs and respond to emergencies
Guess you like
- Are there any pmos and nmos tubes with working current |Ids|=1.2A;|Vds|<0.2V, which don't matter if they are enhanced or not, and have low leakage current when turned off?
- EEWORLD University Hall----TI 77GHz millimeter wave radar product introduction and solution display
- KiCad 5.1.5 latest stable version Chinese tutorial
- Understand C language pointers in 1 minute
- TMS320F28377S LaunchPad XDS100 V2 driver cannot be installed
- Building a Raspberry Pi Pico development environment under Windows
- On-policy, its process is the same as the above strategic gradient. Practical analysis
- 【ESP32-Korvo Review】 03 Blinker Lighting
- Answer the questions and win prizes | TDK special reports are waiting for you (Issue 2)
- Today is Chinese Valentine's Day, Alipay has launched an electronic marriage certificate, have you gone to pick up your partner?