ATV6171 inverter common problems summary 1

  • 2013-06-26
  • 113.22KB
  • Points it Requires : 2

If the start signal is given first and then the power is turned on, 71 and 61 will be in the NST state and will not start. If a certain LI is set to free stop but not closed, it will be in the NST state. In three-wire control, if LI1 is not closed, it will be in the NST state. When the inverter is controlled by communication, NST will be displayed after power-on. According to the DRIVECOM status table, the inverter can be started normally by reading the status word (ETA) and writing the control word (CMD).