Motor current quick-break Bach circuit a composed of electromagnetic current relay

Source: InternetPublisher:MartinFowler Keywords: Electromechanical electric motor current relay electromagnetic Updated: 2021/02/02

51. Electrical<strong>electromechanical</strong> current-breaking Bach circuit a.gif composed of <strong>electromagnetic</strong> type<strong>current relay</strong>

Medium and small-capacity high-voltage motors generally use current quick-break protection as the main protection for phase-to-phase short circuit. For
high-voltage motors that are not prone to overcurrent, current quick-break protection composed of electromagnetic type (such as DL-11 type) current relays is usually used; for high-voltage motors
that may generate overcurrent , induction type (GL type) overcurrent relays can be used The inverse time limit part of the current quick-break protection and over-current protection is used as over-current protection and acts on the signal. The over-current protection time limit is generally 15 to 20 seconds, and the quick-break part is used as phase-to-phase short circuit protection and acts on tripping. The circuit is shown in Figure 4-51.





EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号