Home > Control Circuits >Motor Control > Generator longitudinal differential protection circuit a

Generator longitudinal differential protection circuit a

Source: InternetPublisher:红水杯 Keywords: Protection circuit generator BSP circuit breaker Updated: 2020/07/05

21.<strong>Generator</strong>Longitudinal differential<strong>Protection circuit</strong>a.gif

Generator longitudinal differential protection is used to protect generator stator windings from phase short circuit. For generators below 800kW, when
the sensitivity of the current quick-break protection does not meet the requirements, longitudinal differential protection can be installed; for generators above 800kW,
longitudinal differential protection should be installed.
    The generator longitudinal differential protection circuit is shown in Figure 7-21. In the figure, 1TA and 2TA are current transformers, KA, ~KA.
is the current relay, and KS is the signal relay. KC is the outlet relay, QF is the outlet circuit breaker , and YR is the circuit breaker trip
coil.