Contactor mutual switching circuit for dual power supply part 3

Source: InternetPublisher:toothache Keywords: Power supply BSP contacts Updated: 2021/12/12

133. Dual-circuit<strong>power supply</strong> uses contactor to transfer<strong>circuit</strong> to each other.gif

Mutual switching of dual power supplies means that the load is powered by two power supplies, and the two power supplies work at the same time and bear the electrical load respectively. When
one of the power supplies fails, the tie switch automatically closes, and all loads are powered by the non-power outage circuit.

Voltage relay KAi-KA6 uses DJ-111/220V.


The circuit is shown in the figure. Under normal circumstances, power supply No. 1 supplies power to the load of section A bus, and power supply No. 2 supplies power to
the load of section B bus. Note: The auxiliary contacts
    of circuit breakers QFi and QF2 must act one At time before the main contacts (mechanical adjustment is available), otherwise two different power supplies will merge in an instant, causing a short circuit.