Home > Control Circuits >Motor Control > One of the automatic control circuits that only allows the motor to run in one direction

One of the automatic control circuits that only allows the motor to run in one direction

Source: InternetPublisher:张三叔 Keywords: Motor BSP power supply Updated: 2021/03/16

90. One of the self-control<strong>circuit</strong>s that only allows<strong>motor</strong> to operate in one direction.gif


90. In some places, the motor is only allowed to run in one designated direction. Even when the power phase sequence
is reversed for some reason (such as incorrect connection after external circuit maintenance), the motor must be guaranteed to run in the designated direction. Otherwise, personal and equipment accidents may occur
. For this purpose, a phase sequence discriminator can be used for control.
    The circuit is shown in Figure 3-90. When the phase sequence of the power supply is correct, that is, when the phase sequence is U, V, W, the neon bulb Ne does not light up, the relay
KA is closed, and the start button SBi is pressed, the contactor KMi is closed, and the motor starts running in the forward direction. If the power phase sequence
is wrong, Ne lights up and KA releases. Press the SBi, KMz suction table, change the phase sequence of the motor and then connect it to the power supply . The motor
will still start running in the forward direction.


EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号