ModbusTCP to Profinet Gateway Connection to Schneider PLC Configuration Example

Publisher:CreativeMindLatest update time:2024-03-22 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

This case is a configuration case of Kaijiang Intelligent Profinet to ModbusTCP gateway connecting to Schneider PLC. The devices used are a Siemens 1200PLC, a KJ-PNG-206 gateway, and a Schneider PLC.


Configuration method:
Open Botu, create a new project and add the gsd file;

wKgaomUiI2eATBJuAAXyhSEi21k882.png


Establish a Profinet connection, set the IP address and device name of the Profinet to ModbusTCP gateway. The IP address should be in the same network segment as the Profinet to ModbusTCP gateway.

wKgaomUiI2uAWO8sAAFy3P7mYA0488.png


Enter the device view and select the total data length of input and output;

wKgZomUiI2-AEP3GAAJQCG2-1Y4606.png


Add the selected length from the hardware catalog on the right;

poYBAGL8eFWAQIyfAAEvXUkGIVU664.png


Download the configuration to the PLC, open the Profinet to ModbusTCP gateway configuration software to configure the Modbus parameters, click New in the red circle, and select PN2MS;

wKgZomUiI3eAFwCwAAFvcKhZXSI393.png


Set the IP address and device name of the Profinet to ModbusTCP gateway to be consistent with the PLC configuration;

wKgZomUiI3yAAS0nAAECn1_R0Sk462.png wKgaomUiI3yAYqfOAAChIKTYVmY763.png


Set the server IP of Modbus TCP and keep it in the same network segment as Schneider PLC with different IP;

wKgZomUiI4GAAekXAAIJdO8nqfg302.png


Note: The data area of ​​the Profinet to ModbusTCP gateway supports multiple function codes. Register addresses 0-749 correspond to the I address area of ​​Siemens PLC, and after 750, they correspond to the Q address area of ​​PLC. That is to say, Schneider needs to read the Q address area data of Siemens PLC from address 750, and write the data to the I address area of ​​Siemens PLC from register address 0. After configuring the IP and register address of the Profinet to ModbusTCP gateway slave in the Schneider PLC configuration, it can be used normally.


Reference address:ModbusTCP to Profinet Gateway Connection to Schneider PLC Configuration Example

Previous article:Commonly used methods for smart200PLC one-button start and stop
Next article:ModbusTCP to Profinet Gateway ModbusTCP as Slave Example

Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号