How to make IO configuration list in PLC programming design

Publisher:静默思考Latest update time:2023-08-24 Source: elecfansKeywords:PLC Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

Control system design is a basic skill that every industrial control engineer must master, and IO inventory, which we often call point counting, is the first task to be done.


The number of control system points is usually provided by the design institute. The system points are the sum of the instrument I/O points, electrical I/O points and the communication points between the control system and other systems. Accurately counting the electrical and instrument I/O points can avoid the problem of inconsistent coordination between the electrical and instrument professions. Accurate system points can provide a basis for the user to decide on the control system brand and system cost.


Control systems usually involve automated control contents such as thermal detection, analog control, sequential control and logical control. The points are obtained from the statistical results of five aspects: AI analog input points, AO analog output points, DI switch input points, DO switch output points and the communication points between the control system and other systems.


1. How to calculate the AI ​​input points of the automatic control system

AI refers to the analog input signal entering the control system. AI input signals that can be directly input into the system from the field include thermocouples (J, K, T, N, E, R, S and B-grade thermocouples), thermal resistance signals (Cu50, Cu100, Pt100 and Pt50-grade), standard current signals (4-20mA, 0-20mA), standard voltage signals (1-5V, 0-5V and 0-10V) and pulse signals; if other forms of signals need to be sent to the system, they must be converted into 4-20mA or 1-5V using signal isolators, current transmitters, voltage transmitters and other signal conversion equipment before being sent to the DCS system.

(1) Statistics of thermocouple AI input points

A single assembled thermocouple or a single armored thermocouple is calculated as one AI point. A double assembled thermocouple or a double armored thermocouple needs to be calculated as two AI points if the system displays the two sensor temperatures of the same measuring point, and calculated as one AI point if only one temperature of the measuring point is displayed. A single multi-point thermocouple or a multi-point thermocouple is often used to monitor the temperature of different parts of the same measuring point. If the thermocouple has several measuring points, the AI ​​input of several thermocouples is calculated.

(2) Statistics of thermal resistor AI input points

The statistical method for the number of thermal resistor AI input points is the same as that for the number of thermocouple AI input points.

(3) Statistics of standard current and voltage AI input points

Each 4-20mA, 0-2mA, 0-5V, 1-5V or 0-10V signal sent into the system is counted as one AI point, and the corresponding range of the input signal is counted at the same time. Since two-wire transmitters (including temperature transmitters, pressure transmitters, level transmitters, flow transmitters, etc.) involve DC24V power supply, it is best to count the AI ​​points separately to facilitate system integration wiring.

Special note: Field instruments such as pressure gauges, bimetallic thermometers, glass rotor flow meters, etc. displayed on site are not included in the system point calculation.


2. How to calculate AO output points

AO refers to the analog output signal of the control system that controls the on-site execution equipment. AO output generally has five types: 4-20mA, 0-20mA, 0-5V, 1-5V and 0-10V. 4-20mA is the most commonly used AO output of DCS system. AO output is usually connected to electric actuators, pneumatic actuators, frequency converters, power regulators and industrial control modules. Usually, each controlled object corresponds to one AO ​​output, and the number of AO output points is the same as the number of controlled devices.


3. How to calculate the DI input points

DI refers to the switch input signal entering the control system. DI input must be a passive contact, TTL or CMOS level signal. After DI enters the DCS system or PLC, it is usually connected to DC24V or DC48V query voltage.

The professional DI input of the instrument usually comes from the alarm contacts of on-site electric contact pressure gauges, electric contact bimetallic thermometers, electric contact water level gauges, liquid level switches, flow switches, flame detection, electric contact water level gauges and other instruments. Each alarm contact is calculated as a point DI input when connected to the system.


4. How to calculate DO output points

DO refers to the switch output signal of the control system that controls the field equipment, which is usually connected to other electrical equipment of different voltage levels through an intermediate relay. Instrument professional DO output is often used to control external indicator lights, solenoid valves, sound and light alarms, electrical controls and multi-turn electric actuators, contactors and other equipment.

The number of DO output points required for the system to control different devices is different. The following are the I/O points of common controlled objects:

(1) Switch type electric actuator: Each actuator has one AI input point for valve position feedback 4-20mA, two DO output points for valve forward/reverse control, two DI input points for valve open position/valve closed position signal, and two DI input points for valve open over torque/close over torque fault signal.

(2) Switch-type multi-turn electric actuator (AC380V power supply): For each actuator, the valve position feedback 4-20mA is calculated as 1 AI input point (if there is no feedback signal, the AI ​​point is not calculated), the valve forward/reverse control is calculated as 2 DO output points, the valve open position/valve closed position (limit switch) is calculated as 2 DI input points, and the actuator over-torque/over-torque fault signal is calculated as 2 DI input points.

(3) Modulating electric actuators: Each actuator valve position feedback calculates 1 AI input point, valve control signal calculates 1 AO output point, and actuator fault alarm signal calculates 1 AI input point (fault alarms are common in intelligent electric actuators. If there is no fault alarm signal, the AI ​​points are not calculated)

(4) Modulating multi-turn electric actuator: For each actuator, the valve position feedback is calculated as 1 AI input point, the actuator 4-20mA control signal is calculated as 1 AO output point, the ESD emergency control signal is calculated as 1 DO output point (ESD emergency control signals are common in intelligent multi-turn electric actuators. If this function is not available, the DO point is not calculated), and the opening torque/closing torque alarm signal is calculated as 2 DI input points.

(5) Inverter: Each inverter frequency feedback calculates 1 AI input point, the frequency given signal calculates 1 AO output point, the run/stop given command calculates 1 DO output point, the inverter fault alarm calculates 1 DI input point, the fault reset calculates 1 DO output point, and the inverter operation status calculates 1 DI input point.

If the inverter is connected to the DCS system via communication, only one communication point needs to be calculated, and no other points need to be calculated.

(6) If the system is connected to external devices such as solenoid valves, indicator lights, contactors, etc., calculate 1 DO output point for each device (if multiple devices share a control signal, it is usually accomplished by adding intermediate relay contacts, and only 1 DO output needs to be calculated).


5. How to calculate the control system points in electrical engineering

(1) System points of conventional electrical control

The simplest motor control circuit requires 2 DI input points and 1 DO output point. Each circuit operation status (from the contactor auxiliary contact) calculates 1 DI input point, the start/stop control signal (connected to the contactor coil) calculates 1 DO output point, and the fault signal (from the thermal relay or motor protector overload signal) calculates 1 DI input point.

If the motor circuit requires current display and local/remote control, in addition to calculating 2 DIs and 1 DO, the current signal (from the current transmitter) calculates 0-3 AI input points (small power motors usually do not need to monitor current, so the AI ​​input points are not calculated; high power three-phase motors have several phase currents that need to be sent to the DCS for display, so several AI input points are calculated. Each 0-5A current signal must be converted into a 4-20mA signal through a current transmitter and sent to the control system, up to 3 points); if the motor needs to be controlled in multiple locations, the control location selection switch calculates 1 DI input.

To facilitate your understanding, the following figure is the electrical secondary control schematic diagram of the GGD electrical cabinet, field operation box and control system.

46f21efc-d49c-11ed-bfe3-dac502259ad0.jpg

Functional description of the motor control secondary circuit: The stop button on the electrical cabinet and on-site operation box can stop the motor in any state; the control location selection switch can select "this cabinet control", "on-site control" and "automatic control", and the start button in the corresponding position of the selection switch can start the motor; when the selection switch is in "automatic control", the motor start/stop operation can be performed on the system.

Description of electrical components: In the secondary schematic diagram, 1SS is the stop button on the electrical cabinet, and 1SS1 is the stop button on the on-site operation box; 1SB is the start button on the electrical cabinet, and 1SB1 is the start button on the on-site operation box; DO is the system start/stop control output contact; 1HR5 is the power indicator light; 1HR is the run indicator light on the electrical cabinet, and 1HR1 is the run indicator light on the on-site operation box; 1HG is the stop indicator light on the electrical cabinet, and 1HR1 is the stop indicator light on the on-site operation box; 1KK is the operating ground switch; 1KH is a thermal relay; 1KM is a contactor; 1KA is an intermediate relay; 1FU is a secondary circuit fuse.

[1] [2]
Keywords:PLC Reference address:How to make IO configuration list in PLC programming design

Previous article:SCADA, DCS and PLC in one article
Next article:Siemens S7-1200PLC with parameter programming and without parameter programming

Recommended ReadingLatest update time:2024-11-16 09:50

Analysis of the button interlocking forward and reverse control circuit diagram of PLC electrical circuit control
The principles of electrical circuit control and PLC control are the same. Naturally, electrical control can be performed more conveniently and efficiently through PLC. So how is the electrical control circuit generated? How is it converted into a ladder diagram and then into a PLC-controlled logic instruction? In o
[Embedded]
Analysis of the button interlocking forward and reverse control circuit diagram of PLC electrical circuit control
Multiple ways to realize free port communication between Siemens S7-200PLC and PC
Siemens S7-200 supports multiple communication modes, such as point-to-point interface (PPI), multi-point interface (MPI), Rrofibus DP, etc. PPI and other communication protocols are mainly used for communication between Siemens series products and programming PLC. In free port mode, the user can control the serial
[Embedded]
Hongke Solution | How to choose between Hongke Industrial Raspberry Pi and PLC?
1. Raspberry Pi Before understanding Hongke Industrial Raspberry Pi, we must first understand what Raspberry Pi is. Raspberry Pi is a small computer based on ARM. It provides rich interfaces on Raspberry Pi and can realize more functions. It is also a favorite of developers. It is equipped with Linux system, ha
[Embedded]
Hongke Solution | How to choose between Hongke Industrial Raspberry Pi and PLC?
How to read the existing program in PLC?
PLC (Programmable Logic Controller) is an important automation device used to control and monitor various industrial processes. Programs in PLC are written by users and they define the behavior of the PLC in operation. This article will detail how to read the programs that already exist in the PLC. Reading the
[Embedded]
SIMATIC S7-1500 PLC startup organization block and its application
Startup Organization Block and Its Application The startup organization block (Startup) is executed once when the PLC's operating mode switches from STOP to RUN. After the startup organization block scan is completed, the main program cycle organization block (such as OB1) will be executed. The following exampl
[Embedded]
SIMATIC S7-1500 PLC startup organization block and its application
What are the concepts and instructions of PLC ladder diagram programming?
PLC is a device developed specifically for industrial control. In order to adapt to traditional habits and mastery, PLC usually does not use the programming language of microcomputers, but often uses "natural language" programming that is oriented to the control process and problem. The IEC1131-3 (Programmable Contr
[Embedded]
What are the concepts and instructions of PLC ladder diagram programming?
Siemens Schneider and other ten major manufacturers' mainstream PLC models and applications
1. Siemens LOGO and S7-200 are ultra-miniaturized PLCs, suitable for single-machine control or small-scale system control, and suitable for automatic detection, monitoring and control in all walks of life and various occasions. S7-300 is a modular small PLC system that can be used to directly control equip
[Embedded]
Efficient design and batch editing of PLC
This sharing mainly introduces readers to the efficient design and batch editing of PLC. In the previous research, we found that readers are very concerned about topics related to PLC design. So we hold this sharing, hoping that this sharing can bring some help to readers' work, broaden their R&D ideas, and improve
[Embedded]
Efficient design and batch editing of PLC
Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号