EPS solution based on Delta inverter

Publisher:数据探险家Latest update time:2012-01-11 Source: 互联网Keywords:Inverter Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

1 Introduction

EPS (Emergency Power Supply) is the abbreviation of emergency power supply. EPS is widely used in industrial and civil buildings, where sudden power outages will cause significant economic losses to normal production and life. It is an important part of modern building safety protection facilities. EPS is generally used as a backup support power supply for firefighting or production in emergency situations. For example, in high-rise buildings, shopping malls, hospitals, rail transit, underground shopping malls and other places with many people, few exits and limited natural light sources, once a fire occurs or the power grid is damaged, the light source disappears and it is pitch black. At the same time, there are many people and few exits, and the consequences will be disastrous. At the same time, the fire brigade will be unable to carry out disaster relief work due to the lack of power supply, which will aggravate the degree of the disaster. It can be seen that EPS plays an increasingly important role in the safety of modern society and is the patron saint of the "urban lifeline system".

At present, the control methods and control means adopted by EPS are different. The loads carried by EPS can be summarized into three types: the first is EPS mainly used for emergency lighting and accident lighting; the second is three-phase series EPS used for mixed loads such as air conditioners, elevators, rolling doors, exhaust fans, water pumps, etc. in addition to emergency lighting and accident lighting; the third is the variable frequency series EPS that directly supplies power to the motor . This article introduces the most comprehensive three-phase series EPS power supply for mixed loads.

2 EPS system based on Delta inverter

Delta's EPS solution mainly uses the inverter to drive the inverter AC motor for the fans, water pumps and rolling shutters of the fire protection system. Delta's customized EPS inverter can truly realize the connection of the common DC bus, so it can be used not only in the EPS industry, but also in the chemical fiber and glass manufacturing industries. The Delta dedicated inverter and synchronization card are used in combination to achieve the same input and output phases, thus meeting the application of special occasions. In view of the particularity of the motor drive in the EPS industry, Delta's inverter mainly adds parameters such as automatic torque compensation, torque compensation limit, and abnormal restart to meet the needs of special industries. The EPS charging module matched with the inverter reduces costs for customers, reduces heavy transformers, and reduces transportation costs.

2.1 Overview of EPS Special Machines

One of the main features of Delta EPS dedicated machine is that it can realize the common DC bus, thus expanding the application field of EPS dedicated machine. At the same time, the DC conversion of the internal contactor and soft start circuit meets the battery direct start requirements of EPS dedicated machine. Delta EPS dedicated inverter can form a highly reliable hybrid load dedicated inverter by matching with appropriate low-pass filter and transformer . And ensure the output voltage stability and waveform smoothness of the inverter. Delta EPS emergency power dedicated inverter must meet the application of most occasions in the EPS industry, and is the preferred dedicated inverter of EPS manufacturers.

2.2 Features of Delta EPS

(1) The auxiliary power supply and soft start circuit contactor of the inverter are all DC-powered, so direct DC power supply can be fully realized.

(2) Super strong hardware and software protection functions ensure the reliability of the inverter.

(3) It contains multiple modulation methods, so it can be used with a variety of transformers, thus ensuring that the output voltage waveform is closer to a sine wave.

(4) Delta EPS dedicated inverters are available in two specifications: AC380V and AC220V, with a power range from 0-220KW, which can meet the needs of customers in different occasions.

(5) The use of synchronization card ensures the same input and output phase.

2.3 Delta EPS dedicated inverter application design

(1) Electrical principle design. The principle of the EPS with AC and DC dual power supply is shown in Figure 1. The principle of the EPS with DC single power supply is shown in Figure 2.

(2) Definition of control terminals

Terminal number Terminal Function Description
FWD Forward operation - stop command
REV Reverse operation-stop command
MI1
Abnormal restart function
MI2
External abnormal function
24V Common terminal for digital control signals

DCM
Common terminal for digital control signals
RA Multi-function relay output contact normally open
RB Multi-function relay output contact normally closed
RC
Multi-function output contact common terminal
MO1
Multi-function output terminal (optical coupling)

2.4 Delta EPS inverter special parameter design

Special parameters Specific applications
Cancel PHL alarm fault Meets mixed load requirements; single phase, multi-phase.
Higher carrier frequency
The increase in carrier frequency meets the noise requirements of the system; in offline mode, the inverter working time is less than 120 minutes, and the carrier frequency can be required to reach the maximum
LU voltage level can be set by software Meets the needs of battery voltage fluctuations

LU alarm voltage recovery level can be set by software
Meets the need for rapid fault recovery
Output voltage is 3V (EPS software function)
The national standard requires that the output voltage of EPS should fluctuate within 5V when it is unloaded or fully loaded; the enterprise standard is 3V;
The startup time can reach 0.01S Meet the requirements of emergency response; also the basic point of emergency power supply
Current Limit Level When the load exceeds the overcurrent point of the inverter, the inverter will reduce the frequency and limit the voltage to ensure that the current does not exceed the overcurrent point of the inverter.
Power range diversification During the process, customers may need inverters of various power ranges and require the inverters to be from the same manufacturer.

Automatic torque compensation gain

Automatic torque compensation limit

The automatic slip compensation gain can automatically adjust the output voltage according to the load conditions to maintain the air gap magnetic field of the motor at the rated value to obtain the best operating condition.
Abnormal reactivation times (excluding oc, ocn, ocd, occ, ov, BB abnormalities) Factory setting value 00 When an abnormality occurs in the drive (excluding OC, OCN, OCD, OCC, OV, BB abnormalities) and the abnormality disappears automatically, this parameter allows the drive to automatically reset and operate with the parameter settings before the abnormality.
Abnormal reactivation times automatic reset time This parameter sets the automatic reset time for abnormal reactivation. If an abnormality occurs and reactivation is successful, and no abnormality occurs within the set time, the drive will reset the abnormality count record to zero.

3 Conclusion

Delta's EPS dedicated inverter truly realizes customized service. It is developed completely according to the technical characteristics of the EPS industry and meets the needs of EPS industry customers. Delta inverters have been well received by users for their strict quality management and high cost performance. Through Delta's strict quality management, excellent performance and strong technical support capabilities, customized service is truly realized.

Keywords:Inverter Reference address:EPS solution based on Delta inverter

Previous article:Solar low-pressure sodium lamp electronic ballast R&D solution
Next article:Low dropout linear regulator solution in switching power supply

Recommended ReadingLatest update time:2024-11-17 00:53

A brief discussion on the differences between UPS power supply and EPS power supply in terms of function and application
   EPS power supply is also called EPS, EPS emergency power supply, fire emergency power supply, full name Emergency Power Supply. EPS is mainly aimed at solving the primary load power supply equipment such as emergency lighting, accident lighting, fire fighting facilities, etc., and provides an emergency power supp
[Power Management]
Analysis of the key technologies of "double insurance" redundant EPS for L3 autonomous driving: redundancy strategy and safety mechanism
In the autonomous driving system, the steering system is one of the key components to ensure the normal driving of the vehicle. As a steering system widely used in modern cars, the electric power steering system (EPS) has become an ideal choice for autonomous driving systems with its advantages such as simple struct
[Embedded]
Analysis of the key technologies of
Latest Power Management Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号