How to correctly choose the installation point of electromagnetic flowmeter

Publisher:peon1989Latest update time:2016-12-15 Source: eefocus Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

How to correctly select the installation point of the electromagnetic flowmeter 
1. The electromagnetic flowmeter should select a straight pipe section filled with liquid, such as a vertical section of the pipeline (preferably flowing from bottom to top) or a horizontal pipe filled with liquid (preferably the lowest point in the entire pipeline). During the installation and measurement process, a non-full pipe situation must not occur;
2. The measurement position should be selected at a straight pipe section with a length greater than 5D upstream and 3D downstream;
3. The measurement point should be selected as far away as possible from pumps, valves and other equipment to avoid interference with the measurement;
4. The measurement point should be selected as far away as possible from high-power radio stations, strong magnetic field interference sources, etc. 


Special attention should be paid when choosing the installation location 

---------------------------------------------------------------------------------

· The axis of the measuring electrode must be approximately horizontal. 

· The measuring pipe must be completely filled with liquid.
· There must be a straight pipe section of at least 5xD (D is the inner diameter of the flowmeter) in front of the flowmeter and a straight pipe section of at least 3xD (D is the inner diameter of the flowmeter) in length behind it. To facilitate installation and disassembly, a pipe expansion joint can be installed behind the flowmeter. 

· The flow direction of the fluid is consistent with the arrow direction of the flowmeter;
· There must be a vacuum in the pipeline, which will damage the lining of the flowmeter, so special attention should be paid;
· There should be no strong electromagnetic field near the flowmeter;
· There should be ample space near the flowmeter for installation and maintenance;
· If the measuring pipeline vibrates, there should be fixed supports on both sides of the flowmeter;
· When measuring mixed liquids of different media, the distance between the mixing point and the flowmeter must be at least 30×D (D is the inner diameter of the flowmeter);
· In order to facilitate the cleaning and maintenance of the flowmeter in the future, a bypass pipeline should be installed, and a straight pipe section of 5D in front and 3D behind the flowmeter should be ensured. 

· When installing a flowmeter with a polytetrafluoroethylene liner, the bolts connecting the two flanges should be tightened evenly, otherwise the polytetrafluoroethylene liner is easily crushed. It is best to use a torque wrench. 

... 



​ 
​ 
​ 
​If the pipe drop exceeds 5m, install an exhaust valve downstream of the sensor. 
· The control valve and cut-off valve should be installed downstream of the sensor, not upstream of the sensor. 
· The sensor must not be installed at the inlet or outlet of the pump, but at the outlet of the pump. 
· The way to install the flow meter in the measuring well :

1. Inlet 2. Overflow pipe 3. Inlet grid 
4. Cleaning hole 5. Flow meter 6. Short pipe

7. Outlet 8. Discharge valve 9. Drain valve


Reference address:How to correctly choose the installation point of electromagnetic flowmeter

Previous article:How to debug the converter of electromagnetic flowmeter
Next article:How to correctly install and maintain electromagnetic flowmeter

Latest Test Measurement Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号