CX Lighting Control Panels - 16 and 24 Relays
CX COMMERCIAL LIGHTING CONTROL PANELS
PROJECT INFORMATION
Project Name
Catalog No.
Date
The Hubbell Controls CX Commercial Lighting Control Panels provide feature-rich
and cost-effective lighting control for maximum energy savings. The LCD User
interface is located in the door and utilized simple and intuitive scrolling menus
to program, check status or update the panel. The easy-to-use Pre-Programmed
Scenarios Menu makes project commissioning simple and fast.
The CX Panels can save up to 50% in labor and materials when used in place of
conventional time clock and contactor combinations. The use of the astronomical
clock instead of roof-mounted photocells increases cost savings, lowers
maintenance, and improves reliability.
PRODUCT FEATURES
•
•
•
•
•
•
•
•
•
•
•
•
•
Two Relay panel sizes – 16 and 24 relay spaces
Four types of relays – 20A/1P, N/O, 20A/2P, N/O, N/C (14K SSCR)
and 30A/1P latching (18K SCCR)
LCD user interface with keypad
365 day programming with 64 schedules
Astronomical and real time clock
20 Programmable dry contact inputs for 16 relay panel;
30 programmable dry contact inputs for 24 relay panel
Selectable pre-programmed scenarios
Programmable inputs accept low voltage switches, photocells,
or motion sensors
Two low voltage dry contact output relays on 16 relay panel;
three for 24 relay panel
Program uploads via removable SD memory card
Listed to UL916, UL924 and cUL
Five-year limited warranty
120-277 Vac
20”
24”
4”
General Specifications
Programming and configuration
Physical
Programmable via user interface mounted on door
Fully programmable by users with door closed and locked
NEMA 1 surface enclosure
Pre-drilled mounting holes for mounting to wall, KOs provided on top and bottom
16 and 24 relay enclosures with hinged locking door
120-277VAC Standard, 347/480VAC Optional
120 and 277VAC 20 Amp Single Pole Relays (14K SCCR)
120 and 277VAC 30 Amp Single Pole Relays (18K SCCR)
347VAC, 20A, IP Relay (14K SCCR)
208, 240, and 480VAC 20 Amp Double Pole Relays(14K SCCR)
Location: interior space
Operating temperature: 0° to 50°C (32° to 112°F)
Relative humidity (non-condensing): 10% to 90%
Listed to UL916, UL924 and cUL
Five-year limited
Electrical input
Relays
Operating environment
Certifications
Warranty
Ordering Information
CX
MODEL
CX
CX Lighting Control Panel
S
SPACES
16
16 Relay Spaces
24
24 Relay Spaces
INPUT VOLTAGE
2
120-277V Universal
3
347/480V
ENCLOSURE
S
NEMA 1 Surface
RELAY QUANTITY
00
No Relays - Spaces Only
16
16 Relays Installed
24
24 Relays Installed
SP
2N
3L
TN
TC
RELAY TYPE
Space Only
20A 1-Pole Electrically Held N.O. 120-277V 14KSCCR @ 277VAC
30A 1-Pole Latching 120-277-347V 18KSCCR @ 277VAC, 14KSCCR @ 347VAC
20A 2-Pole Electrically Held N.O. 480V 14KSCCR @ 480VAC
20A 2-Pole Electrically Held N.C. 480V 14KSCCR @ 480VAC
OPTIONS
M
Master Panel
S
Secondary Panel (Note 4)
NOTES:
1.
2-Pole relays take the same amount of space as 1-Pole relays.
2.
Installed relays must be all of the same type. Relay Type TC and TN not available in fully populate panels and must be ordered separately to be installed in the field.
See Relay Specification Sheet.
3.
“00” option has no relays, all must be installed in the field.
4.
Secondary panel includes (2) master/secondary panel interface cards.
9601 Dessau Road | Building One | Austin, Texas 78754 | 512-450-1100 | 512-450-1215 fax | www.hubbell-automation.com
3301A 2.4.2016