1-Phase Line Filters
www.schurter.com/PG84
AC Filter 2-Stage, Broad Band Attenuation
FMBB NEO
Quick connect terminals 6.3x0.8 mm
Case MF
Quick connect terminals 6.3x0.8 mm
Case 09
Bolt and n
Case MB
Description
- Chassis:
Screw-on mounting, from top
- Line filter in standard and medical version, 2 stages
- 3 designs: Design C, Design D, Design F
- Quick connect-, wired- or bolt terminals
- High symmetrical and asymmetrical attenuation in the frequency range
of 100kHz up to 300MHz
Characteristics
- Designed for current applications of 1 - 36 A
- Protection against interference voltage from the mains
Possible interferences generated in the equipment are strongly atte-
nuated
- Especially designed for industrial applications such as: Frequency Con-
verters, Stepper Motor Drives, UPS-Systems, Inverters
- Suitable for use in equipment according to IEC/UL 60950
Approvals
Other versions on request
- Version with wire connection
- VDE Certificate Number: 40030410
- UL File Number: E72928
References
Weblinks
Alternative: Standard version
pdf-datasheet, html-datasheet, General Product Information,
Approvals, CE declaration of conformity, RoHS, CHINA-RoHS, e-Shop,
SCHURTER-Stock-Check, Distributor-Stock-Check, Detailed request for
product
Technical Data
Ratings IEC
Ratings UL/CSA
Leakage Current
1 - 36 A @ Ta 40 °C / 250 VAC; 50 Hz
1 - 30 A @ Ta 40 °C / 125/250 VAC;
60 Hz
standard < 0.5 mA (250 V / 60 Hz)
medical (M5) < 5 µA resp. (M80) < 80
µA (250 V / 60 Hz)
1.7 kVDC between L-N
2.75 kVDC between L/N-PE
Test voltage (2 sec)
-25 °C to 100 °C
25/100/21 acc. to IEC 60068-1
from rear-side IP 20 IEC 60529
Suitable for appliances with protection
class I acc. to IEC 61140
Quick connect terminal 6.3 x 0.8 mm
Bolt and nut M4
Aluminum
Line Filter
Standard Version, IEC 60939, UL 1283
ed.5, CSA C22.2 no. 8
Technical Details
> 200'000 h acc. to MIL-HB-217 F
MTBF
Dielectric Strength
Allowable Operation Temp.
Climatic Category
Degree of Protection
Protection Class
Terminal
Material: Housing
Connectors
1