• Optional Remote I/O via Flex modules. Communication can be
via the DeviceNet communication platform or the Remote I/O
communication platform.
Available from 23-1200 Amperes.
Specifications
Approvals
C
UL
US
Standards
The ElectroGuard Safety Isolation System is used in place of a
disconnect switch for Lockout and Tagout (LOTO). It uses power
contactors and Remote Lockout Stations to accomplish LOTO.
Isolating the electrical energy usually involves calling an electrician to
turn “Off ” the main disconnecting means. The electrician would
then perform LOTO of the disconnecting means operating handle.
This same procedure is required to perform cleaning, maintenance,
setup, lubrication or adjustment. Machines or processes with
multiple access points may require operator/maintenance
intervention several times a shift (perhaps as often as 60 times per
shift).
To perform these activities, the operator/maintenance person may
be required to place part of his or her body into an area not accessed
during normal operation. This may cause serious or fatal injury if
LOTO procedures are not followed.
The ElectroGuard Safety Isolation System allows the machine
operator to safely and quickly accomplish LOTO with dramatically
reduced downtime.
Provides Energy Isolation
• Power isolation accomplished by means of contactors rather than
disconnect switches.
• Uses redundant, independent and self-monitoring circuits to
detect a system fault.
• Prevents accumulation of faults in order to maintain the integrity
of the safety system.
• Tamper-resistant design.
Convenient Remote Lockout Station
• Allows remote isolation of the electrical power to the machine or
process—machine operator simply turns “Off ” a Remote
Lockout Station.
• A light on the Remote Lockout Station indicates that the three-
phase power source to the machine or process has been isolated.
No Light Means No Entry.
• If a fault occurs in the Safety Isolation System, the “System
Isolated” light on the Remote Lockout Stations will not
illuminate.
• Easy Lockout/Tagout.
Certified by TUV to meet requirements of Category 4
• Certified by TUV to meet Category 4, the most stringent safety
category defined within International Standard EN 954-1/ISO
13849-1.
• Subjected by TUV to rigorous third party testing and verification
of the Failure Mode & Effect Analysis (FMEA).
Estimated Component Life
Remote Lockout Station
Power Contactors
(Isolation & Grounding)
Environmental
Storage Temperature
Operating Temperature
Relative Humidity,
Non condensing
Power Panel Construction
Listed Industrial Control Panel;
TUV Rheinland certified; CE marked
for all applicable directives
IEC/EN 60204-1; IEC/EN 60439-1;
Category 4 to International Standard
EN 954-1/ISO 13849-1; 98/37/EC
Machinery Directive; 89/336/EC EMC
Directive; 73/23/EC Low Voltage
Directive; Fulfils the function of an
energy isolating device in accordance
with the conditions set forth in the
FedOSHA letter of interpretation
pertaining to Section 1910.147(b);
Cal/OSHA 3314.
250,000 operations
23A - 85A: 2,000,000 operations
110A-1200A: 1,000,000 operations
-10°C...+60°C (14°F...140°F)
0°C...+40°C (32°F...104°F) (Ambient)
90% Relative Humidity
Tamper-resistant Control Module
23A-85A systems support up to 4
Remote Lockout Stations without an
Expansion Module
110A-1200A systems support up to 6
Remote Lockout Stations without an
Expansion Module
Control Module with viewing window
for visual check of status indicator lights
Top and bottom 25.4mm (1.0in)
conduit entry (removable plug in
bottom conduit hole)
Sealing provision for tamper-resistance
Operating handle accepts up to 3
padlocks
4 port—supports up to 4 lockout
stations
• allows the systems to
accommodate up to 24 Remote
Lockout Stations
10 port—supports up to 10 lockout
stations
• allows the systems to
accommodate up to 60 Remote
Lockout Stations
Window for viewing status indicator
lights; Sealed for tamper-resistance
Remote Lockout Stations
Safety Mats,
➊
Light Curtains,
➊
E-Stop Stations,
➊
Proximity Switches,
➊
Photo Switches
➊
+10%, -15% of the line voltage
Remote Lockout Station
Construction
Expansion Module
Construction
Safety Isolation Sys. Inputs
Standard Inputs from
Optional Inputs from
Rockwell Automation
Safety Products
System Operational Limits
➊
Use of any of these input devices will not meet Lockout/Tagout (LOTO)
requirements.
12-2
Safety Isolation System
ElectroGuard
Overview
Principle of Operation
Power Circuit
1IC
Incoming
3 Phase
Power
H1
X1
Disconnecting
Means/Branch
Circuit Protection
➊
H2
Trans.
X2
GC
Voltage
Decay
Relays
(VDR)
2IC
To Motor
Controllers
To Loads
After using the normal stopping
method of the machine or process,
the machine operator turns a
Remote Lockout Station handle
from the “On” to “Off ” position.
The station signals the isolation
contactors (1IC and 2IC) to drop
out and isolate the supply voltage
from the loads (see Control
Circuit).
When system residual voltage
decays to pre-determined levels,
the grounding contactor (GC) is
energized, connecting the load to
ground (see Power Circuit). The
grounding contactor (GC) is
electrically and mechanically
interlocked with the isolation
contactors (1IC and 2IC).
The “System Isolated” Light will
now illuminate on the Remote
Lockout Station to indicate the
system is isolated. The machine
operator then Locks-Out and
Tags-Out the station in the “Off ”
position.
Control Power
Grd
Control Circuit
Remote Lockout Station
Off
On
GC
1IC
GC
2IC
VDR
1IC
2IC
GC
Mechanically
Interlocked
1IC, 2IC,
&
GC are
mechanically
and electrically
interlocked
GC
1IC
2IC
System Isolated (*)
(*) = “On” when the Remote
Lockout Station switch is “Off”
➊
Available factory installed within the ElectroGuard as an option.
Optional Features
• Four (4) or ten (10) port Expansion Modules to permit additional Remote
Lockout Stations to be used (see page 12-16 for details).
• Pneumatic Isolation Module to isolate pneumatic energy (see page 12-15 for
details).
• Status communication to a remote PLC (see page 12-17 for details).
• Fusible disconnect switch (Bulletin 2032) or thermal-magnetic circuit breaker
(Bulletin 2033) to provide branch circuit protection.
Optional Pneumatic Isolation Module
12-3
Safety Isolation System
ElectroGuard
Non Combination Systems
+
Power Panel
3-Phase Max. Hp Rating (60Hz)
Ampere
Rating
(AC-3)
23
43
85
110
180
210
300
420
630
860
1200
Type 1 General
Purpose
Enclosure
2031-A0023A⊗
2031-A0043A⊗
2031-A0085A⊗
2031-A0110A⊗
2031-A0180A⊗
2031-A0210A⊗
2031-A0300A⊗
2031-A0420A⊗
2031*-A0630A⊗
2031*-A0860A⊗
2031*-A1200A⊗
One or More Remote Lockout Stations
(conduit hub not included)
Product Selection: For North America (see page 12-19 for Ordering Instructions)
Catalogue Number
➊
Type 12
Dust tight
Enclosure
2031-A0023J⊗
2031-A0043J⊗
2031-A0085J⊗
2031-A0110J⊗
2031-A0180J⊗
2031-A0210J⊗
2031-A0300J⊗
2031-A0420J⊗
2031*-A0630J⊗
2031*-A0860J⊗
2031*-A1200J⊗
200V
5
10
25
40
50
60
100
150
200
250
450
230V
7.5
15
30
40
60
75
125
175
250
300
450
460V
15
30
60
75
150
-
250
350
500
600
900
575V
15
30
60
100
150
200
300
400
600
700
900
Type 12 Motor
Control Centre
Type Enclosure
(with bussing)
2031-!0023J⊗
2031-!0043J⊗
2031-!0085J⊗
2031-!0110J⊗
2031-!0180J⊗
2031-!0210J⊗
2031-!0300J⊗
2031-!0420J⊗
2031-!0630J⊗
2031-!0860J⊗
2031-!1200J⊗
Type 4
Watertight
Painted Steel
Enclosure
2031-A0023F⊗
2031-A0043F⊗
2031-A0085F⊗
2031-A0110F⊗
2031-A0180F⊗
2031-A0210F⊗
2031-A0300F⊗
2031-A0420F⊗
2031*-A0630F⊗
2031*-A0860F⊗
2031*-A1200F⊗
Type 4X
Watertight
Stainless Steel
Enclosure
2031-A0023C⊗
2031-A0043C⊗
2031-A0085C⊗
2031-A0110C⊗
2031-A0180C⊗
2031-A0210C⊗
2031-A0300C⊗
2031-A0420C⊗
2031*-A0630C⊗
2031*-A0860C⊗
2031*-A1200C⊗
To order the Time Delay feature, add the following Catalogue String to the end of the Catalogue Number shown in the
table:
Factory set 30 second time delay feature:
-1TD
Example:
Catalogue Number
2031-A0180A⊗
becomes Catalogue Number
2031-A0180A⊗-1TD
to include the time delay feature.
* Input Power Feed Catalogue Number Code
The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below.
Example:
Catalogue Number
2031*-A0630J⊗
becomes Catalogue Number
2031T-A0630J⊗
for a “Top Feed” input power requirement.
Input Power Feed
Top Feed
Bottom Feed
Catalogue Number Code
T
B
Example:
Catalogue Number
2031-
!
0085J⊗
becomes Catalogue Number
2031-M0085J⊗
for “600A Line Side Incoming Bus and Outgoing Power Cables”
bussing designation.
Type of Bussing
➋
600A Line Side Incoming Bus and Outgoing Power Cables
1200A Line Side Incoming Bus and Outgoing Power Cables
Line Side Incoming Power Cables and 600A Load Side Outgoing Bus
Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus
⊗
Input Line Voltage Code
Catalogue Number Code
M
S
F
B
!
Bussing Designation
The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table below.
The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below.
Example:
Catalogue Number
2031-A0085J⊗
becomes Catalogue Number
2031-A0085JB
for a 480V 60Hz Input Line Voltage application.
Input Line Voltage
Voltage Code for Catalogue Number
208V 60Hz
H
240V 60Hz
A
480V 60Hz
B
600V 60Hz
C
➊
Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine
operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off”
position. Consult your local Rockwell Automation sales office for other time settings.
➋
Bus Type: Copper with tin plating. Consult factory for other types of bussing.
12-4
Safety Isolation System
ElectroGuard
Non Combination Systems
Product Selection: Remote Lockout Station
➊
“System Isolated”
Light Colour
White
Type 1 General
Purpose Enclosure
2030-RLSAW
Catalogue Number
Type 12 Dust tight
Type 4 Watertight Painted
Enclosure
Steel Enclosure
2030-RLSJW
2030-RLSFW
Type 4X Watertight Stainless
Steel Enclosure
2030-RLSCW
Product Selection: For Outside of North America (see page 12-19 for Ordering Instructions)
3-Phase Max. kW Rating (50Hz)
Ampere
Rating
(AC-3)
23
43
85
110
180
210
300
420
630
860
1200
230V
7.5
13
25
32
55
63
90
132
200
250
391
400V
11
22
45
55
90
110
160
220
355
500
710
500V
11
22
45
63
110
150
200
300
450
560
888
600V
11
22
45
100
160
200
300
425
500
600
1043
IP 30 Enclosure
2031-C0023P⊗
2031-C0043P⊗
2031-C0085P⊗
2031-C0110P⊗
2031-C0180P⊗
2031-C0210P⊗
2031-C0300P⊗
2031-C0420P⊗
2031*-C0630P⊗
2031*-C0860P⊗
2031*-C1200P⊗
Catalogue Number
➋
IP 54 Motor Control
Centre Type Enclosure
IP 54 Enclosure
(w/bussing)
2031-C0023H⊗
2031-C0043H⊗
2031-C0085H⊗
2031-C0110H⊗
2031-C0180H⊗
2031-C0210H⊗
2031-C0300H⊗
2031-C0420H⊗
2031*-C0630H⊗
2031*-C0860H⊗
2031*-C1200H⊗
2031-!0023H⊗
2031-!0043H⊗
2031-!0085H⊗
2031-!0110H⊗
2031-!0180H⊗
2031-!0210H⊗
2031-!0300H⊗
2031-!0420H⊗
2031-!0630H⊗
2031-!0860H⊗
2031-!1200H⊗
IP 65 Enclosure
2031-C0023W⊗
2031-C0043W⊗
2031-C0085W⊗
2031-C0110W⊗
2031-C0180W⊗
2031-C0210W⊗
2031-C0300W⊗
2031-C0420W⊗
2031*-C0630W⊗
2031*-C0860W⊗
2031*-C1200W⊗
To order the Time Delay feature, add the following Cat. String to the end of the Cat. No. shown in the table:
Factory set 30 second time delay feature:
-1TD
Example:
Catalogue Number
2031-C0180H⊗becomes
Catalogue Number
2031-C0180H⊗-1TD
to include the time delay feature.
* Input Power Feed Catalogue Number Code
The Catalogue Number as listed is incomplete. Select an Input Power Feed Code from the table below.
Example:
Catalogue Number
2031*-C0630H⊗
becomes Catalogue Number
2031T-C0630H⊗
for a “Top Feed” input power requirement.
Input Power Feed
Catalogue Number Code
Top Feed
T
Bottom Feed
B
Example:
Catalogue Number
2031-
!
0085H⊗
becomes Catalogue Number
2031-E0085H⊗
for “600A Line Side Incoming Bus and Outgoing Power Cables”
bussing designation.
Type of Bussing
➌
600A Line Side Incoming Bus and Outgoing Power Cables
1200A Line Side Incoming Bus and Outgoing Power Cables
Line Side Incoming Power Cables and 600A Load Side Outgoing Bus
Line Side Incoming Power Cables and 1200A Load Side Outgoing Bus
⊗
Input Line Voltage Code
Catalogue Number Code
E
D
H
R
!
Bussing Designation
The Catalogue Number as listed is incomplete. Select a Bussing Designation Code from the table.
The Catalogue Number as listed is incomplete. Select an Input Line Voltage Code from the table below.
Example:
Catalogue Number
2031-C0085P⊗
becomes Catalogue Number
2031-C0085PN
for a 380V 50Hz Input Line Voltage application.
Input Line Voltage
220V 50HZ
380-400V 50Hz
400-415V 50Hz
440V 50Hz 500V 50Hz
Voltage Code for Catalogue Number
A
N
G
B
M
550V 50Hz
C
Product Selection: Remote Lockout Station
➊
“System Isolated” Light Colour
Green
IP 30 Enclosure
2030-RLSPG
Catalogue Number
IP 54 Enclosure
2030-RLSHG
IP 65 Enclosure
2030-RLSWG
➊
Safety Isolation Systems rated up through 85A can support a maximum of four (4) Remote Lockout Stations (RLS).
Systems rated from 110A - 1200A can support a maximum of six (6) RLS. If additional RLS are required, order the optional Expansion Module(s) (see page 12-16).
➋
Optional Time Delay Feature. The Safety Isolation System may be ordered with a factory set time delay feature (30 seconds) in order to allow time for the machine
operator to shut-down drives or other equipment that requires a controlled stop, after the operating handle on a Remote Lockout Station has been moved to the “Off”
position. Consult your local Rockwell Automation sales office for other time settings.
➌
Bus Type: Copper with tin plating. Consult factory for other types of bussing.
After the basic electrochemical performance test, the 18650 lithium battery can be subjected to in-depth performance research to select batteries with good consistency and low impedance for various pe...
[size=4]This is the structural block diagram of the dead zone circuit[/size] [size=4] [/size] [size=4]The sampling signal sent by the Hall sensor is input through the pin header JP2[/size] [size=4] [/...
High-speed PCB design rules and techniques analysis : https://training.eeworld.com.cn/course/6004[Course Background]:What are rules? How much should be controlled between various devices? How much sho...
As we all know, Win95 has the function of setting passwords, but I wonder if you have noticed that when returning to Win95 from the "suspend" state, the system does not require us to enter a password....
In modern automotive embedded systems, highly secure data storage is essential, especially in the face of increasingly sophisticated cyberattacks. This article walks designers through the steps to pr...[Details]
According to domestic digital bloggers, the development of Huawei's P50 series is going smoothly, and the release date has been determined and will not be postponed. The blogger said that the gamep...[Details]
Sensors are the "eyes" and "ears" of processors, coprocessors, and computing modules. They come in all shapes, forms, and functions, and are deployed in an increasing number of applications. From edg...[Details]
1 Background
The asphalt workshop of the third refining department of Cangzhou Refinery currently has a set of road asphalt equipment with an annual output of 100,000 tons. The workshop is...[Details]
According to the 2021 "Asian Supply Chain Top 100 Market Value Survey Report" released by DIGITIMES Asia, the semiconductor industry and the automotive manufacturing industry account for more than ha...[Details]
Recently, Sichuan Tianfu Energy Storage Technology Co., Ltd. provided customers with a batch of carefully manufactured 128kW vanadium battery super stacks and efficient 500kW power modules. After T...[Details]
By Guillaume Crinon, Global IoT Strategy Manager, Avnet Driven by industries such as discrete manufacturing, transportation, logistics, and utilities, the global IoT market will reach $3.9 trilli...[Details]
Usually AVR chips include flash, eeprom, fuse, lockbits, user signature and other non-volatile contents that need to be burned into the chip during programming. Among them, the fuse part can only be ...[Details]
Actual
circuits
are composed of non-ideal components, and many unexpected situations may be encountered in the design. When debugging the ordinary full-bridge
power supply
shown in Figure 1
...[Details]
During the application of high-power LED products and devices, heat dissipation, electrostatic protection and welding have a great impact on their characteristics, which need to be paid great attenti...[Details]
In recent years, with the rise of artificial intelligence, the development of self-driving cars has also been very rapid. Not only have technology and Internet companies such as Google and Baidu ente...[Details]
This article introduces the main features of AD5421, functional block diagram, HART modem connection diagram and application diagram.
The AD5421 is a complete, loop powered, digital to ...[Details]
Control transfer instructions are used to control the flow of the program. The range of control is the program memory range. The MCS-51 series of microcontrollers has a relatively rich range of c...[Details]
0 Introduction
A beacon is the abbreviation of a navigation mark. It is a mark indicating the direction, boundary and obstacles of a waterway, and provides basic guarantee for the safe navigati...[Details]
Recently, the external lines of the Yongji Guoyun Microcontroller 100MW independent hybrid energy storage project, the country's first 100MW hybrid energy storage and frequency regulation project u...[Details]