General Purpose US
US Fuses
Fuses
General Purpose
American Power Fuses
AMP-TRAP 2000
®
ATQR (Class CC TD)
Take control of fault currents headed
for your control transformer
ATQR small-dimension fuses feature time delay
characteristics ideally suited for the high inrush
currents of control transformers, solenoids, and similar
inductive loads. The newest member of our Amp-trap
2000® family of fuses - ATQR fuses
provide superior protection for the branch circuits of elec-
trical distribution systems.
Features /Benefits
• Time delay for control transformer inrush loads without
nuisance opening
• Highly current limiting for low peak let-thru current
• Rejection-style design prevents replacement errors
(when used with recommended fuse blocks)
• High-visibility orange label ensures instant recognition,
and simplifies replacement
• Metal-embossed date and catalog number for
traceability and lasting identification
• Fiberglass body provides dimensional stability in harsh
industrial settings
• High-grade silica filler ensures fast arc quenching and
high current limitation
Applications
•
•
•
•
Control Transformers
Solenoids
Inductive Loads
Lighting, Heating and
General-purpose Loads
Approvals
• UL Listed to Standard 248-4
•
CSA Certified to Standard
C22.2 No. 248.4
Ratings
AC:
1/10 to 30A 600VAC, 200kA I.R.
Highlights
• Time Delay
• Best Choice for Small Transformer Protection
• Most Current-Limiting
GPUS
21
12/04
General Purpose US Fuses
General Purpose US Fuses
American Power Fuses
AMP-TRAP 2000
®
ATQR (Class CC TD)
Standard Fuse Ampere Ratings, Reference Numbers
Ampere
Rating
Catalog
Number
Reference
Number
Ampere
Rating
Catalog
Number
Reference
Number
1/10
1/8
15/100
3/16
2/10
1/4
3/10
4/10
1/2
6/10
3/4
8/10
1
1-1/8
1-1/4
1-4/10
1-1/2
1-6/10
1-8/10
2
2-1/4
2-1/2
ATQR1/10
ATQR1/8
ATQR15/100
ATQR3/16
ATQR2/10
ATQR1/4
ATQR3/10
ATQR4/10
ATQR1/2
ATQR6/10
ATQR3/4
ATQR8/10
ATQR1
ATQR1-1/8
ATQR1-1/4
ATQR1-4/10
ATQR1-1/2
ATQR1-6/10
ATQR1-8/10
ATQR2
ATQR2-1/4
ATQR2-1/2
E201921
A212175
S223507
J222556
Q216766
V211664
V219875
D211143
C211142
V213711
A223077
L215750
F218827
H222555
T219874
Z223076
T219345
E200863
R201403
D214731
K215749
G215240
2-8/10
3
3-2/10
3-1/2
4
4-1/2
5
5-6/10
6
6-1/4
7
7-1/2
8
9
10
12
15
17-1/2
20
25
30
ATQR2-8/10
ATQR3
ATQR3-2/10
ATQR3-1/2
ATQR4
ATQR4-1/2
ATQR5
ATQR5-6/10
ATQR6
ATQR6-1/4
ATQR7
ATQR7-1/2
ATQR8
ATQR9
ATQR10
ATQR12
ATQR15
ATQR17-1/2
ATQR20
ATQR25
ATQR30
Q216260
T218310
V219346
G218828
S201404
F201922
W211665
B212176
T212698
D213213
B214223
E214732
H215241
R216261
S212697
C213212
T213710
A214222
D217284
H217794
F200864
Recommended ATQR Class CC Primary
Fuses For Single Phase Control Transformers
Trans
Primary
VA
Volts
Fla
600
0.04
480
0.05
25
240
0.10
208
0.12
120
0.21
600
0.08
480
0.10
50
240
0.21
208
0.24
120
0.42
600
0.13
480
0.16
75
240
0.31
208
0.36
120
0.63
600
0.17
480
0.21
100
240
0.42
208
0.48
120
0.83
600
0.25
480
0.31
150
240
0.63
208
0.72
120
1.25
600
0.33
480
0.42
200
240
0.83
208
0.96
120
1.67
600
0.42
480
0.52
250
240
1.04
208
1.2
120
2.08
12/04
ATQR
AMPS
1/10
1/10
2/10
1/4
4/10
1/4
1/4
4/10
1/2
6/10
1/4
3/10
1/2
3/4
1
3/10
4/10
6/10
1
1-1/2
1/2
1/2
1
1-1/2
2-1/2
1/2
6/10
1-1/2
2
3
6/10
1-1/8
2
3
4*
* Secondary protection is required for these ratings.
+ Fuse will withstand 30 x FLA for .01 second
++ Fuse will withstand 25 x FLA for .01 second
Trans
Primary
VA
Volts
Fla
0.50
600
0.63
480
1.25
300
240
1.44
208
2.5
120
0.83
600
1.04
480
2.08
500
240
2.40
208
4.17
120
1.25
600
1.56
480
3.13
750
240
3.61
208
6.25
120
1.67
600
2.08
480
1000
4.16
240
4.81
208
8.33
120
2.50
600
3.13
480
1500
6.25
240
7.21
208
12.5
120
3.33
600
2000
480
4.17
240
8.33
208
9.62
600
5.00
3000
480
6.25
240
12.5
5000
600
8.33
480
10.4
ATQR
AMPS
1-1/8
1-1/2
2-1/2
3
5*
1-1/2
2
4*
6*
10*
2-1/2
3
7*
8*
15*
3
4*
10*
12*
20*
5*
7*
10
20*
25*
8*
10*
20++*
20++*
12+*
15+*
30++*
20++*
25+*
GPUS
22
General Purpose US
US Fuses
Fuses
General Purpose
American Power Fuses
AMP-TRAP 2000
®
ATQR (Class CC TD)
Recommended Fuse Blocks for Class CC Fuses
Catalog Number
Number
of
Poles
Ultrasafe
Indicating
Fuse Holder
Screw
with Double
Quick Connects
Pressure Plate
with Double
Quick Connects
Copper Box
Connector
ADDER
1
2
3
USCC1I
USCC2I
USCC3I
30310R
30311R
30312R
30313R
30320R
30321R
30322R
30323R
30350R
30351R
30352R
30353R
Reference Number
Number
of
Poles
ADDER
1
Ultrasafe
Indicating
Fuse Holder
X213943
Screw
with Double
Quick Connects
W204857
R212397
Pressure Plate
with Double
Quick Connects
Z217510
M218534
Copper Box
Connector
N213429
G213929
2
3
D217008
Y218038
Z212910
M213428
Y219579
B222779
V214447
X214955
Primary fuses - If primary FLA is less than 2 amps, fuse may be 300%
max. (500% for motor control). If primary FLA exceeds 2 amps but is
less than 9 amps, fuse may not exceed 167% of primary FLA unless
secondary protection is used, when it may be increased to 250%.
Fuse sizes shown are based on approx. 40 x FLA for .01 sec.
Dimensions
GPUS
23
12/04
General Purpose US Fuses
General Purpose US Fuses
American Power Fuses
AMP-TRAP 2000
®
ATQR (Class CC TD)
ATQR 1/8 to 30
MELTING TIME – CURRENT DATA, 600V FUSES
TIME IN SECONDS
Peak Let-Thru Current Data – ATQR 1/8 to 30, 600 Volts AC
MAX. INSTANTANEOUS PEAK LET-THRU CURRENT
AVAILABLE CURRENT IN RMS SYM. AMPERES
12/04
GPUS
24
CURRENT IN AMPERES