Technical Data 1161
Effective August 2018
Supersedes April 2017
BUSSMANN
SERIES
CUBEFuse™ Compact Circuit Protector Base
(cat. no. CCP2B)
Features
2011/65/EU
•
Uses finger-safe, current-limiting Class CF
CUBEFuse with Class J performance available
in time-delay or fast-acting versions from 1 to
100 amps
Patented amp rating rejection feature helps
prevent overfusing
High 200 kA short-circuit current rating
Disconnect rated to provide a means for load
isolation
2- and 3-pole versions straight voltage rated at
600 Vac
Up to 125 Vdc ratings
UL 98 Listed for branch circuit disconnect
1-, 2- and 3-pole versions are horsepower rated
UL and cULus Listed
Open fuse indication lamp per pole speeds
troubleshooting
Additional open fuse indication can be provided
by using the time-delay indicating CUBEFuse in
ratings from 6 to 100 amps
Built-in switch/fuse interlock prevents removing
or installing a fuse while energized
Permanent lockout/tagout and lock-on provision
using a 1/4” lock
•
•
•
•
•
•
•
•
•
•
•
•
Description
The revolutionary Bussmann™ series Compact
Circuit Protector Base (CCP2B) with CUBEFuse™
is a UL
®
98 horsepower rated fused branch circuit
disconnect. Primarily used in the Bussmann series
Quik-Spec™ Coordination Panelboard, the CCP2B
with CUBEFuse simplifies selective coordination
for code compliance and features a lockout/tagout
feature for isolating individual branch circuit loads
to promote safe work practices.
Technical Data
1161
Effective August 2018
CUBEFuse Compact Circuit Protector Base (CCP2B)
Specifications:
Switch amp ratings and rejection breaks
•
15, 20, 30, 40, 50, 60, 70, 90 and 100 A
Poles
•
1-, 2- and 3-poles
Volts
•
•
•
347 Vac (1-pole switches)
600 Vac (2- and 3-pole switches)
125 Vdc*
1-Pole
CCP2B-1-_CF
2-Pole
CCP2B-2-_CF
3-pole
CCP2B-3-_CF
* Switch amp rating and installed fuse amp rating dependent, see catalog number
table for details.
Agency information
•
•
UL 98 Listed, Guide WHTY, File E302370
cULus to Canadian Standard 22.2 No. 4, Guide WHTY7
,
File E302370
RoHS compliant
CE
Bolt-mounted design fits into Quik-Spec Coordination Panelboard
bus
#10-32 UNC hex flange Phillips screw; 2.8 N•m (25 lb-in)
See conductor table for details
Lineside bolt-on
bus connector
•
•
Lineside bolt-on bus connector and torque
•
Switch ON and OFF
symbols
•
Loadside box lug terminal conductor data
•
Lockout/tagout provision
Loadside fork terminal
•
Max. 30 A suitable for use with:
•
10-24 screw for switches up to 60 A
•
Switch handle
Local open fuse
indication light
1/4-28 screw for switches from 70 to 100 A
Lockout/tagout
•
1/4” lock
CUBEFuse base
Local open fuse indication light
•
Light illumination requires closed circuit and minimum 90 volts
Carton quantity and shipping weight
Item
up to 60 amp switches
70 to 100 amp switches
Poles
6
6
lbs (kg)
1.7 (0.77)
2.6 (1.18)
Environmental data
Storage and operating temperature -20°C to 75°C**
** For fuse performance under or above 25°C, consult fuse performance derating
charts.
Loadside
box lug
terminal
Loadside
fork
terminal
Available Bussmann series fuses
UL fuse
class
Type/description
Volts
Data sheet no.
Indicating time-delay, Low-
Peak™ CUBEFuse (6-100 A)
600 Vac/
9000
300 Vdc
Non-indicating time-delay,
Low-Peak CUBEFuse (1-100 A)
Non-indicating fast-acting
600 Vac/dc 2147
CUBEFuse (1-100 A)
CF
2
Eaton.com/bussmannseries
CUBEFuse Compact Circuit Protector Base (CCP2B)
Technical Data
1161
Effective August 2018
Catalog numbers and ratings
Catalog
numbers
CCP2B-1-15CF
CCP2B-2-15CF
CCP2B-3-15CF
CCP2B-1-20CF
CCP2B-2-20CF
CCP2B-3-20CF
CCP2B-1-30CF
CCP2B-2-30CF
CCP2B-3-30CF
CCP2B-1-40CF
CCP2B-2-40CF
CCP2B-3-40CF
CCP2B-1-50CF
CCP2B-2-50CF
CCP2B-3-50CF
CCP2B-1-60CF
CCP2B-2-60CF
CCP2B-3-60CF
CCP2B-1-70CF
CCP2B-2-70CF
CCP2B-3-70CF
CCP2B-1-90CF
CCP2B-2-90CF
CCP2B-3-90CF
CCP2B-1-100CF
CCP2B-2-100CF
CCP2B-3-100CF
†
††
†††
††††
*
**
Poles
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
Voltage
ratings
347 Vac,
125 Vdc
600 Vac,
125 Vdc
600 Vac
347 Vac,
125 Vdc
600 Vac,
125 Vdc
600 Vac
347 Vac,
125 Vdc
600 Vac,
125 Vdc
600 Vac
347 Vac,
125 Vdc
600 Vac,
125 Vdc
600 Vac
347 Vac,
125 Vdc*
600 Vac,
125 Vdc*
600 Vac
347 Vac,
125 Vdc*
600 Vac,
125 Vdc*
600 Vac
347 Vac,
125 Vdc
600 Vac,
125 Vdc
600 Vac
347 Vac,
125 Vdc**
600 Vac,
125 Vdc**
600 Vac
347 Vac,
125 Vdc**
600 Vac,
125 Vdc**
600 Vac
Accepts
CUBEFuse
amp range
Typical installed fuse amp range
Time-delay
Time-delay
Fast-acting
non-indicating
indicating†
non-indicating††
TCF1RN,
TCF3RN,
TCF6RN,
TCF10RN,
TCF15RN
TCF6,
TCF10,
TCF15
FCF1RN,
FCF3RN,
FCF6RN,
FCF10RN,
FCF15RN
Max.
fuse
amp†††
SCCR
Hp ratings
(Vac)††††
0.5 Hp @ 120 V
1 to 15
15
1.5 Hp @ 240 V
3 Hp @ 240 V
5 Hp @ 480 V
7 Hp @ 600 V
.5
0.75 Hp @ 120 V
1 to 20
TCF17-1/2RN,
TCF20RN
TCF17-1/2, TCF20
FCF20RN
20
2 Hp @ 240 V
3 Hp @ 240 V
7 Hp @ 480 V
.5
10 Hp @ 600 V
1.5 Hp @ 120 V
1 to 30
TCF25RN,
TCF30RN
TCF25,
TCF30
FCF25RN,
FCF30RN
30
3 Hp @ 240 V
5 Hp @ 240 V
15 Hp @ 480 V
10 Hp @ 600 V
2.0 Hp @ 120 V
1 to 40
TCF35RN,
TCF40RN
TCF35,
TCF40
FCF35RN,
FCF40RN
40
3 Hp @ 240 V
7 Hp @ 240 V
.5
20 Hp @ 480 V
10 Hp @ 600 V
3.0 Hp @ 120 V
200 kA AC
100 kA DC
1 to 50
TCF45RN,
TCF50RN
TCF45,
TCF50
FCF45RN,
FCF50RN
50
5 Hp @ 240 V
7 Hp @ 240 V
.5
20 Hp @ 480 V
10 Hp @ 600 V
3.0 Hp @ 120 V
1 to 60
TCF60RN
TCF60
FCF60RN
60
7 Hp @ 240 V
.5
7 Hp @ 240 V
.5
20 Hp @ 480 V
10 Hp @ 600 V
3.0 Hp @ 120 V
1 to 70
TCF70RN
TCF70
FCF70RN
70
7 Hp @ 240 V
.5
15 Hp @ 240 V
30 Hp @ 480 V
40 Hp @ 600 V
5.0 Hp @ 120 V
1 to 90
TCF90RN
TCF90
FCF80RN,
FCF90RN
90
10 Hp @ 240 V
20 Hp @ 240 V
50 Hp @ 480 V
40 Hp @ 600 V
5.0 Hp @ 120 V
1 to 100
TCF100RN
TCF100
FCF100RN
100
10 Hp @ 240 V
20 Hp @ 240 V
50 Hp @ 480 V
40 Hp @ 600 V
1 and 3 A indicating CUBEFuse not available. Correct fit with CCP2B disconnect requires indicating CUBEFuse with date code R38 or later.
Not for use with motors.
Any amp rating less than or equal to the switch max fuse rating may be installed. E.g., TCF15 can be installed in the CCP2B-1-20CF
.
Indicating or non-indicating time-delay CUBEFuse only.
125 Vdc for installed fuse amp ratings up to 40 A. 24 Vdc for installed fuse amp ratings from 45 to 60 A.
125 Vdc for installed fuse amp ratings up to 80 A, 24 Vdc for installed fuse amp ratings from 90 to 100 A.
Eaton.com/bussmannseries
3
Technical Data
1161
Effective August 2018
CUBEFuse Compact Circuit Protector Base (CCP2B)
Box lug conductor data
Wire type
AWG range
15 to 60 A switches
4-6
8-18
6-8
10-18
10-18
4-18
6-18
4-18
6-18
70 to 100 A switches
12-18
10
8
4-6
1-3
3-12
12-18
10
1-8
75°C Cu
10-18
6-8
10-18
10-18
8-18
1-6
3-10
8-18
1-6
6-18
75°C Cu
Class
Stranded, Class B to K
Stranded, Class B/C
Stranded, Class K
Stranded, Class B to K
Solid
Stranded, UL ferrule, Class B/C
Stranded, UL ferrule, Class K
Quantity
Single
Dual
Single/dual
Single
Twin
†
Single
Twin
†
Torque N•m (lb-in)
3.95 (35)
2.26 (20)
3.39 (30)
2.26 (20)
2.26 (20)
3.39 (30)
2.82 (25)
2.26
2.82
4.52
5.08
6.21
3.95
2.26
3.95
4.52
2.26
2.82
2.26
2.26
2.26
3.39
5.08
2.26
3.39
2.26
(20)
(25)
(40
(45)
(55)
(35)
(20)
(35)
(40)
(20)
(25)
(20)
(20)
(20)
(30)
(45)
(20)
(30)
(20)
Stranded, Class B to K
Single
Stranded, Class B to K
Dual
Single
Stranded, UL ferrule, Class B/C
Twin†
Solid
Class K
Single
Dual
Single
Dual
Class K, UL ferrule
Single
Twin
† Two stranded conductors placed in one UL Listed twin ferrule.
4
Eaton.com/bussmannseries
CUBEFuse Compact Circuit Protector Base (CCP2B)
Technical Data
1161
Effective August 2018
Dimensions — in (mm)
3.0
(76)
2.0
(51)
1.0
(25)
0.5
(13)
Ø 0.2
(Ø 5.1)
2.7
(69)
3.9
(99)
15-60 A switches
2.9
(73)
3.0
(76)
Ø 0.2
(Ø 5.1)
2.0
(51)
1.0
(25)
0.54
(14)
0.03
(0.8)
2.7
(70)
5.3
(133)
70-100 A switches
3.4
(86)
For details on the CCP2B and its use in the Quik-Spec Coordination Panelboard, see data sheet no. 1160.
Eaton.com/bussmannseries
5