violet, rose and aqua. The colored jacket allows for easy
visual identification of the cables. The standard jacket
color will be determined by the dominant fiber type in
the cable and will use the standard part numbers shown
here. Contact Customer Care at 1-800-743-2675 to order
other color options.
Standards
Approval and Listings
National Electrical Code
®
(NEC
®
) OFNP, CSA FT-6,
ICEA S-83-596
NFPA 262 (for plenum, riser
and general building appli-
cations)
Flame Resistance
Ripcord
Flame-Retardant
Outer Jacket
Dielectric Central
Element
Dielectric Strength
Members
Tight-Buffered
Fiber
Flame-Retardant
Subunit Jacket
Fan-Out Plenum Cables, 4 Fibers
| Photo PIM1063
Fan-Out Plenum Cables, 4 Fibers
| Photo PIM1961
Family Spec Sheet 0026_NAFTA_AEN
Page 1 | Revision date 2014-02-17
Fan-Out Plenum Cables, 2-24 Fibers
Specifications
Temperature Range
Storage
Installation
Operation
-40 °C to 70 °C (-40 °F to 158 °F)
0 °C to 60 °C (32 °F to 140 °F)
0 °C to 70 °C (32 °F to 158 °F)
*
Note: Corning recommends storing cable in a proper temperature environment prior to installation to allow the cable temperature to meet installation tempera-
ture range specifications for best installation results.
Mechanical Characteristics Cable
Fiber
Count
Central Element
Nominal
Min. Bend
Min. Bend
Outer Diame- Radius Instal- Radius
ter
lation
Operation
8.9 mm
(0.4 in)
10.9 mm
(0.4 in)
12.2 mm
(0.5 in)
5.2 mm
(0.2 in)
6 mm
(0.2 in)
7.1 mm
(0.3 in)
8.1 mm
(0.3 in)
10.5 mm
(0.4 in)
12.1 mm
(0.5 in)
14.2 mm
(0.6 in)
5.8 mm
(0.2 in)
6.8 mm
(0.3 in)
134 mm
(5.3 in)
164 mm
(6.3 in)
183 mm
(7.2 in)
78 mm
(3.1 in)
90 mm
(3.6 in)
106 mm
(4.1 in)
122 mm
(4.8 in)
158 mm
(6.2 in)
182 mm
(7.2 in)
213 mm
(8.4 in)
87 mm
(3.5 in)
102 mm
(4.0 in)
89 mm
(3.5 in)
109 mm
(4.3 in)
122 mm
(4.8 in)
52 mm
(2.1 in)
60 mm
(2.4 in)
71 mm
(2.8 in)
81 mm
(3.1 in)
105 mm
(4.1 in)
121 mm
(4.8 in)
142 mm
(5.6 in)
58 mm
(2.3 in)
68 mm
(2.7 in)
Weight
Product Type
1.65 mm Subunits, Dual-Layer
12
16
24
Yarn
GRP
Jacketed GRP
82 kg/km
(55 lb/1000 ft)
109 kg/km
(73 lb/1000 ft)
152 kg/km
(102 lb/1000 ft)
28 kg/km
(19 lb/1000 ft)
37 kg/km
(25 lb/1000 ft)
53 kg/km
(36 lb/1000 ft)
61 kg/km
(41 lb/1000 ft)
99 kg/km
(67 lb/1000 ft)
141 kg/km
(95 lb/1000 ft)
211 kg/km
(142 lb/1000 ft)
33 kg/km
(22 lb/1000 ft)
47 kg/km
(32 lb/1000 ft)
Distribution
Distribution
Distribution
1.65 mm Subunits, Single-Layer
2
4
6
8
Yarn
Yarn
GRP
Jacketed GRP
Distribution
Distribution
Distribution
Distribution
2.0 mm Subunits, Dual-Layer
12
16
24
GRP
GRP
Jacketed GRP
Distribution
Distribution
Distribution
2.0 mm Subunits, Single-Layer
2
4
Yarn
GRP
Distribution
Distribution
Family Spec Sheet 0026_NAFTA_AEN
Page 2 | Revision date 2014-02-17
Fan-Out Plenum Cables, 2-24 Fibers
Fiber
Count
4
6
8
Central Element
Nominal
Min. Bend
Min. Bend
Outer Diame- Radius Instal- Radius
ter
lation
Operation
6.8 mm
(0.3 in)
8.3 mm
(0.3 in)
8.8 mm
(0.4 in)
13.5 mm
(0.5 in)
15.4 mm
(0.6 in)
19.2 mm
(0.8 in)
7.7 mm
(0.3 in)
8.6 mm
(0.4 in)
10.4 mm
(0.4 in)
12.3 mm
(0.5 in)
125 mm
(4.9 in)
132 mm
(5.2 in)
203 mm
(8.0 in)
231 mm
(9.1 in)
288 mm
(11.3 in)
116 mm
(4.6 in)
129 mm
(5.1 in)
156 mm
(6.2 in)
185 mm
(7.3 in)
68 mm
(2.7 in)
83 mm
(3.3 in)
88 mm
(3.5 in)
135 mm
(5.3 in)
154 mm
(6.1 in)
192 mm
(7.6 in)
77 mm
(3.0 in)
86 mm
(3.4 in)
104 mm
(4.1 in)
123 mm
(4.8 in)
Weight
Product Type
GRP
GRP
Jacketed GRP
47 kg/km
(32 lb/1000 ft)
72 kg/km
(48 lb/1000 ft)
88 kg/km
(59 lb/1000 ft)
152 kg/km
(102 lb/1000 ft)
215 kg/km
(144 lb/1000 ft)
336 kg/km
(226 lb/1000 ft)
48 kg/km
(33 lb/1000 ft)
69 kg/km
(47 lb/1000 ft)
105 kg/km
(71 lb/1000 ft)
146 kg/km
(98 lb/1000 ft)
Distribution
Distribution
Distribution
2.9 mm Subunits, Dual-Layer
12
16
24
GRP
GRP
Jacketed GRP
Distribution
Distribution
Distribution
2.9 mm Subunits, Single-Layer
2
4
6
8
Yarn
GRP
Jacketed GRP
Jacketed GRP
Distribution
Distribution
Distribution
Distribution
Chemical Characteristics
RoHS
Free of hazardous substances according to RoHS 2002/95/
EG
Family Spec Sheet 0026_NAFTA_AEN
Page 3 | Revision date 2014-02-17
Fan-Out Plenum Cables, 2-24 Fibers
Transmission Performance
Fiber Type
Fiber Core Diameter (µm)
Fiber Category
Fiber Code
Performance Option Code
Wavelengths (nm)
Maximum Attenuation (dB/km)
Min. Overfilled Launch (OFL)
Bandwidth (MHz*km)
Minimum Effective Modal
Bandwidth (EMB) (MHz*km)
Serial 1 Gigabit Ethernet (m)
Serial 10 Gigabit Ethernet (m)
Induced Attenuation @ 7.5 mm
Radius (dB)
Multimode
62.5
OM1
K
30
850 / 1300
3.4 / 1.0
200 / 500
220 / -
300 / 550
33 / -
Multimode
50
OM2
T
31
850 / 1300
2.8 / 1.0
700 / 500
950 / -
750 / 600
150 / -
Multimode
50
OM3
T
80
850 / 1300
2.8 / 1.0
1500 / 500
2000 / -
1000 / 600
300 / -
< 0.2 up to
80
Multimode
50
OM4
T
90
850 / 1300
2.8 / 1.0
3500 / 500
4700 / -
1100 / 600
550 / -
Multimode
50
OM4
Extended
Distance
T
91
850 / 1300
2.8 / 1.0
3500 / 500
5350 / -
1100 / 600
600 / -
5000 / - / -
10000 / - /
40000
Single-mode
8.2
OS2
E
31
1310 / 1383
/ 1550
0.65 / 0.65 /
0.50
*
Assumes 1.0 dB maximum total connector/splice loss.
*
Assumes 0.7 dB maximum total connector/splice loss.
*
Meets 0.75 ns optical skew when used in all Corning Plug and Play™/Pretium EDGE
®
systems solutions.
*
ITU-T G.652 D compliant.
Notes:
1)
Improved attenuation and bandwidth options available.
2)
Bend-insensitive single-mode fibers available on request.
3)
Contact a Corning Customer Care Representative for additional information.
4)
50 µm multimode fiber macrobend loss ≤ 0.2 dB at 850 nm for two turns around 7.5 mm radius mandrel.
Family Spec Sheet 0026_NAFTA_AEN
Page 4 | Revision date 2014-02-17
Fan-Out Plenum Cables, 2-24 Fibers
Ordering Information |
Note: Contact Customer Care at 1-800-743-2675 for other options.
Corning Cable Systems LLC • PO Box 489 • Hickory, NC 28603-0489 USA