V-EA-Series - UL508 Manual Motor Controller -
2 pole Z-Trip
UL508 Listed
E137938
Standard Pack:
6
Weight:
0.3A - 32A
1.8kg (3.97 lb.)
40A - 63A
1.98kg (4.37 lb.)
Two Pole
35 mm
(1.38 in.)
93.3 mm
(3.67 in.)
Minutes
74.7 mm
(2.94 in.)
35 mm
(1.38 in.)
Rated
Current
0.3A
0.5A
0.75A
0.8A
1.0A
1.6A
2.0A
2.5A
3.0A
3.5A
4.0A
5.0A
6.0A
8.0A
10A
12A
13A
15A
16A
20A
25A
30A
32A
40A
50A
Type/
Cat. No.
2Z03UM
2Z05UM
2Z075UM
NA
2Z1UM
2Z1.6UM
2Z2UM
2Z2.5UM
2Z3UM
2Z3.5UM
2Z4UM
2Z5UM
2Z6UM
2Z8UM
2Z10UM
2Z12UM
2Z13UM
2Z15UM
2Z16UM
2Z20UM
2Z25UM
2Z30UM
2Z32UM
2Z40UM
2Z50UM
Approvals
V-EA-Z Trip
0.3A Through 10A Rated Current
1.05-1.35xI
N
60
40
Minutes
10
4
1
40
20
10
4
1
0.4
10
-1
4x10
-2
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
Seconds
Tripping time t
10
-2
4x10
-3
10
-3
1
2
3
4 5 6 8 10
20
40
100
Multiple of Rated Current
V-EA-Z Trip
12A Through 50A Rated Current
1.05-1.35xI
N
60
40
10
4
1
Thermal Overload
“Must Trip” < 1 hr = 135% RC
“Must Not Trip” > 1 hr = 105% RC
Voltage Rating
Short Circuit Withstand Rating
(UL/CSA - Ratings)
Group Short Circuit Withstand Rating
(UL/CSA - Ratings)
Interrupting Capacity (VDE - Ratings)
Calibration Temperature
Operating Temperature
Storage Temperature
Terminal Size Acceptability
Terminal Torque
Terminal Protection Degree
480Y/277VAC
0.3-25A: 1 pole - 42VDC; 2 Pole - 80VDC
30-60A: 1 pole - 24VDC; 2 Pole - 60VDC
0.3-60A (RC): 10kA with UL-listed
RK5 back-up fuse or MCCB
0.3-10A (RC): 10kA; 13-60A (RC): 5kA
no branch circuit protection required
0.3-63A (RC): 10kA
40°C (104°F)
-25°C to 55°C (-13°F to 131°F)
-40°C to 70°C (-40°F to 158°F)
Top: 18-3 AWG; Bottom: 18-2 AWG (Line/Load reversible)
20 lb.in.
IP20
Tripping time t
10
4
1
0.4
10
-1
4x10
-2
Seconds
10
-2
4x10
-3
10
-3
1
2
3
4 5 6 8 10
20
40
100
Multiple of Rated Current
Standard Dual
Connection Terminal
All parts are ring tongue compatible.
short circuit Withstand ratings for v-ea manual motor controller
Trip
Curve
all
all
all
all
Backup
Protection
Amp Range
0.3 - 10A
12 - 30/32A
40 - 50A
60 / 63A
UL-Listed
RK5-Fuse
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
UL-Listed
MCCB
up to 10kA
4xRC*
min 15A, max 70A
4xRC*
max 125A
4xRC*
max 200A
4xRC*
max 250A
No BCP
Required
up to:
10kA
5kA
5kA
5kA
Ring
tongue
Box
clamp
*up to nearest rated current