https://www.phoenixcontact.com/hq/products/2905140
Hybrid motor starter - ELR H5-IES-PT/500AC-9-IFS - 2905140
Please be informed that the data shown in this PDF Document is generated from our Online Catalog. Please find the complete data in the user's
documentation. Our General Terms of Use for Downloads are valid
(http://phoenixcontact.com/download)
Networkable hybrid motor starter for reversing of 3~ AC motors up to 500 V AC and 9 A output current, with
adjustable overload shutdown, emergency stop function to SIL 3 / PL e and push-in connection, DIN rail
connector provided.
Why buy this product
22.5 mm wide
Safety level according to IEC 61508-1: SIL 3, ISO 13849: PL e
Reduction in wiring
Space saving
Long service life
3-phase loop bridges
Adjustable current for bimetal function
Low-wear switching
Key Commercial Data
Packing unit
GTIN
GTIN
Custom tariff number
Note
4046356920483
85371099
Made to Order (non-returnable)
1 STK
Technical data
Dimensions
Width
Height
Depth
22.5 mm
99 mm
114.5 mm
Ambient conditions
Ambient temperature (operation)
Ambient temperature (storage/transport)
-5 °C ... 60 °C (observe derating)
-40 °C ... 80 °C
11/15/2016 Page 1 / 5
https://www.phoenixcontact.com/hq/products/2905140
Hybrid motor starter - ELR H5-IES-PT/500AC-9-IFS - 2905140
Technical data
Ambient conditions
Degree of protection
IP20
Device supply
Rated control circuit supply voltage U
S
Control supply voltage range
Rated control supply current I
S
Protective circuit
24 V DC
19.2 V DC ... 30 V DC
60 mA
Reverse polarity protection Parallel polarity protection diode
Surge protection
Input data
Input name
Note
Rated actuating voltage U
C
Rated actuating current I
C
Switching threshold
Switching level
Protective circuit
Typical turn-off time
Enable input
The enable input is compatible with signals with blanking (semiconductor
output signals with test pulse with max. 3 ms duration),
unblanking pulses of max. 4 ms are tolerated without adversely
affecting the safety function.
24 V DC
7 mA
9.6 V (“0” signal)
19.2 V (“1” signal)
< 5 V DC (For EMERGENCY STOP)
Reverse polarity protection
< 30 ms
Output data load output
Output name
Rated operating voltage U
e
Operating voltage range
Mains frequency
Load current range
Trigger characteristic in acc. with IEC 60947-4-2
Cooling time
Rated operating current at AC-51
Rated operating current at AC-53a
Leakage current
Protective circuit
AC output
500 V AC
42 V AC ... 550 V AC
50 Hz
60 Hz
1.5 A ... 9 A (see to derating)
Class 10A
20 min. (for auto reset)
9A
7A
0 mA
Surge protection Varistor
Overspeed tripping
Operate threshold
Response time
> 60 A
< 0.5 s
General
Switching frequency
Mounting position
≤ 2 Hz (Load-dependent)
vertical (horizontal DIN rail, motor output below)
11/15/2016 Page 2 / 5
https://www.phoenixcontact.com/hq/products/2905140
Hybrid motor starter - ELR H5-IES-PT/500AC-9-IFS - 2905140
Technical data
General
Assembly instructions
Operating mode
Maximum power dissipation
Minimum power dissipation
Operating voltage display
Status display
Indication
alignable, for spacing see derating
100% operating factor
7W
0.88 W
Green LED
Yellow LED
Red LED
Connection data, input side
Connection name
Connection method
Stripping length
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Control circuits
Push-in connection
10 mm
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
Connection data, output side
Connection name
Connection method
Stripping length
Conductor cross section solid
Conductor cross section flexible
Conductor cross section AWG
Load circuit
Push-in connection
10 mm
0.2 mm² ... 2.5 mm²
0.2 mm² ... 2.5 mm²
24 ... 14
Insulation characteristics
Rated insulation voltage
Rated surge voltage
Overvoltage category
Degree of pollution
Designation
Insulation
Designation
Insulation
550 V
6 kV
III
2
Insulation characteristics between the control input and control supply
voltage, and auxiliary circuit to the main circuit
Safe isolation (IEC 60947-1)
Isolation characteristics between the control input and control supply
voltage to auxiliary circuit
Safe isolation (IEC 60947-1) in the auxiliary circuit ≤ 300 V AC
Safe isolation (EN 50178) in the auxiliary circuit ≤ 300 V AC
Approvals/conformities
Safety Integrity Level according to IEC 61508
Category acc. to EN ISO 13849
Performance level according to ISO 13849
ATEX
≤ 3 (Safe shutdown)
2 (Motor protection)
3 (Safe shutdown)
e (Safe shutdown)
II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
11/15/2016 Page 3 / 5
https://www.phoenixcontact.com/hq/products/2905140
Hybrid motor starter - ELR H5-IES-PT/500AC-9-IFS - 2905140
Technical data
Approvals/conformities
EU-type examination certificate
UL certificate
PTB 15 ATEX 3000
NLDX.E228652
NRNT.E172140
UL data
SCCR
FLA
Group installation
100 kA (480 V AC (fuse: 30 A class CC/30 A class J (high fault)))
5 kA (480 V AC (fuse: 20 A RK5 (standard fault)))
7.6 A (480 V AC)
20 A (class RK5, SCCR 5kA (480 V AC), 24 - 14 AWG max. solid and
stranded)
30 A (class CC or J, SCCR 100kA (480 V AC), 24 - 14 AWG max, solid
and stranded)
Category code
Horsepower ratings
NLDX / NRNT
2 hp (120 V AC / 208 V AC)
5 hp (277 V AC / 480 V AC)
Standards and Regulations
Designation
Standards/regulations
Standards/regulations
IEC 60947-1
EN 60947-4-2
IEC 61508
ISO 13849
ATEX
II (2) G [Ex e] [Ex d] [Ex px]
II (2) D [Ex t] [Ex p]
Environmental Product Compliance
China RoHS
Environmentally Friendly Use Period = 50
For details about hazardous substances go to tab “Downloads”,
Category “Manufacturer's declaration”
Drawings
Block diagram
Load current [A]
Reset
-
EN-
EN+
+
Enable
Logic
µP
1/L1
3/L2
5/L3
2/T1
4/T2
6/T3
9
8
7
6
5
4
3
2
1
0,18
0
50
60
70
Ambient temperature [°C]
= aligned with > 20 mm spacing
= aligned without spacing
10
20
30
40
Diagram
T-BUS
Derating diagram
11/15/2016 Page 4 / 5
https://www.phoenixcontact.com/hq/products/2905140
Hybrid motor starter - ELR H5-IES-PT/500AC-9-IFS - 2905140
Approvals
Approvals
Approvals
UL Listed / UL Listed / cUL Listed / cUL Listed / IECEE CB Scheme / cULus Listed
Ex Approvals
Approval details
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 228652
UL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 172140
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 172140
cUL Listed
http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/index.htm FILE E 228652
IECEE CB Scheme
http://www.iecee.org/ DE1-56580
cULus Listed
Phoenix Contact 2016 © - all rights reserved
http://www.phoenixcontact.com
11/15/2016 Page 5 / 5