One use and one standby constant pressure water supply frequency conversion speed control circuit b

Source: InternetPublisher:同住地球村 Keywords: Control circuit constant pressure water supply frequency conversion speed control Updated: 2021/11/30

25. One use and one backup<strong>Constant pressure water supply</strong>Frequency control<strong>Control circuit</strong>b.gif

The soft start control circuit of the fire pump (one in use and one in standby) using FSR1000X soft starter is shown in Figure 5-26. When the transfer
switch 1SA is placed in the automatic position, one of the two fire pumps is running and the other is in standby. The two pumps are standby for each other
. After an operation failure, the standby pump is automatically put into operation immediately. When 1SA is placed in the manual position, both pumps can be operated manually and independently. The time relay
(KT) delay setting value is greater than the soft start time of a single unit.
    In the figure, 1 and 2 are bypass relay terminals ; 3 and 4 are fault output terminals; 7 is instantaneous stop input terminal; 8 is soft stop
input terminal; 9 is soft start input terminal; 10 is common contact input terminal (COM ); Il is the ground terminal (PE);
12 and 13 are the control power input terminals .


EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号