One use and one standby constant pressure water supply frequency conversion speed control circuit b
Source: InternetPublisher:同住地球村 Keywords: Control circuit constant pressure water supply frequency conversion speed control Updated: 2021/11/30
The soft start control circuit of the fire pump (one in use and one in standby) using FSR1000X soft starter is shown in Figure 5-26. When the transfer
switch 1SA is placed in the automatic position, one of the two fire pumps is running and the other is in standby. The two pumps are standby for each other
. After an operation failure, the standby pump is automatically put into operation immediately. When 1SA is placed in the manual position, both pumps can be operated manually and independently. The time relay
(KT) delay setting value is greater than the soft start time of a single unit.
In the figure, 1 and 2 are bypass relay terminals ; 3 and 4 are fault output terminals; 7 is instantaneous stop input terminal; 8 is soft stop
input terminal; 9 is soft start input terminal; 10 is common contact input terminal (COM ); Il is the ground terminal (PE);
12 and 13 are the control power input terminals .
- Binary clock design based on FPGA
- Design of water management system based on Internet of Things
- What components and functions does the battery management system consist of?
- Grain temperature measuring instrument circuit
- One control two constant pressure water supply frequency conversion speed control circuit b
- Infrared blind cane circuit diagram
- 220V AC mains directly drives small relay circuit_3
- Infrared light controlled toy tank circuit
- Box type electronic mousetrap circuit
- Low cost alarm circuit
- Flashing wall light control circuit
- Electronic rhythm control circuit
- Car window control circuit
- AM radio automatic search and trigger circuit
- CPU input and output and memory control circuit
- Photoelectric output control circuit
- Humidity detection box control circuit in greenhouse
- Steam iron temperature detection control circuit
- SHD301 single water supply pump frequency conversion speed regulation constant pressure water supply circuit a
- One control and one constant pressure water supply frequency conversion speed control circuit b