Fire pump (one in use and one in standby) soft start control circuit b
Source: InternetPublisher:公子李 Keywords: control circuit soft start start control Updated: 2020/09/17
The soft start control circuit of the fire pump (one in use and one in standby) using FSR1000X soft starter is shown in Figure 5-26. When the transfer
switch 1SA is placed in the automatic position, one of the two fire pumps is running and the other is in standby. The two pumps are standby for each other
. After an operation failure, the standby pump is automatically put into operation immediately. When 1SA is placed in the manual position, both pumps can be operated manually and independently. The time relay
(KT) delay setting value is greater than the soft start time of a single unit.
In the figure, 1 and 2 are bypass relay terminals ; 3 and 4 are fault output terminals; 7 is instantaneous stop input terminal; 8 is soft stop input
terminal; 9 is soft start input terminal; 10 is common contact input terminal (COM ); Il is the ground terminal (PE);
12 and 13 are the control power input terminals .
- How to use MFRC522 to create an RFID card reader security system
- How to build a self-driving drone
- One control two constant pressure water supply frequency conversion speed control circuit b
- Secret code lock circuit
- Infrared light controlled toy tank circuit
- Slow logic pulse listener circuit diagram
- Sensor alarm circuit
- Chinese learning machine disk drive interface card circuit diagram circuit
- Automobile fuel tank level measurement circuit
- Chinese learning machine system board circuit diagram circuit 02
- Rural fish farming control circuit
- Water and electricity saving infrared control circuit
- Photocell amplification control circuit
- Photocell trigger control circuit
- Traffic traffic light control circuit
- CPU input and output and memory control circuit
- Small power electric heater temperature detection control circuit
- Step-down starting control circuit for starting multiple motors one by one
- Multi-place reversible stop, jog, start control circuit_1
- Start control circuit with phase sequence and phase loss protection