Modbus to Profinet gateway connects to Mitsubishi inverter Botu quick configuration

Publisher:superstar11Latest update time:2024-02-21 Source: elecfans Reading articles on mobile phones Scan QR code
Read articles on your mobile phone anytime, anywhere

This case will share how to use Xingda Easy Control's modbus to profinet gateway (XD-MDPN100) to connect Siemens 1200 series plc and realize the 485 communication compatibility conversion of Mitsubishi inverter to modbusTCP communication. By configuring in Botu, we can achieve connection and communication between devices. image.png

First, we need to install the Xingda Easy Control Modbus to Profinet Gateway (XD-MDPN100) and the required software. Then, physically connect the gateway to the Siemens 1200 PLC. Ensure the normal operation of the device by properly connecting the network cable and power supply
.
image.png

Next, we need to configure the software: Open Botu and add PLC
image.png

Modify the IP address of the PLC. The IP address of this machine should be in the same network segment as the PLC.
image.png

Load the modbus to profinet gateway GSD driver file
image.png

Find the new MDPN driver in the GSD file hardware directory and select it
image.png
image.png

Connect the Modbus to Profinet gateway network port to the 1200plc network port
image.png

Modify the IP address and device name of the modbus to profinet gateway, or assign it by default
image.png

Open the inverter manual. Set the inverter 09 communication parameters

1. The communication address is 09-00, and the setting range is 1-254. The factory value is 1.

2. The default parameter for 09-01 communication transmission speed is 9600. If the communication speed is too slow, it needs to be increased.

3. The communication format is 09-04. The communication formats are mainly the following:
image.png

Before normal communication, the communication speed and communication format of the PLC and each inverter in the system must be consistent.

Communication data structure, in this case, select communication No. 3 and set 8, N, 2 for RTU
image.png

Set up Modbus to Profinet gateway 485 Modbus communication parameter settings
image.png

1. Function code 03H: Read cache content
image.png

Example: Confirm the current state of the inverter by reading the value of address 2101H. The data in address 2101H of the inverter is mapped with QW10 in the PLC, and the state of the inverter is confirmed by judging Bit1-0. If Bit1-0 is 00, it means that the inverter is in the stopped state; if it is 11, it means that the inverter is in the running state.
image.png

2. 06H: Write data into the buffer
image.png

Assign values ​​according to the instructions of the inverter Modbus address. The inverter address 2000H corresponding to the PLC internal register is QW2. When QW204114 (binary 000100000010010010) is assigned, the inverter will run. If you want the inverter to stop A operation, you need to assign 4097 (binary 00100000000000001) to QW20.
image.png

Summarize:

This case study shares how to use Xingda Easy Control's modbus to profinet gateway (XD-MDPN100) to connect to Siemens 1200plc and achieve Mitsubishi inverter 485 communication compatible to modbusTCP communication. During the configuration process in Botu, we established a stable and reliable connection and communication channel by correctly setting the parameters of each device. This provides an effective solution for the upgrade and optimization of industrial automation systems. Through such a configuration, we can better control and monitor the operation of the equipment and achieve a more efficient, reliable and safe industrial production process.


Reference address:Modbus to Profinet gateway connects to Mitsubishi inverter Botu quick configuration

Previous article:How do input and output inverter filters differ?
Next article:Siemens PLC floating point program case sharing

Latest Embedded Articles
Change More Related Popular Components

EEWorld
subscription
account

EEWorld
service
account

Automotive
development
circle

About Us Customer Service Contact Information Datasheet Sitemap LatestNews


Room 1530, 15th Floor, Building B, No.18 Zhongguancun Street, Haidian District, Beijing, Postal Code: 100190 China Telephone: 008610 8235 0740

Copyright © 2005-2024 EEWORLD.com.cn, Inc. All rights reserved 京ICP证060456号 京ICP备10001474号-1 电信业务审批[2006]字第258号函 京公网安备 11010802033920号