Extract all alarm data of power environment equipment from the power environment network management system, convert it into a unified data storage format, and submit it to the centralized alarm monitoring system for unified processing and presentation. The main functions that need to be implemented are as follows: (1) Data acquisition: First, it is necessary to adopt a communication protocol that is compatible with the object to build a data acquisition channel. Secondly, it is necessary to select a data acquisition method that is compatible with the acquisition interface characteristics to ensure that the required data is collected correctly. (2) Alarm judgment: It is necessary to design a mechanism to determine whether the currently collected alarm is a new alarm, an already collected alarm (that is, an alarm that already existed at the time of the last collection) or a restored alarm, and mark it, and then other functions will further process it. (3) Data format conversion: The original alarm data format collected from the object has strong heterogeneity and must be converted into a unified standardized format before it can be processed and applied. The main attributes of normalized data include: alarm ID; alarm source area and profession; alarm source network management system name and network element name; network element type; multi-layer alarm location description information - such as rack/frame/board slot/module/port/link, etc.; alarm type; alarm level; alarm trigger time; alarm details; and alarm status flag.